WF—U-v ————~— ‘5..- :' ‘ 1‘3 ~< W .3 3 . :_. -J"< ‘yf‘ n‘k» 4": ~ ,1 " .242? J". xx. ‘5 :1": I 1x ". “V I?“ ' m . $51 #3:}, '3: r I 1. 4) '7 “3| .1 l 3" i '9»: > 7 ? 1: ‘ ‘.. 1:71” w 3 .g 1 "at 't‘ > i1 1 3‘3?" 4 4 4L a 5 . 9‘? 5r l Aw -, . .12 W fir} ‘ "A .' ‘11} 1... '1 >I 1 "‘31 ‘“Es . 1! k3"; 1‘ a«' 9‘3: 0 xi»? IA. 11 ,1. w l' «1.1.4. , Q’Q‘k; ‘1’ ‘” r l 1.. ‘ 11.1.11 $1,119,111 {1 '1 v o 1'! J 1 . . ,1 filialg§él ‘0?” d V “ ' «31.:- v as, + - n‘ I “'ll‘ . _ tn: fifilfi'ii “9.1 I 13.94. ,1... _ "'2’ , n ,i ’1‘ ' ’ x 13 i , I! wfi‘ 5mg :1 1‘. . J 3&1» '2}, ~: ”K -‘ 5411);“. '.'~‘;," «T 2’35? - .‘ , pg ‘ 1 - c.1' L ‘ I ‘1'; ' J 1 4336352; ' W 113 5;? VP “‘4: u .~ . A big—€11.55. - ‘kmwgb FUR? - {w 55:21' 1 M. a :l‘Af: i"‘." :5 Jaw: ( * 45;}. 1p wr'Sfi’fi ‘12-’13; .‘ "NW1?! ‘ 1 ' ,r' .39— 1 1-54.. Q 1 I figs?! Wu “Wk: ‘ ' I 1 ‘ “if" ‘ ' {A . ' .1 ‘7, {$3117 , 235': 1 I 1'4“ 1’7"?” '7 ‘m‘ . WM 51 1‘" ' 1, *1 fir .Z" . ‘“ w a. P AM» , “or :1; ~ ‘1 .“ A 1 i: ”if,“ f ‘ ) ‘ It .- w 1, 9&1,» .r 14” £5 2 PL 1' 1. 1.1 .1 :J .3 “ '4": " 1 my . . . WW? - .1 . ’15'3‘,~,-\?2i€452433fi . ,1 I»! - 1 ~.;- 1 3 ‘1%.;J:=.a.~\-' Mr 1.5m!» [TY iii‘i ‘ \\‘i\\ W liliiiiiili" iii a H l 3 1293 01409 9372 ii This is to certify that the dissertation entitled Analysis of Neutral-to-Earth Voltage Characteristics along Rural Electric Power Distribution Systems through Computer Simulation and Field Testing presented by (hanging Li has been accepted towards fulfillment of the requirements for Ph.D. degree in Agricultural Engineering QMWW C5510} . ' v Major professor 3/ K/fif MSU is an Affirmative Action/Equal Opportunity Institution 0- 12771 ____—_-—___._—._—-——__ LIBRARY MIchlgan State UniversIty PLACE N RETURN BoxwmmmhMMMywm TO AVOID FINES Mum on or bdon duo duo. DATE DUE DATE DUE DATE DUE MSU IoAn Affirmative Adm/Emu Oppommlly Imam mm: ANALYSIS OF N EUTRAL—TO-EARTH VOLTAGE CHARACTERISTICS ALONG RURAL ELECTRIC POWER DISTRIBUTION SYSTEMS THROUGH COMPUTER SIMULATION AND FIELD TESTING By Changming Li A DISSERTATION Submitted to Michigan State University in partial fulfillment of the requirements for the degree of DOCTOR OF PHILOSOPHY ‘6 Department of Agricultural Engineering 1994 ABSTRACT ANALYSIS OF NEUTRAL-TO-EARTH VOLTAGE CHARACTERISTICS ALONG RURAL ELECTRIC POWER DISTRIBUTION SYSTEMS THROUGH COMPUTER SIMULATION AND FIELD TESTING By Changming Li The multi-grounded rural electric power distribution systems in the U. S. can produce neutral-to-earth voltage (NEV) on a dairy farm which may affect milk production of a dairy cow. In this study, computer simulation models were developed and farm field tests were conducted to facilitate the investigation and analysis of this NEV phenomenon. The computer models of nearly 4.3 kilometers long, 4.8 kV rural power distribution systems simulated the NEV changes arising from high resistance segments in the neutral of the primary line, primary heavy loading demand, substation and other ground resistance changes, different levels of the neutral line grounding, primary operating voltage- change, secondary ground faults and primary phase-to-earth faults. Based upon the analysis of the simulation results, guidelines were established for power suppliers to identify the sources of NEV originating from the parameter changes of the power distribution system. It is expected that the overall NEV is substantially lower along the electric power distribution system of a balanced three-phase four-wire Yo/Yo circuit than that of the single-phase. The farm field tests revealed the NEV gradient distribution near the ground electrode systems on the primary and secondary sides of the neutral isolated distribution transformer. The NEV gradient which the isolated secondary ground electrode coupled from the primary side ground system was determined and analyzed. The equivalent circuit of the isolated secondary ground system was developed to study the parameters that influence the neutral separation. Low farm grounding system resistance to earth is important for effective neutral separation. Increased separation distance between the primary and secondary ground rods is a factor for separation effectiveness increasing. Resistivity of the soil is also an important parameter. The low resistance of the isolated farm ground will result in low NEV on farm. In memory of the author’s mother iv ACKNOWLEDGMENTS I would like to express my deepest gratitude to Dr. Truman C. Surbrook, advisor and friend, for his academic guidance, moral encouragement and technical support since 1988 throughout my master’s and doctoral programs. His fruitful cooperation with Michigan Consumers Power Company has made this study possible financially. I would like to extend my cordial thanks to Dr. Larry J. Segerlind, Dr. H. Roland Zapp and Dr. Howard L. Person for their serving on my Ph. D. guidance committee. Their helpful academic guidances and moral encouragements are greatly appreciated by the author. Special thanks also goes to the faculty, staff and other graduate students of the Department of Agricultural Engineering for their assistance and cooperation in the recent years. A very special thanks goes to my parents and all of my family members for their expectation, encouragement, understanding and moral support from the remote China. Special thanks goes to the N ingxia T.V. University, China for letting me attend the graduate school in the United States, and for its subsequent moral encouragement of me. TABLE OF CONTENTS LIST OF FIGURES ........................................... ix LIST OF TABLES .......................................... xvii I. INTRODUCTION ...................................... 1 II. LITERATURE REVIEW ....................................... 5 2.1 Stray Voltage and Electric Current Effect on Dairy Cows ........... 6 2.2 Possnble Sources of the Farm N eutral-to-Earth Voltage ........... 14 2.3 Field Test and Diagnosis of Farm Neutral-to-Earth Voltage ....... 21 2.4 Mitigation of Farm N eutral-to-Earth Voltage Problem ............ 24 III. OBJECTIVE .................................. . ......... 31 IV. METHODOLOGY ..................................... 34 4.1 Computer Simulations of Primary N eutral-to-Earth Voltages ...... 34 4.1.1 The DC Single-Phase Distribution Simulation Model ....... 34 4.1.2 The AC Single-Phase Electric Power Distribution Model . . . .40 4.1.3 The AC Three-Phase Electric Power Distribution Model . . . .43 4.2 Simulation of Abnormal Conditions along the Distribution line ..... 45 4.2.1 Neutral Conductor Resistance Change .................... 45 4.2.2 Heavily Loaded Power Line on Farm ..................... 46 4.2.3 The Distribution System Ground Resistance Calculation . . . . 47 4.2.4 Substation Grounding Resistance Change ................. 49 4.2.5 Neutral-to-Earth Resistance Reduction ................... 49 4.2.6 Primary Operating Voltage Level Change ................ 50 4.2.7 Secondary Earth Fault .................................. 52 4.2.8 Primary Phase-to-Earth Fault ............................ 54 4.3 Field Tests of Neutral-to-Earth Voltage Gradient ................ 57 4.3.0 Data Collection of Voltage and Resistance of Ground Rod . .58 4.3.1 Test of NEV Gradient Distribution, Primary One Ground Rod ............................... 61 4.3.2 Test of NEV Gradient Distribution, Primary Two Ground Rods .............................. 62 4.3.3 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod Without Farm Ground Connection ................... 63 4.3.4 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod With Farm Ground Connection ..................... 65 4.3.5 Verification of the Neutral Isolation Circuit Model ......... 67 V. RESULTS and DISCUSSION ............................ 70 5.1 Results and Analysis of NEV Computer Simulation .............. 70 5.1.0 Normal Operational Condition .......................... 70 5.1.1 Neutral Conductor Resistance Change .................... 75 5.1.2 Heavily Loaded Power Line on Farm ..................... 83 5.1.3 The Distribution System Ground Resistance Calculation . . . . 90 5.1.4 Substation Grounding Resistance Change ................. 98 5.1.5 Neutral-to-Earth Resistance Reduction .................. 103 5.1.6 Primary Operating Voltage Level Change ............... 111 5.1.7 Secondary Earth Fault ................................. 114 5.1.8 Primary Phase-to-Earth Fault .......................... 130 5.2 Guidelines to Identify NEV along the Distribution Systems ....... 139 5.3 Field Tests of Neutral-to-Earth Voltage Gradient ............... 141 5.3.1 Test of NEV Gradient Distribution, _ Primary One Ground Rod ............................. 142 5.3.2 Test of NEV Gradient Distribution, Primary Two Ground Rods ............................ 154 5.3.3 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod Without Farm Ground Connection ................. 164 5.3.4 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod With Farm Ground Connection .................... 169 5.3.5 Verification of the Neutral Isolation Circuit Model ........ 174 5.3.6 Parameters Influencing Effectiveness of Neutral Separation .................................... 188 VI. CONCLUSION ....................................... 201 APPENDIX ................................................ 206 REFERENCES ............................................ 224 Figure 1. Figure 2. Figure 3. Figure 4. Figure 5. Figure 6. Figure 7. Figure 8. Figure 9. Figure 10. Figure 11. LIST OF FIGURES Page Behavioral and milk production responses to increasing current levels ................................................. 8 Circuit Model for Estimation of Effect of Neutral Isolation on N eutral-to-Earth Voltage (Althouse, 1990) ...................... 29 Transition Design for Equipotential Planes on Farm .............. 30 DC circuit model for single-phase electrical distribution system (input voltage 4,800 V) ....................................... 35 AC circuit model for single-phase electrical distribution system (input voltage 4,800 V) ....................................... 41 AC circuit model for three-phase four-wire wye connection (Yo/Yo connection) distribution system (4800 V for each phase-to-neutral voltage) ...................................... 44 DC circuit model for single-phase electrical distribution system with secondary earth fault simulated ............................ 53 DC circuit model for single-phase electrical distribution system with primary phase-to-earth fault simulated ..................... 55 AC circuit model for three-phase four-wire wye connection (Yo/Yo connection) distribution system (4800 V for each phase-to-neutral voltage) with phase A to earth fault simulated ..... 5 6 A variable transformer was used to drive electric current into the earth at the test primary ground rod ......................... 59 The 40 x 40 Feet Square Shaped Test Plot for NEV Gradient Testing, Primary One and Two Ground Rods .................... 60 Figure 12. Figure 13. Figure 14. Figure 15. Figure 16. Figure 17. Figure 18. Figure 19. Figure 20. Page The 4 x 10 Feet Square Shaped Test Plot for NEV Gradient Testing, Isolated Primary and Secondary Ground Systems ......... 64 A secondary isolated ground rod and farm grounding system were established to an area away from influence of earth voltage gradients from other electrical systems ................... 66 The physical quantities measured in the neutral separation circuit model ................................................ 69 Profile of the neutral-to-earth voltage along the primary distribution line from substation (node 1) to 57th node for the DC single-phase base model .......... , ...................... 71 Profile of the neutral-to-earth voltage along the primary distribution line from substation (node 1) to 57th node for the AC single-phase base model ................................ 73 Neutral-to-earth voltage profile comparison between the simulations of single-phase AC and DC models .................. 74 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable neutral conductor resistance RD9 between node 9 and node 10 and a normal customer load of 3A at node 9 (single-phase DC model simulation) ........................................ 76 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 5 7th node with variable neutral conductor resistance RD33 between node 33 and node 34 and a normal customer load of 3A at node 33 (single-phase DC model simulation) ........................................ 77 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 5 7th node with variable neutral conductor resistance RD56 between node 56 and node 57 and a normal customer load of 3A at node 57 (single-phase DC model simulation) ............................ 79 Figure 21. Figure 22. Figure 23. Figure 24. Figure 25. Figure 26. Figure 27. Page The circuit connection to study the neutral-to-earth voltage changes resulting from changing the neutral conductor resistance RD9, RD33 and RD56 in three different representative locations along the line at normal load demand condition (3 A load) .......................................... 81 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 404-9 (single-phase DC model simulation) .................................................. 84 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 416-33 (single-phase DC model simulation) .................................................. 86 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 428-57 (single-phase DC model simulation) ................................................. 88 The test circuit to determine the system resistance from the farm at node 33 ........................................... 93 The simulation plot of changes of the distribution system ground resistance (Thevenin Equivalent Resistance) and Thevenin Equivalent Open Circuit Voltages at the location of node 33 to earth as well as neutral-to-earth voltage at node 33 with the resistances increased from 0.086 ohm to 100 ohms in the neutral line segments RD4, RD8, RD12, RD16, RD20 RD56, respectively in the DC circuit model ............................ 95 The circuit connection to determine the changes of the distribution system ground resistance (Thevenin Equivalent Resistance) and Thevenin Equivalent Open Circuit Voltages at the location of node 33 to earth as well as neutral-to-earth voltage at node 33 with the resistances increased from 0.086 ohm to 100 ohms in the neutral line segments RD4, RD8, RD12, RD16, RD20 RD56, respectively ................................... 96 Page Figure 28. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable substation resistance RS (single-phase DC model simulation) .................................................. 99 Figure 29. The substation Thevenin equivalent open circuit voltage is divided in series by the substation ground resistance and the system Thevenin equivalent resistance at this location ............ 104 Figure 30. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. ground resistance RFG33 change at node 33. (single-phase DC model simulation) ........................................... 105 Figure 31. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. ground rod number increasing along the entire system (single-phase DC model simulation) ........................... 110 Figure 32. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case 4.8 kV operating voltage vs. 2.4, 7.2 and 26.4 kV operating voltages (single-phase DC model simulation) .................. 112 Figure 33. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 33 (out-of-phase, single-phase DC model simulation) ............... 115 Figure 34. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 33 (in-phase, single-phase DC model simulation) ............................ 117 Figure 35. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 9 (out-of-phase, single-phase DC model simulation) ............... 119 Figure 36. Figure 37. Figure 38. Figure 39. Figure 40. Figure 41. Figure 42. Figure 43. Page Profile of the neutral-to-earth voltage along the primary distribution line from substation to 5 7th node with base case vs. variable secondary ground fault attached to node 9 (in-phase, single-phase DC model simulation) ............................ 121 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 57 (out-of-phase, single-phase DC model simulation) ............... 122 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 57 (in-phase, single-phase DC model simulation) ............................ 124 Neutral conductor and grounding electrode current with secondary out-of-phase ground fault attached at node 57 at the end of the distribution line .............................. 127 Neutral conductor and grounding electrode current with secondary in-phase ground fault attached at node 57 at the eitd of the distribution line .............................. 128 Profile of the neutral-tooearth voltage along the primary distribution line from substation to 57th node with an ungrounded phase conductor to earth fault at node 416 compared with the normal line (single-phase DC model simulation) ........................... 131 Profile of the neutral-to—earth voltage along the primary distribution line from substation to 57th node with 12 A phase conductor to earth fault at node 404, 416, or 428 compared with normal line (single-phase DC model simulation) .- ............... 133 Profile of the neutral-to-earth voltage along the three-phase primary distribution line from substation to 57th node with an ungrounded phase conductor (phase A) to earth fault at node 416A compared with the normal line (three-phase AC model simulation) ................................................. 135 Figure 44. Figure 45. Figure 46. Figure 47. Figure 48. Figure 49. Figure 50. Figure 51. Figure 52. Profile of the neutral-to-earth voltage along the three-phase primary distribution line from substation to 57th node with 12 A phase conductor (phase A) to earth fault at node 404A, 416A, or 428A compared with normal line (three-phase AC model simulation) ........................................ Three dimensional graphic plot of the neutral-to-earth voltage gradient distribution from single driven electrode rod (length unit is foot) .............................................. Equi-potential lines of the neutral-to-earth voltage gradient distribution from single driven electrode rod (length unit is foot) ....................................... Neutral-to-earth voltage gradient distributions from single driven electrode rod along four directions (length unit is foot) . . Comparison between theoretical value calculated from equation (5.3) and field measured value of neutral-to-earth voltage gradient distributions from single driven electrode rod along east direction (length unit is inch) ...................... Three dimensional graphic plot of the neutral-to-earth voltage gradient distribution from two electrode ground rods with 6 feet separation distance (length unit is foot) .................. Equi-potential lines of the neutral-to—earth voltage gradient distribution from two electrode ground rods with 6 feet separation distance (length unit is foot) ...................... Graphic plot of the neutral-to-earth voltage profile data comparison (per unit normalized) between one rod and two rods of primary ground systems along the north direction (length unit is foot) ....................................... Graphic plot of the neutral-to-earth voltage profile data comparison (per unit normalized) between one rod and two rods of primary ground systems along the other three directions (length unit is foot) .............................. xiv Page ...137 ...146 ...147 . . .149 ..152 ..157 ..158 . . .161 . . .163 Figure 53. Figure 54. Figure 55. Figure 56. Figure 57. Figure 58. Figure 59. Figure 60. The test circuit for the neutral-to-earth voltage gradient distribution resulting from one primary ground rod, and one secondary isolated ground rod without the farm grounding system connected .......................................... Three dimensional graphic plot of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) without farm ground connection (length unit is foot) .................. Equi-potential lines of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) without farm ground connection (length unit is foot) ....................... The test circuit for the neutral-to-earth voltage gradient distribution resulting from one primary ground rod, and an isolated secondary ground rod connected to a 5.24 ohm farm ground resistance ......................................... Three dimensional graphic plot of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) with farm ground connection resistance 5.2 ohm (length unit is foot) ...... Equi-potential lines of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) with farm ground connection resistance 5.2 ohm (length unit is foot) ............. Comparison between neutral-to-earth voltage gradient distributions (per unit normalized) from secondary isolated ground systems with and without farm ground connection along the direction of primary and secondary isolated connection line (length unit is foot) ........................................ The circuit model of Figure 14 of Section 4.3.5 is arranged vertically so that all quantities can be visualized more easily ..... Page .166 ..167 . .168 ..171 ..172 . .173 . .177 . 182 Figure 61. Figure 62. Figure 63. Figure 64. Figure 65. The circuit model of Figure 14 of Section 4.3.5 without farm ground system connection is arranged vertically so that all quantities can be visualized more easily ...................... Slightly altered form of the neutral separation circuit model (Althouse, 1990) .......................................... The ratio of farm neutral-to-earth voltage (EF) to primary ground rod neutral-to—earth voltage (Es) was plotted against the value of farm grounding system resistance to earth (R1,). The data was from Table 18 and Table 19 for two levels of primary grounding resistance ............................... The ratio of farm neutral-to-earth voltage (BF) to primary ground rod neutral-to-earth voltage (Es) was plotted against the value of farm grounding system resistance to earth (Rr)' The data was calculated from the circuit model in Figure 62 . . . . The ratio of farm neutral-to-earth voltage (Er) to primary ground rod neutral-to-earth voltage (Es) was plotted against the value of farm grounding system resistance to earth (RF) for 6 inch and 6 foot separation distance. The calculated data was from the circuit model in Figure 62 ...................... Page ..185 ..191 ..194 . . .197 ..199 Table 1. Table 2. Table 3. Table 4. Table 5. Table 6. Table 7. Table 8. LIST OF TABLES Page Resistance of various electrical pathways through the cow .......... 7 Parameters for Base DC Circuit Model in Figure 4 ............... 37 Some typical values of the ground resistances for the farm and residential distribution transformers on the field in the service area of the Consumers Power Company ......................... 42 Primary Current and Load Resistance, RRL and RFL, for Different Primary Voltage Simulations ......................... 51 Calculation results of the distribution system ground resistance from the four different representative locations along the single-phase DC distribution line model ......................... 91 The simulation data of changes of the distribution system ground resistance (Thevenin Equivalent Resistance) and Thevenin Equivalent Open Circuit Voltages at the location of node 33 to earth as well as neutral-to-earth voltage at node 33 with the resistances increased from 0.086 ohm to 100 ohms in the neutral line segments RD4, RD8, RD12, RD16, RD20 RD56, respectively in the DC circuit model ............................ 97 Numerical calculation results of substation system ground resistance, open circuit neutral-to-earth voltage, ground resistance and neutral-to-earth voltage of the single-phase DC distribution line model ........................ 102 Numerical calculation results of system ground resistance, open circuit neutral-to-earth voltage, ground resistance and neutral-to-earth voltage at mid-point of the single-phase DC distribution line model ....................................... 108 Table 9. Table 10. Table 11. Table 12. Table 13. Table 14. Table 15. Table 16. Table 17. Page Test measurement data of the neutral-to-earth voltage gradient distribution from single driven electrode rod (length unit is foot). . . 144 Test measurement data of neutral-to-earth voltage gradient distributions from single driven electrode rod along four directions .................................................. 148 Data comparison between theoretical value calculated from equation (5.3) and field measured value of neutral-to-earth voltage gradient distributions from single driven electrode rod along east direction (length unit is inch) ........................ 151 Test measurement data of the neutral-to-earth voltage gradient distribution from primary two electrode ground rods with 6 feet separation distance (length unit is foot) ........................ 155 N eutral-to-earth voltage test data (per unit normalized) from primary ground systems of two electrode rods along the north direction ................................................... 160 Test measurement data of the neutral-to-earth voltage profile data comparison (per unit normalized) between one rod and two rods of primary ground systems along the other three directions .................................................. 162 Test measurement data of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) without farm ground connection (length unit is foot) ............................... 165 Test measurement data of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) with farm ground connection resistance 5 .2 ohm (length unit is foot) .............. 170 Data comparison between neutral-to-earth voltage gradient distributions (per unit normalized) from secondary isolated ground systems with and without farm ground connection along the direction of primary and secondary isolated connection line ............................................. 175 Table 18. Table 19. Table 20. Table 21. Table 22. Table 23. Page Data for neutral separation test using one primary ground rod and one secondary ground rod with a six foot separation ......... 178 Data for neutral separation test using two primary ground rods and one secondary ground rod with a six foot separation ......... 179 Calculated values of grounding electrode and ground circuit resistances from data in Table 18 and Table 19 ................. 183 Data for neutral separation test of Althouse (1990) using one primary ground rod and one secondary ground rod with a six inch separation and six foot separation ........................ 189 calculated value of grounding electrode and ground circuit resistances from Althouse (1990) data in Table 21 ............... 190 Ground rod spacing, grounding electrode resistances, and ratio of secondary to primary ground rod neutral-to-earth voltage at the separated transformer location ............................ 196 I. INTRODUCTION The most prevalent rural electric power distribution systems in the United States are multi-grounded neutral systems. These are generally single-phase two-wire or three-phase three-wire or three-phase four-wire systems which are effectively grounded to provide for the power delivery with maximum safety and reliability. The multi-grounded distribution system under normal and abnormal operating conditions will produce neutral-to-earth voltage all along the distribution line. The neutral conductor is required by the National Electrical Safety Code (IEEE, 1990) to be connected to the earth by means of ground rods or similar means at four locations for each mile of the line. When electrical current flows along this grounded neutral conductor, a portion of the current will also flow through the earth back to the substation or source transformer, resulting in some neutral-to-earth voltage (NEV). Farm electrical systems are also multi-grounded and also produce the neutral-to-earth voltage. Under some abnormal operational condition (such as ground fault), the power distribution system of a farm can produce a substantially high level of neutral-to-earth voltage which bothers animals. A loose terminal or damaged insulation can lead to an on-farm electrical fault. 2 The neutral~to-earth voltage can affect animals in two different ways. In the way of a "touch voltage" or in the way of a "step voltage". The ”touch voltage" is a rise in potential of metal objects such as water pipes, stanchions and feeders contacted by animals making contact to the earth or through the floor to the earth. The "step voltage" is related to the voltage gradient measured horizontally on the earth’s surface particularly in close proximity to the ground electrode system. The "step voltage" is actually a voltage experienced by an animal between hooves making contact with the floor or earth. Both "touch voltage" and "step voltage" could present an electric shock to animals on farms when a complete current path is formed and the voltage is of sufficient level. Some dairy farmers complain that their cows’ milk production has been adversely affected by the electric shock due to the presence of this kind of voltage, often called stray voltage. Stray voltage is defined as (USDA, 1991) "A difference in voltage measured between two surfaces that may be contacted simultaneously by an animal.” In past years, research on neutral-to-earth voltage on dairy farms has made significant progress. However, the levels of neutral-to-earth voltage along a distribution line are not clearly understood in relation to grounding and ground resistance, loading demand, neutral resistance, ground fault and primary / secondary neutral isolation. Guidelines have not been available for efficient and accurate diagnosing and remedying distribution line abnormalities which cause elevated levels of neutral-to-earth voltage. The mechanisms of mitigation measures for 3 neutral-to-earth voltage on dairy farms have not been scientifically elucidated for extensive acceptance. These are very important issues discussed in this study. In the study of this dissertation, computer simulation models are developed and farm field tests were conducted to facilitate a thorough investigation and analysis of neutral-to-earth voltage levels along the rural electric power distribution systems. Computer models of 4.26 kilometers (2.65 miles) long, 4.8 kV rural power distribution systems simulate the neutral-to-earth voltage changes arising from high resistance segments in the neutral of the primary line, primary heavy loading at one point, substation and other ground resistance changes, different levels of the neutral-to-earth resistance, primary operating voltage change, secondary ground faults and primary phase-to-earth faults. Actual data from an operating distribution line is important to be considered, but controlled experiments are difficult to conduct and in some cases may create dangerous conditions. Computer simulation of a primary distribution system provides the opportunity to study conditions whose field data are not available or not practical or safe to obtain. Based upon the analysis of simulation results, guidelines need to be established for power suppliers to identify the sources of neutral-to-earth voltage originating from the parameter changes of the power distribution system. It is expected that the overall neutral-to-earth voltage is substantially lower along the electric power 4 distribution system of a three-phase four-wire Yo/Y0 connection than that of a single-phase line. It is expected that the equi-potential contour lines of the voltage gradient in the area of a single ground rod with a neutral-to-earth voltage will be a series of circular rings. When there is more than one ground rod the distribution of the voltage gradient is not exactly known. When a primary and secondary neutral are separated, the secondary ground rod at the transformer will likely be installed in the voltage gradient created by the primary neutral-to-earth voltage. This research will investigate the voltage gradient for a single ground rod and two ground rods with a neutral-to-earth voltage. It is expected that some of the primary neutral-to-earth voltage will appear on the secondary ground rod when the neutrals are separated. Past research indicates that the amount of neutral-to-earth voltage appearing on the secondary is very small. It is also believed that the farm grounding resistance-to-earth is an important parameter in determining the amount of primary neutral-to-earth voltage which will appear on the secondary neutral. A controlled study will be conducted in the field to investigate the influence of farm grounding resistance on the effectiveness of neutral separation as well as the influence of two primary ground rods as compared to a single ground rod. II. LITERATURE REVIEW Since early this century, extensive research has been conducted concerning the effect of electrical voltage and current on humans. The lethal threshold value of continuous alternating current through the human body was determined by several researchers. Based on the results of Dalziel’s studies (IEEE, 1986), 99.5% of all persons can safely withstand, without ventricular fibrillation, the passage of a current not exceeding a magnitude 1B (in amperes) for duration ts (in seconds) determined by the formula 13 = k ts-005. For so kg body weight, k=0.116. Since the 1960’s, extensive research has also found the effect of the electric voltage and current on animals as well as general indications of levels of voltage that bothered cows. Phillips (1963, 1969) and Woolford (1971, 1972) studied the effects of voltage and current on milk production (New Zealand). In past years, significant research concerning farm stray voltage has also been conducted in the United States. Since the late 1970’s, the major concerns of stray voltage researchers in the U. S. and other countries were focused on: (1) How, and to what extent, does the neutral-to-earth voltage affect cows’ milk production? (2) What is the source of the stray voltage? How is the neutral-to-earth voltage produced? What is its changing trend under the 6 various operational conditions of an electrical system? (3) Is it possible to mitigate or lower neutral-to-earth voltage to an insignificant level on a farm? If yes, how? The literature will be reviewed with respect to these issues. 2.1 Stray Voltage and Electric Current Effect on Dairy Cows U. S. Department of Agriculture (USDA) summarized the Effects of Electrical Voltage/Current on Farm Animals in Agricultural Handbook No. 696 in 1991. This summary includes the following: 1. Today, stray voltage/current is a recognized phenomenon. Cows are considered to be more susceptible to stray voltage / current than humans because cows have lower body impedances and lower contact impedances (cows are nearly always in contact with moisture in the farm animal environment). There are several pathways for current to pass through the cows and the lowest impedance pathway is from the mouth to the hooves. Table 1 shows the resistances of various electrical pathways through the cow (USDA, 1991). 2. The primary impact of stray voltages /currents on milk production involves cow’s behavior changes rather than physiological changes. Good milk yield can probably be maintained despite the presence of moderate levels of stray voltage / current if farming practices are good. 7 The effects of current (and voltage) on the cow’s behavioral response and milk production are shown graphically in Figure 1 (USDA, 1991). Table 1. Resistance of various electrical pathways through the cow Res-stances ct vanous electrical W W the cow‘ Rm Cm ‘ Mean Range My hmm___ .n; mu m (Ha m— Mouth to all hooves 70 350 323-393 60 cm a at. 1970 23 36l 244-52!»J so Naell et at. 1933 Mouth to te- hooves 23 as ass-776’ so Naell a at. m: Mouthtolrunthooves 23 624 new so Naeuaettm Front leg to re. leg 5 300 250-403 60 talcum. 1932 13 362 3024:: 60 wen-t a at. 1905 FM to M hooves 23 734 49641523 so Norell er .1. I903 Rumptoall homes 7 6” 411-130 50 Wall. 1975 Chainsaw 5 900 fill-1230 so Would”: 7 won 2 50 Mad. 1m remom 23 433 29:41? so Naelleul. ma Teutonllhoovu 28 594 402-933 60 Metal. I903 4 no ao-ttso 50 W a :1. I973 Testicular». 20 594 Mo”? 60 Naelleul. I903 Tantra-rm 20 014 593.1!“ 60 Noelle”. I903 mmnmm‘ 6 1320 too-1960 so Mud. 1973 7 two 7 so aniline et al. I963 vaccinating": :2 1700 mm to “mu-urns ‘mmwuomumr “mam ’MgapmnfalO-mm.amdmmmmmmmu ‘Mmflaow. (From USDA Agricultural Handbook No. 696) W'm 5000M. 1.0mm D I- 4 I- D None Perception Moderate Seven 1. u only ._.° I- I- 6 '1 1 ”P , n - 3 - 0 E . loamy .- .— g ‘ - . V... ‘ ”MID - 2 p ‘ E NW '0“ I" change In 5 d . .“l practicum m - - 3 2 " ...v'NeIouln I'M“ ? 1 I- 2 u ( production :ma _ _ O O 0 WWW Figure 1. Behavioral and milk production responses to increasing current levels. Voltages (right vertical axis) were estimated using a worst-case circuit impedance (500 ohms) and a more realistic impedance (1,000 ohms). (From USDA Agricultural Handbook No. 696) The detailed literature review which some of this summary is based upon follows next. Appleman and Gustafson (1985) classified the observed effects of stray voltage on dairy cows into four general areas: effect on milking performance and behavior; effect on herd health; effect on nutritional intake; and, effect on production. Nevertheless, it was reported that any negative effects of electrical shock on milk production or mammary gland health most likely were not directly related to shock, i.e., 9 physiological responses to shock were minimal and milk yield was generally maintained at normal levels during the shock period. However, the severe behavioral responses to shock usually caused management problems. In addition, the degree to which milk production would be affected depended on how dairy producers would deal with the abnormal behavior. Gustafson et al. (1985) indicated that the effect of a stray voltage on a dairy cow was influenced by many factors: (a) voltage magnitude and waveform; (b) the resistance of a cow’s body pathway; (c) condition of concrete, soil and metallic conductors affecting resistance to "true earth”; (d) resistance of the cow’s contact points; (e) resistance of the electrical pathway to the cow’s contact points; and (f) impedance of the source. When combined, these factors determine the current flow through the cow’s body. It is known that a current above some level flowing through the cow’s body directly affects the cow’s behavior or health. A voltage drives the current in the circuit with the cow body pathways as resistances. Norell et al. (1982) reported the electrical resistance data for eight pathways through a dairy cow. The mean resistances of a cow ranged from 359 to 877 ohms, with the lowest for a mouth-all hooves path. Some pathways were selected in order to model the common cow conditions on farms. For example: the pathway of front-to-rear hooves can be used to model the cows that stand or walk across an area of the barn or milking parlor where a floor voltage gradient exists; the pathway 10 of mouth-to-all hooves was to model the cows that bridged the gaps between metallic feeders or water bowls and ground; and the pathway of body-to-all hooves was to model the cows that bridged the gaps between metal pipeworks connected to the grounded neutral systems and concrete floor or earth. They found that the hoof-to-earth contact resistance was a large component of the pathway resistance but they did not evaluate the hoof-to-earth contact resistance quantitatively. So far, there has been little research reported on the quantitative analysis of animal contact resistance. Aneshansley and Czarniecki (1990) measured the complex impedances in Holstein cows (lst through 4th lactation) between 10 and 100,000 Hz. They reported that a circuit model developed for humans appears to be appropriate for cows. Currents delivered at frequencies about 1000 Hz were well above perception levels at 60 Hz but caused no behavioral response. , Gustafson et al. (1985) studied 3 dairy cow-body pathways’ behavioral sensitivity to DC and 30 seconds on-off AC current. They reported that the pathway front-to-rear hooves response rate (ratio of responding cows to total test cows) became statistically significant above 2.0 mA AC. Mouth-to-all hooves response rate became significant above 2 mA AC and 4 mA DC. Response rate for a body-to-all hooves pathway with currents from 0 to 7.5 mA AC and 0 to 9 mA DC were inconclusive. Appleman and Gustafson (1985) reported for AC 60 Hz source, the cow’s behavioral sensitivity threshold currents are different with the different body pathways, ranging from 0.75 to 7.1 mA. 11 Gustafson et al. (1985) reported that the cow’s behavioral sensitivity threshold to DC current was about 30 percent higher than AC. Drenkard et al. (1985) did experiment which exposed six multiparous non-pregnant Holstein cows to electric current to assess its effects on cow’s behavior, health, milking performance, and endocrine responses. Three treatments (0, 4 and 8 mA) were applied in a changeover design over three consecutive one week periods. They concluded that behavioral responses to regularly applied AC current treatment decreased in frequency and intensity with time. Changes of milking performance and milk composition were not significant. Changes of milking related cortisol responses during 8 mA current experiment were significant. Oxytocin release was delayed during 8 mA treatments. Current treatments did not affect prolactin. Gorewit et al. (1984) summarized that hormones play critical roles in regulating milk synthesis and milk removal. Oxytocin is a hormone stored and released from the posterior pituitary and is responsible for milk ejection of cows. Oxytocin, prolactin (PRL) and cortisol are normally released during milking in cows. Aneshansley et al. (1987) reported their experiment which had fifteen first-calf heifers and fifteen 2nd to 4th lactation cows exposed to five voltages (0-4 volts) while drinking. Exposure was continuous for 21 days. They reported no significant difference in water consumption, feed intake, milk production, or concentration of fat or protein in the milk. Drinking behavior (number of drinks / day and time /drink) did change significantly. 12 Aneshansley et al. (1990) and Gorewit et al. (1990) did the controlled study to 40 Holstein cows with stray voltage. Three groups of 10 Holstein cows (2nd-5th lactation) were exposed to voltage (1, 2, or 4 V) at waterers over their full lactation. A fourth group received no voltage. They reported that these voltages applied did not influence animal health or reproductive performance. They also reported that no significant reduction in milk production or milk quality was found when comparing "no-voltage" cows to cows that received voltage. Water intake was significantly higher for the cows exposed to 4 volts. Over the past years, most studies of the cows’ behavioral sensitivity response have been conducted with continuous, fixed and steady state current /voltage levels and various duration. However, one area that has not been adequately studied is dairy cow sensitivity to short duration currents. Currence et al. (1987) used three durations ( 1, 10 and 100 cycles at 60Hz) of AC electrical current with the left front-left rear hoof pathway to determine the magnitude of short bursts of 60 Hz current that were required to cause a physical reaction in dairy cows. The conclusion was that the magnitudes of 60-Hz AC currents required to cause dairy cows to respond were essentially the same for current duration of 1.67 and 0.17 seconds (100 and 10 cycles at 60 Hz) with a value equal to about 3.5 mA (rms). The magnitude required for current duration of 0.017 second (1 cycles at 60 Hz) was approximately 50% higher. The similar tests were also given to twelve human volunteers to determine the magnitude of short bursts of 60 Hz current that were 13 required to cause their "perception" and "equal level of discomfort". The conclusion was that the difference in mean current magnitudes due to current duration were statistically insignificant. Gustafson et al. (1988) conducted the electric strength/duration experiments to six Holstein cows by using the square current wave-form (about 11 mA in height and 38 ms in width) to cows’ mouth-to-all hooves pathways. They processed their experimental data statistically to verify the model of Pearce et al. in 1982 and their own exponential model. They concluded that the model of Pearce et al. did not fit their experimental data as well as might be desired and their own statistical model was better. Their model was: IS = 11.02 x (0°16. Where Is was the current strength of the stimulation needed to evoke the response in mA and t was duration of stimulation in mS. In the empirical formula above, the time ranged from 0.1 to 300 m8 and the current strength ranged within 3 to 14 mA. Reinemann et al. (1994) conducted research to address the concern over possible effects of transient voltages and magnetic fields on dairy cows. Dairy cow behavioral response to transient voltages and magnetic fields was observed. The wave forms of the transient voltages applied were: 5 cycles of 60 Hz AC with a total pulse time of 83 m8; 1 cycle of 60 Hz AC with a total pulse time of 16 m8; and 1 cycle of an AC square wave (spiking positive and negative) of 2 ms duration. Alternating magnetic fields were produced by passing 60 Hz AC fundamental frequency with 2nd and 3rd harmonic and random noise components in metal structures around cows. The maximum magnetic 14 field associated with this current flow was in excess of 4 gauss. They reported that a wide range of behavioral sensitivity to transient voltages was observed among cows. Behavioral response levels from 24 cows to each transient exposure were normally distributed. No behavioral responses to magnetic fields were observed. 2.2 Possible Sources of the Farm Neutral-to-Earth Voltage Surbrook and Reese (1981) defined the terminologies regarding the farm stray voltage as follows: (1) Neutral-to-Earth Voltage -- A voltage difference measured between the neutral of an electrical system and the earth. Metallic structures and equipment bonded to the neutral will also be at a difference in potential from the earth. (2) Transient Voltage -- A voltage that is not constant. It can be a sudden voltage spike or a gradual rise and fall of the voltage. This voltage is usually measured between earth and the neutral. (3) Tingle Voltage -- A term sometimes used to describe a very slight voltage that causes a slight shock or tingle when encountered by a human. A 120 V supply may only cause a tingle if the person is well insulated. (4) Stray Voltage -- A general term often used to include all sources of voltages found on the farm that may be encountered by humans and animals between a metal object and the adjacent earth or floor. Surbrook and Reese ( 1981) traced the origins of farm stray voltage from two sources -- on-farm and off-farm. They indicated that common on-farm stray voltage sources were: (1) ground faults on the 15 farm; (2) voltage gradient across the ground or floor arising from wires faulted in the earth; (3) electric fencer wires shorting direct to equipment or inducing a charge in pipes and equipment; (4) grounding conductor intentionally used as a neutral and a neutral used as a grounding conductor; and (5) voltage drop on the secondary neutrals. Typical off-farm stray voltage sources were: (1) voltage drop on the primary neutral; (2) a ground fault on a neighbor’s property; and (3) a fault in primary equipment or a problem with primary grounding. Bodman et al. (1981) surveyed approximately 100 dairy farms in the State of Nebraska. They reported over 58% of the survey farms have the stray voltages in excess of 0.5 V and found that the primary causes of the stray voltages were poor electric system installation and maintenance procedures. Gustafson and Cloud (1982) indicated that in the field, several or possibly all of these sources would interact. However, unless the contribution from each source could be clearly distinguished and analyzed, successful diagnosis was difficult. So, a good understanding of the sources and their interaction, the electric nature of the problem, and the effects of the electrical characteristics of the system were important to proper diagnosis and solution. Gustafson and Cloud (1982) further proposed the solutions to stray voltage problems: (a) eliminate or minimize the voltage causing the problem; (b) isolate the voltage from any equipment in the vicinity of all potential animal contact points; or (c) install an equipotential plane that will keep all possible animal contact points at the same 16 potential. The solution or solutions selected depends on (a) the source or sources of the stray voltage; (b) the magnitude of the stray voltage; (c) the cost of alternative solutions; (d) the physical facilities involved; and (e) the policies of the power supplier. The solutions can be relatively simple if the problem is clearly diagnosed and the alternatives evaluated and explained to the farmer. Several researchers have contributed to the identification of the sources of the neutral-to-earth voltage in the past years based on experimental circuit measurement and circuit calculation by computer. Stetson et al. (1984) developed an analog model of the neutral-to-earth voltage in a single-phase distribution system. They used resistors, conducting wires, switches, and a DC power source to build up the physical circuit experiment model of a single-phase distribution system. Their analog used the DC power source to simulate the substation transformer and resistors to simulate the load transformers. The analog assumed that each connection between the neutral conductor and earth ground could be represented by a resistance between the conductor and true earth. True earth had zero resistance, and zero potential difference existed between any two true earth ground connections regardless of their physical spacing. By taking physical measurement of their circuit model, they revealed the neutral-to-earth voltage phenomenon associated with multi-grounded- single-phase distribution systems. Their analog could be used to demonstrate the effects on primary lines of magnitude and location of loads with respect to the substation, 17 poor neutral connections, and poor grounds. On the secondary lines the effects of poor connections, poor grounds, and undersized neutrals could be illustrated with two farmstead loads. These loads could be connected to illustrate the effects of loads in-phase and out-of-phase with the primary line, and the influence of one farm on another. The effect of separating primary and secondary neutrals could be illustrated. They reported their six demonstrations: (1) The effect of primary conductor resistance on the neutral-to-earth voltage demonstrated the influence of neutral wire size. The voltage increased as neutral conductor resistance increased. For the isolated line segment represented by the analog, the voltage was a maximum at the ends of the line and minimum at or near the center. (2) The effect of a high resistance at some location along the primary or secondary neutral conductor demonstrated the effect of a high-resistance splice or connection. The voltage drop across the high-resistance splice or connection was much higher than across any of the other neutral segments. (3) The effect of different neutral-to-earth resistance on neutral-to-earth voltage demonstrated the effect of good and poor grounding. Ground resistance changes could cause the neutral-to-earth voltage changes, but the effect was location-dependent. (4) The effect of connecting a farmstead neutral at different locations along the primary neutral demonstrated that the farm neutral-to-earth voltage could be location-dependent as well as farm-load-dependent. With no secondary neutral current, an off-farm source was responsible for the farm neutral-to-earth voltage. With both on-farm neutral and an 18 off-farm source, the phase relationship between the primary and secondary neutral currents and the line location affected the voltage on farm. (5) With identical neutral current at each farm and farms at the different taps, the interaction magnitude decreased as the distance between farms increased. (6) The effect of connecting or disconnecting the farmstead neutral from the primary neutral demonstrated connecting the primary and secondary neutrals sometimes reduced and sometime increased the measured neutral-to—earth voltage. They summarized that to solve the problem of excessive neutral-to-earth voltage, an orderly approach was essential because of the difficulties of analysis necessary to identify its source. Kehrle (1984) developed the DC circuit model of a 7.2 kV single-phase distribution power system to facilitate the analyses of the neutral-to-earth voltage on farm. The computer program of circuit simulation was used to perform the theoretical calculations and analyses of the neutral-to-earth voltage along the distribution line. Eight conclusions were reached. (1) The results obtained from the theoretical analyses showed many similarities to the measurement results of the DC physical analog model of Stetson et al. in 1984. (2) The effect of a neutral/ transformer grounding resistance was location-dependent. A significant reduction of the grounding resistance at a specific point resulted in a significant reduction of neutral-to-earth voltage at that point, and to a less extent elsewhere in the system. Also, the resistance changes made near the substation did not affect the general neutral-to-earth voltage over the entire line. However, when changes 19 were made at the end of the line, net voltage changes at that point were maximized. (3) The effects of a primary neutral conductor resistance was also location-dependent. Increasing the resistance of the neutral conductor in a segment located at the beginning of the line resulted in an increase of the neutral-to-earth voltage at all points along the line. Increasing the resistance in a segment located at the middle of the line resulted in a decrease of the neutral-to-earth voltage at some location ahead of that segment in the direction of the substation. An increase of neutral-to-earth voltage resulted at all points behind that segment in the direction toward the end of the line. However, an increase in the conductor resistance in a segment located at the end of the line did not have a significant effect along the line. (4) Changes made on the secondary neutral conductor resistance did not affect the primary neutral-to-earth voltage along the line. (5) Changing the load at one location resulted in a change of neutral-to-earth voltage at that point, but the change was much less significant as the distance increased away from that point. (6) The effect of varying the resistance of the substation grounding mat was more apparent at the substation and adjacent locations. (7) The effect of a primary ground fault was found to be location-independent. A sustained primary line to ground fault near the substation, or at the middle, or at the end of the line had the same effects on the neutral-to-earth voltage along the line. (8) The effect of a secondary ground fault was found to be location-dependent. The effect of a sustained secondary line to ground fault at a location was more apparent at that location than at the adjacent locations. 20 Surbrook et al. (1986, 1987) reported that the stray voltage was caused by voltage drop and ground faults and might have its origin in certain parameter changes of the primary electrical distribution system or in the customer’s secondary electrical system. The rms value of the neutral-to-earth voltage along a primary distribution line might be at a value of zero some distance from the substation, depending on the condition of the conductor resistances and of the loads. Gustafson (1985) used a computer program to find the neutral-to-earth voltages in a DC circuit model. Some of his findings revealed basic parameters that caused a rise in neutral-to-earth voltage levels. Three of his findings are as follows: (1) Increased neutral wire resistance resulted in the largest percentage effect (on the neutral-to-earth voltage) in the central portion of the distribution line. (2) Deterioration of splices in the primary neutral conductor can dramatically change the apparent resistance of the conductor. When the high resistance splice was near the substation, the increase of neutral-to-earth voltage was largest on those farms on the substation side of the high resistance. The highest value, at the end of the line, was not changed significantly by a high resistance near the substation. When the additional resistance was placed near the midpoint of the line, some farms ahead of the poor connection had reduced levels of the neutral-to-earth voltage, while those further along saw increased levels. (3) As the substation grounding resistance was increased, the voltage near the substation increased and the zero point along the line was 21 moved further down the line. The effect diminished with distance from the substation. Dick and Winter (1987) presented computer generated profiles of primary neutral-to-earth voltage of a 7.2 kV electric power distribution system under secondary heavy load condition. Their simulation outputs showed secondary heavy load increased the local neutral-to-earth voltage. 2.3 Field Test and Diagnosis of Farm Neutral-to-Earth Voltage Beside theoretical analyses and computer simulations of the neutral-to-earth voltage problem, several researches have made contributions to the field testing and diagnosis of farm neutral-to-earth voltage in the past years. Sodcrholm (1982) discussed possible sources of stray voltage, measurement techniques to determine their cause, and corrective measures that could be applied. He indicated that proper choice of a meter or recording device for measuring stray voltage was essential if misleading indications were to be avoided. He suggested 6 specifications for voltmeters used for these measurements. (1) The meter scale should be such that AC voltage levels of 0.1 to 1.0 V can be observed. (2) The meter must be capable of separating AC and DC. (3) A low input impedance equivalent to an animal mouth-to-hoof resistance (approximately 300 ohms) should be used to evaluate voltages with a low source impedance and avoid misleading 22 measurements due to stray pick-up. (4) The meter should be capable of high impedance input (1 megohm or greater) for use in measuring induced voltage. (5) The speed of response should be fast enough to give an indication of transient voltages. (6) In addition to a voltmeter, other measurement tools such as graphic recorder, oscilloscope or clamp-on ammeter capable of measuring current levels from 1 mA to 20 A have been found valuable in monitoring and determining causes of stray voltage. Stetson et al. (1982) reported a test method developed to electrically evaluate an operating primary neutral connector, or splice. Their method required only a digital voltmeter and was not dependent upon a constant or given line load. Connections could be evaluated both before and after adjustment or replacement. They described specific step by step measurement procedures as follows. (1) PrOper safety procedures should be followed. (2) An insulated aerial lift was the safest and quickest method to reach the connections in question. (3) All connections and tests should be made using insulated electrical safety gloves. (4) A digital voltmeter was preferred since precise, low-level voltage readings were more quickly and easily obtained. (5) A clamp—on ammeter could be used to determine the level and monitor any changes in current. (6) Attach the voltmeter leads to the conductor near the connection with leads approximately 1/ 3 meter apart and note the readings. (7) Move to one side or the other of the splice and take a voltage measurement across a 1 / 3 meter section of the wire without 3 splice. If the voltage reading across the splice was greater than the 23 voltage reading on the wire without the splice, then there is resistance in the splice which should be eliminated. (8) In all cases prior to installing any connector, dirt or corrosion on the conductors must be removed with steel brush, steel wool or emery cloth. They reported their procedure had been verified by field tests and worked well on primary neutral or secondary neutral lines with bare conductors. Surbrook et al. (1988) developed a stray voltage diagnostic procedure with a minimum number of measurements. They described the minimum instrumentation needed was voltmeter, reference ground rod, wire and a 120 V load. Their procedure was: (1) Start at the main meter location or transformer pole. Measure between the transformer ground wire and a reference ground at least 15 feet away and not under the primary right of way. (2) Make the voltage measurement near the building or area on the farm where the voltage was suspected to be affecting the animals. (3) Determine if there was an excessive voltage drop on the neutral wire to any building on the property. (4) Check ground faults on the farm. If other sources were not found in steps 1 and 3, then it was possible that a ground fault was present. (5) The power supplier line crew would Open the bond between the primary and secondary neutrals at the farm transformer. At this point, telephone personnel and cable television personnel must check the grounding of their lines at the farm to make sure they did not themselves form a bond from the farm neutral to the electrical power supplier primary neutral. This was because that if the previous tests did not lead to an identification of the neutral-to-earth voltage, then it was possible that 24 the source may be due to a secondary ground fault some place other than on the farm. Prothero et al. (1988) studied the primary neutral-to-earth voltage levels impacted by various wiring system treatments through taking field measurements. The test circuit that they chose was a radial two phase 3-wire tap, from a three-phase 4-wire multi-grounded neutral feeder beginning approximately 2.5 miles from the source substation. Through analyzing the field measurement data, they reported that the present preferred method of solidly bonding primary and secondary neutrals was consistent with the goal of minimizing primary neutral-to-earth voltage on rural feeders. And the large amounts of supplemental primary neutral grounding, as well as load balancing and line reconstruction accomplished during their investigation, could not reduce the primary neutral-to-earth voltage to zero. 2.4 Mitigation of Farm Neutral-to-Earth Voltage Problem Gustafson (1985) proposed three possible approaches to mitigate neutral-to—earth voltage problem on farms. The first recommendation was voltage reduction -- by either elimination or reduction of the voltage source (e.g., by removing bad neutral connections, improving or correcting wiring and load balancing), or by active suppression of the voltage by a nulling device. (2) When the voltage could not be reduced to acceptable levels, the suggestion was gradient control -- by use of equipotential planes and transition zones to maintain the anirnal’s step 25 and touch potential at an acceptable level. (3) Isolation of a portion of the grounding or grounded neutral system accessing the animals, so that they will not be subjected to objectionable currents due to stray voltages existing on the remainder of the grounded neutral system. From the literature (USDA, 1991), the term "isolation" is used to mean the electrical separation of all or a portion of the grounded neutral system of a farmstead from the remainder of the primary neutral system or the remainder of the farm electrical system. Isolation of part of the grounded neutral system can prevent neutral-to-earth voltage on the non-isolated portion of the system from accessing the animals. Isolation can be accomplished on a conventional multi-grounded system (1) ahead of the farm main service (whole farm isolation); or (2) at the livestock building (single service isolation). The whole farm isolation can be accomplished (1) by isolation at the distribution transformer or (2) with an isolation transformer following the distribution transformer. If a satisfactory solution can be obtained by isolation of a single building service, an isolating transformer can be used. Depending on farmstead load, the transformer for the single service can be smaller and less expensive than a transformer for the entire farmstead. Cloud et al. (1987) summarized the available devices for neutral isolation at the distribution transformer. They indicated that three methods have been developed for isolating the primary and secondary neutrals at the distribution transformers. They make use of (1) conventional spark gap; (2) a saturable reactor; or (3) a solid state 26 switch. These methods provide a high impedance interconnect below a specified threshold voltage, and a low impedance interconnect when the voltage exceeds that threshold. The "high" impedance is relative to the grounding impedance of the isolated secondary system. The "low" impedance provides that, under any condition creating a primary to secondary voltage above the threshold level, the device impedance will be reduced to a value such that the neutrals are essentially bonded. Surbrook et al. (1989) proposed a number of mitigation techniques to reduce farm neutral-to-earth voltage. They indicated that common mitigation techniques can be applied once the sources were positively identified. On-farm sources usually responded to one or more of the techniques described in their report. (1) Elimination of resistance at splices and terminations of the neutral conductors on the farm was necessary when this was found to be the source. (2) Increasing neutral conductor size may reduce the voltage. (3) Reducing the length of feeder conductors to a building was effective during initial layout of the farm buildings. (4) Balancing the 120 V loads in a building to maintain neutral current at or near zero was important. (5) A four-wire feeder, separating the neutral from the equipment grounding conductor, may be installed to a building where animals may be affected. (6) Elimination of the interconnections between neutral conductors and equipment grounding conductors in a building. (7) Providing all electrical equipment with an equipment grounding conductor that was continuous from the equipment to the grounding bus of the circuit supply panel increased the safety and reduced the chances of 27 neutral-to-earth voltage. (8) Elimination of any fault in equipment or wiring, or any wiring that potentially could cause a fault from an ungrounded conductor to the equipment or the earth was extremely important. Surbrook et al. (1989) also indicated that off-farm source mitigation normally handled by the power supplier included: (1) separating the primary and secondary neutral conductors; (2) repairing corroded neutral conductor splices; (3) increasing the neutral conductor size; (4) increasing the primary line operating voltage; (5) reducing neutral-to-earth resistance at one or more locations along a distribution line; and (6) elimination of ground faults on the primary system, or at another customer location. They indicated that there were some mitigation techniques that were an attempt to lower the cow contact voltage regardless of the source. These mitigation approaches included: (1) Equipotential planes installed in the floor of milking areas, at watering devices and feeding areas were intended to put everything within reach of the cow at the same electric potential so there would be no contact voltage. (2) Installing an active suppression device counteracting the neutral-to-earth voltage condition may be effective where the voltage could not be eliminated. Althouse et al. (1990) proposed a circuit model to evaluate the effectiveness of neutral isolation at the distribution transformers on neutral-to-earth voltage. Figure 2 shows this model. In Figure 2, RD is the primary system source resistance, Rs’s are the resistances of the 28 primary ground rod at the power supply transformer, Rl’s are resistances of the isolated secondary ground rod, RF’s are ground resistances of the farm electrical system, and R A’s are resistance of electric pathway of the animal body. When distance of neutral separation becomes farther and farther, the position of line B-C in Figure 2 will move downward lower and lower. The operations of this circuit model can be summarized into three steps as follows (referring to Figure 2): 1. With the farm grounding open, take the measurements of BS (primary neutral-to-earth voltage), 135-] (the voltage between separated primary-secondary neutrals), E1 (farm ground neutral-to-earth voltage) and Rs (the primary source ground resistance, RS = R31 + R52), and then use the voltage division law to calculate the resistance R51 and R32 in the circuit model: R51 = R5 x (E5111 / ES) (2.1) and R82 = R8 X (E1 / ES) (2.2) According to Kirchhoff’s Voltage Law (KVL), with farm grounding closed: Es=IrXRsl+IIXRl+El (2.3) and R1=03 0:80 05 5 00.00580 3.0300 0.8 5053 -- 58:0. 8: 08 8088080: 855038 05 .8 O 08.8 0.8 m 00.0.8 08 0.020. b09808 0:. 6000.808 830800.08 05 @000. 8. .Aommxg 308099-038 £000 08 > .5va 80:»... 8:99.58 50:00:80 c>\o>v 8:00:80 0.9. 00.05.88 08590005 08 .0008 0800.0 U< I: 0.585.. O 8.3. 8.3 0 02.: g .m. w, an 3.! .84 .3. .84?! <33. <33 < 09...... < unit <23 3...! <2. <23. <23 < it .0 88E 45 In the field, several operational conditions are usually superimposed making the source identification of neutral-to-earth voltage difficult. However, a clear and thorough understandings of these effects requires an understanding of the individual contribution of each operational condition. Only one parameter at a time in each of eight cases was changed, and all other parameters remained unchanged. 4.2 Simulation of Abnormal Conditions along the Distribution Line The base models of power distribution lines as described in preceding sections were used for comparison with each of the abnormal line conditions studied. The deviation of the neutral-to-earth voltage of the test case as compared with the base model was considered as significant criteria for evaluation rather than the actual magnitude of the voltage per se. 4.2.1 Neutral Conductor Resistance Change In order to study the neutral-to-earth voltage changes arising from corroded and other poor connection (high resistance) conditions on the primary neutral conductors, the neutral resistances or impedances in the following individual segments of the DC circuit model in Figure 4 and the single-phase AC circuit model in Figure 5 were changed from the value 0.086 (normal, base case value) ohm to 1.0, 5.0, 20.0 and 100K (open circuit condition) ohms: 1. The segment between node 9 and 10, RD9, near the substation of each circuit model. 2. The segment between node 33 and 34, RD33, near the mid-point of each circuit model. 3. The segment between node 56 and 57, RD56, at the end of each circuit model. 4.2.2 Heavily Loaded Power Line on Farm In order to study the neutral-to—earth voltage changes arising from heavily loaded power line on farm, the primary load demands of 3 A (normal at base case), 6 A, 9 A, 12 A and 15 A were simulated in the following individual branch transformer locations of the DC circuit model in Figure 4 and the single-phase AC circuit model in Figure 5: 1. The branch between node 404 and 9, near the substation of each circuit model. 2. The branch between node 416 and 33, near the mid-point of each circuit model. 47 3. The branch between node 428 and 57, at the end of each circuit model. The load demand changes in the DC circuit model of Figure 4 were implemented by altering the corresponding primary branch load resistance from 1,600 ohms (normal at base case), to 800, 533.3, 400 and 320 ohms, sequentially. The load demand changes in the single-phase AC circuit model of Figure 5 were implemented by altering the corresponding branch secondary load resistances from 2 ohms (normal at base case), to 1, 0.67, 0.5 and 0.4 ohm, sequentially. This gave a secondary current of 60 A (normal at base case), 120, 180, 240 and 300 A in sequence. The primary / secondary current radio for 4800/ 120/ 120 transformer was 1:20, producing the corresponding primary load demands. 4.2.3 The Distribution System Ground Resistance Calculation In order to evaluate the neutral-to-earth voltage changes due to the ground resistance changes at a particular location, the system ground resistance along the 4,800 V distribution line model in Figure 4 were calculated through the following procedures: 1. Set the substation source voltage VI to zero. 48 2. Replace ground resistance at node 1 (substation), node 9, 33 and 57 (end of the line) with test voltage source, respectively. 3. Two different levels of test voltage were selected, 5 V and 10 V. The corresponding test currents were obtained through the SPICE simulation output. 4. The test voltage divided by the corresponding test current gives the system ground resistance (Thevenin Equivalent Resistance). The corresponding Thevenin Equivalent Open Circuit Voltages at location of node 1 to earth (substation) and node 33 to earth were also calculated in the DC model of Figure 4 through removing the ground resistance RS and RF G33 and obtaining the neutral-to-earth voltage values of node 1 and node 33, respectively from the SPICE simulation output. In order to determine the effect of the changes of neutral-to-earth voltage producing parameters on the primary system ground impedance as observed from a particular farm transformer location, the following procedures were performed: 1. Each time respectively, increase the neutral line resistances from 0.086 ohm (base case) to 100 ohms (bad neutral connection) in the immediate left segment next to simulated transformer load of the 49 circuit model, i.e., in the circuit model of Figure 4, the resistances were increased from 0.086 ohm to 100 ohms in the neutral line segments RD4, RD8, R012, R016, R020 R056, respectively. 2. Calculate primary system ground resistance (Thevenin Equivalent Resistance) and Thevenin Equivalent Open Circuit Voltages at the location of node 33 to earth as well as neutral-to-earth voltage at node 33 in each of corresponding neutral segment RD settings above, respectively. 4.2.4 Substation Grounding Resistance Change The normal grounding resistance for the substation in this model is 0.5 ohm. The substation grounding resistance change effect on the neutral-to—earth voltage was studied by increasing substation grounding resistance RS from 05 ohm respectively to 1 ohm, 5 ohms, 10 ohms, 20 ohms and 40 ohms at the substation, node 1 for the DC model. in Figure 4 and the single-phase AC model in Figure 5. This was to model the effect of a poor grounding connection at the substation on neutral-to-earth voltage. 4.2.5 Neutral-to-Earth Resistance Reduction The normal grounding resistance in both DC and single-phase AC models for each residential transformer is 10 ohm and for each farm 50 transformer is 1.5 ohm. The neutral-to-earth resistance reduction effect on neutral-to-earth voltage was studied by reducing the grounding resistance RFG33 from 1.5 ohms to 1.2, 0.9, 0.6 ohm and then to 0.3 ohm. Grounding electrode RF G33 was at the middle of the distribution neutral line (node 33) which was the fourth farm transformer location from the substation shown in Figure 4 and Figure 5. This exercise was to model how well a low resistance-to-earth electrode could lower a neutral-to-earth voltage at a farm. In the base case, the normal grounding resistance for each residential transformer was 10 ohm, and for each farm transformer was 1.5 ohm. There was one grounding electrode at 25 ohm between each neighboring transformers. The effect of lowering the grounding electrode resistance all along the distribution line was studied by changing the extra grounding electrode resistance, REG, from 100 k-ohm to 25 ohm. This resulted in a simulation with a grounding electrode of not more than 25 ohms at every pole along the distribution line. The distribution line models are shown in Figure 4 for the DC model, Figure 5 for the single-phase AC model and the base case values of grounding electrode resistance are listed in Table 2. 4.2.6 Primary Operating Voltage Level Change In the base case, the primary operating voltage level was 4.8 kV. The effect of the change of primary operating voltage level on the neutral-to—earth voltage was studied by simulating the other primary 51 operating voltage levels of 2.4 kV, 7.2 kV and 26.4 kV in the DC model of Figure 4, respectively. The primary currents were set so that the A secondary load currents for all these cases were maintained the same as in the base simulation of 30 amperes for residential transformer secondaries and 60 amperes for farm transformer secondaries. The power consumed on the circuit remained the same as the base case. The resistances RRL and RFL were changed to maintain the desired secondary currents. Values of primary voltage, VI, load resistances RFL and RRL, and primary current are listed in Table 4. Table 4. Primary Current and Load Resistance, RRL and RFL, for Different Primary Voltage Simulations. Distribution Residential Load Farm Load Voltage Pri. A See. A RRL Pri. A See. A RFL 2.4kV 3.0 30 SN 6 0 60 4N 4.8kV 1.5 30 3,2N 3.0 60 1,6N 7.2kV 1.0 30 7,211) 2.0 60 3,6N 26.4kV 0.27 30 96,8N 0.54 60 48,400 52 4.2.7 Secondary Earth Fault The secondary circuit simulation for the DC model in Figure 4 is shown in Figure 7. This was a 120/ 120 volt, single-phase, three-wire grounded system with a balanced load. The secondary earth fault effect on neutral-to-earth voltage was studied by introducing a 3, 6, 9 and 12 A secondary ground fault through the resistor RF3 set at 40, 20 13.3 and 10 ohms from the ungrounded conductor of the secondary circuit to earth. The faults of in-phase (only SW3 and SW4 closed in Figure 7) and 180 ° out-of-phase (only SW3 and SW5 closed in Figure 7) on the secondary side were respectively attached to: (1) node 9 which was the farm transformer location nearest the substation; (2) node 33 which was the fourth farm transformer located at the middle of the primary distribution line; and (3) node 57 which was the farm transformer location farthest from the substation. Every transformer simulation in the single-phase AC model of Figure 5 has its own secondary circuit. The 3, 6, 9 and 12 A secondary earth faults (in-phase and 180° out-of-phase at three different locations as described above) were also introduced by connecting the corresponding fault simulation resistance directly to the corresponding position of the secondary circuit of the single-phase AC model. 53 .9 008.351.. :38 5.80 .8800... 5.3 50.0.? 8:25:36 30:80.0 08;..-0320. .2 3.88 .5020 Un— 5n: an E a HE! 522:... :— ‘7‘." s o 9 3 2 r.- ..B u m . ’ s 050E 54 4.2.8 Primary Phase-to-Earth Fault In order to analyze the neutral-to-earth voltage changes arising from phase line to earth fault, first, the effect of the primary phase line to earth fault size on the neutral-to-earth voltage was studied by simulating a fault in the middle of the distribution line. This was implemented by introducing a resistor RF2 from the ungrounded phase conductor node 416 to earth in Figure 8 for the DC model and the similar connections for the AC single-phase model. The similar connection for the three-phase AC model was shown in Figure 9 (RF2 connected from node 416A of phase A to earth). RF2 was set at the values of 1,600, 800, 533.33 and 400 ohms to model the fault levels of 3A, 6A, 9A and 12 A, respectively. The effect of this fault’s location on the neutral-to-earth voltage was studied by moving the resistor RF2 above from node 416 (or node 416A for three-phase model) to node 404 and to node 428 (or node 404A and node 428A for three-phase model), respectively. Node 404 was the farm transformer location nearest the substation and node 428 was the farm transformer location farthest from the substation. At this time, RF2 was only set at 400 ohms to model a 12 A fault, the most serious fault situation simulated. 55 00.0—38.0. .3... 580-208.... .008...— 53 80.0.»... 828:3... 80:80.0 03:90.35... 8.. .28... .3030 06 .w 0.89m ‘ n In 0 m s m a ...- u 0 0 mm 3. 8 8 .n .2... 8.... ..- 030 .2... 6 39.300..- m W couuflunmam 0e.4-.e-ue no eo..ou . u L<<03 00.0. 0... 0. 00.000000 3.00.00 0.0 00.03 - 030... .00 0.0 ..00..0..00.. 00.05....6 00. .0 U 0.0.... 000 m 0.000 .0. .00.. b00080. 0... 60.0.0000: 0000.00.00. 0... 000.. 0 H 60.0.00... .30.. 5.00 0. < 0.000 5.3 Aow0._0> 00000-0780.... 0000 .0. > 8w... 0.0.... 00.05....6 302000000 0 . >\0>. 000000000 0.? 0.5-.00. 0.0.3-003. .0. .0000. .3000 O< a 0.035 ..v I I.“ “ ‘4 ll: '5 '23 ..3 ..a ..a ..3 a; - E" DDDDD ' ii‘i‘ an .09. .03 .3. .3. WIS-.1! on: 0003. 005... 0 008500303 in! IN ONE 0.! 3... .r <- . <05. .35.. c 02:. c 02.... 3.3 .35. Sam-3...... < 092.1 F I put» ..w 57 4.3 Field Tests of Neutral-to-Earth Voltage Gradient In order to implement the secondary goal of this study, that is, to conduct the farm field tests to investigate and analyze the effectiveness of isolation of distribution primary neutrals from secondary neutrals on neutral-to-earth voltage on a farm, a series of tests were devised. These tests included: (1) neutral-to-earth voltage gradient distribution near a single primary ground rod; (2) neutral-to-earth voltage gradient distribution near two parallel primary ground rods acting as a grounding system; (3) neutral-to-earth voltage gradient distribution near one primary ground rod and one isolated secondary ground rod when the farm ground system was not connected (farm ground open); (4) neutral-to-earth voltage gradient distribution near one primary ground rod and one isolated secondary ground rod when the farm ground system was connected with 5.24 ohms ground resistance; and (5) discussion of the neutral isolation circuit model from literature (Althouse, 1990). The test site was an actual farm located in Williamston, NH and was supplied by 4,800/120/ 120 V electric power distribution system. To facilitate the analysis and visualization of the test data, the personal computer program software SURFER was employed to draw 3-dimensional distribution and equi-potential contour lines of the tested neutral-to-earth voltage gradients. The personal computer software SUPERCALC and its spreadsheet were also employed to draw the tested neutral-to-earth voltage gradient along some particular directions and perform some data analysis. 58 4.3.0 Data Collection of Voltage and Resistance of Ground Rod A test primary ground rod was located in a farm field at a distance of not less than 200 feet from any known metal in contact with the earth and connected to an electrical grounding system. A site in Williamston, MI was chosen which was served by an ungrounded 4,800 volts single-phase distribution system. This site was chosen so that earth voltage gradients from other electrical systems would be negligible. A voltage was established on the test primary ground rod by passing a 60 Hz AC current from the test ground rod to a low resistance return ground electrode system located 400 feet away from the test primary ground rod. An isolation type variable transformer was used to create this earth current at the test primary ground rod. This is illustrated in Figure 10. The test ground rod was placed in sandy loam soil with a depth to bed rock greater than 50 feet. All measurements of earth voltage were taken from a point on the test site to a reference ground which was located 400 feet south of the primary test ground rod. A digital Fluke 87, multimeter, with an internal impedance of 10 mega-ohms was used for all neutral-to-earth voltage gradient data measurements. The AC Volt scale was selected. It has been verified that the meter did not read DC quantities on the AC scale. A copper probe for voltage measurement consisted of a AWG number 8 solid copper conductor fastened to a wooden handle. The conductor extended one inch below the bottom of the handle and the insulation 59 Test Forn N Grounding Systen Residence Drive Test Site ' Tronsforner ole Test Current Return Grounding Systen 60 Hz 120 v Isolation Type Vorioble Tronsforner -* Reference Si 1 ~Ph Ground no e use Unqrounded 4000 Volt Prinory 0 Figure 10. A variable transformer was used to drive electric current into the earth at the test primary ground rod. 0 5 10 15 20 25 30 35 4O ‘0 l i T l i r T ‘0 .35 r- _- 35 30 L. I O _- 30 DUO-30) COO-30) A . 25 - 3.00.26) - 25 20 ‘- . - 20 RAN-20) N 15 r- - 15 10 .— O O ..- lO AUG-10) Baa-m) 5 ~ ‘ 5 O 1 l 1 L 1 1 1 O O 5 10 15 20 25 30 35 40 Figill 11. The 40 x 40 Feet Square Shaped Test Plot for NEV Gradient Testing, Primary One and Two Ground Rods 61 was removed from that portion. When taking the voltage measurement, the probe was firmly placed against the soil and the meter was allowed to stabilize before any voltage measurement was recorded. For some earth voltage measurements, a solid AWG number 12 copper wire was inserted approximately 0.5 cm into the soil. This technique was used for all earth voltage measurements where the distance between measurements was less than six inches. A Megger Earth Tester (Null Balance, Battery Operated, James G. Biddle Co.) was used for all ground electrode resistance data measurements. The principle of this instrument was based upon The fall-ofipotential method or 3-point method (Tag, 1964 and IEEE, 1983). The distance between the test rod and the potential probe of the Tester was 65 feet (19.8 m), with another additional 35 feet (10.7 m) distance to the current probe of the Tester. 4.3.1 Test of NEV Gradient Distribution, Primary One Ground Rod The 40 x 40 feet square shaped test plot is shown in Figure 11 in which the direction expressed was consistent with conventional map (upper - north, lower - south, left - west and right - east). The coordinate system of the plot was established with origin at low-left corner (south-west corner), positive X axis toward the horizontal direction (east direction), positive Y axis toward the vertical direction (north direction) and the length unit as foot. One primary electrode rod Rs (connected with neutral-to-earth voltage source) was located in the center (20, 20) of the plot and was driven 8 feet deep into earth. 62. Within the inner square A (10, 10), B (30, 10), C (30, 30) and D (10, 30), the earth voltage measurements were taken at every foot, both horizontally and vertically. Outside the inner square ABCD, the earth voltage measurements were taken at every 5 feet, both horizontally and vertically. From the center (20, 20) of the plot, along the four radial directions of straight north, straight south, straight west and straight ' east, the earth voltage measurements were taken up to 100 feet distance. The measurement incremental intervals were: every inch for the distance from the center to 1 foot, every 3 inches for distance up to 2 feet, every 6 inches for distance up to 4 feet, every foot for distance up to 10 feet, every 5 feet for distance up to 20 feet, and every 10 feet for distance up to 100 feet. 4.3.2 Test of NEV Gradient Distribution, Primary Two Ground Rods The layout configuration of this test was same as the previous test in section 4.3.1, except: 1. One more primary ground rod (driven 8 feet deep into earth) was located at 6 feet (1.83 m) away straight north from the original one at center. The coordinate for this additional primary ground rod was Rsa (20, 26). Both primary rods were connected with the same neutral-to-earth voltage source. 63 2. The earth voltage measurements along the radial direction of straight north were taken with the incremental intervals as: every inch for the distance from the center to 1 foot, every 3 inches for distance up to 5 feet, every inch for distance up to 7 feet, every foot for distance up to 10 feet, every 5 feet for distance up to 20 feet, and every 10 feet for distance up to 100 feet. 4.3.3 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod Without Farm Ground Connection The 4 x 10 feet rectangular shaped test plot is shown in Figure 12 in which the direction expressed was consistent with conventional map as described in section 4.3.1. The coordinate system of the plot was also established with origin at low-left corner (south-west corner), positive X axis toward the horizontal direction (east direction), positive Y axis toward the vertical direction (north direction) and the length unit as foot. One primary electrode rod Rs was located in the position (2, 2) and one secondary isolated rod R1 was located in the position (2, 8). The distance between two rods was 6 feet and both rods were driven 8 feet deep into earth. Within this plot, the earth voltage measurements were taken at every half foot, both horizontally and vertically. More detailed earth voltage measurements were taken along the connection line from the south side center (2, 0) to north side center (2, 10) of this plot. The measurement incremental intervals were: every 3 O 1 2 3 4 9— -9 a— 0 —8 size) 7. "7 + 6" ..5 51- ‘5 4— -“ N .- -- 0 2— R. -2 R_(-4,2) -(12) 1- -1 O l 2 3 4 Figure 12. The 4 x 10 Feet Square Shaped Test Plot for NEV Gradient Testing, Isolated Primary and Secondary Ground Systems 65 inches for the distance from the south side to 1 foot, every inch for distance up to 3 feet, every 3 inches for distance up to 7 feet, every inch for distance up to 9 feet, and every 3 inches for distance up to 10 feet -- north side center (2, 10). In this test, the primary rod was connected with a neutral-to-earth voltage source, the secondary isolated rod was not connected with a neutral-to-earth voltage source, and the farm ground system was not connected. 4.3.4 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod With Farm Ground Connection From the layout configuration of the test in the section 4.3.3, an isolated secondary ground rod was driven 6 feet north away from the test primary ground rod. To create an actual earth circuit as exists on a farm, seven ground rods were driven in an area 600 feet (183 m) to the north of the test site. This farm grounding system was connected to the secondary ground rod at the test site. By connecting different combinations of ground rods, several levels of ,farm grounding resistances could be achieved from infinite to as low as 5 .24 ohms. The test procedure is shown in Figure 13. 60 H2 120 V Isolation Type llllll, Variable Transforner Tl ll] ? v v v 7 Test Prlnory Test Secondary 7 ' Test Current Ground R°d 5'0“"6 R°d Fara Grounding Return Systen Grounding Systen 400 Ft. 600 Ft. Figure 13. A secondary isolated ground rod and farm grounding system were established to an area away from influence of earth voltage gradients from other electrical systems. 67 4.3.5 Verification of the Neutral Isolation Circuit Model This circuit model was described in detail in Figure 2 and in section 2.4, Chapter 2. The schematic diagram of the circuit model, Figure 2, also showed the locations of the instrumentation to measure the voltages and currents during the testing. The test plot was the same as in Figure 12, described as in section 4.3.3 and 4.3.4, except that one more primary ground rod RSS was driven 8 feet deep into earth at the location (-4, 2), 6 feet away straight west from the other primary ground rod Rs- The combinations of different farm ground electrode connection schemes gave the farm ground resistance (R) levels at open circuit, 23.7, 10.3 and 5.24 ohms, respectively. The animal simulation resistors, RM and R,u were not connected. The resistances of the original primary ground Rs, additional primary ground rod Rss» isolated secondary ground rod R1 + R11 and primary NEV source ground RD were measured. Their values were 18.6, 11.4, 22.0 and 6.2, respectively. Sixteen sets of the tests were performed: (1) primary one rod, primary NEV 10 V and farm ground open; (2) primary one rod, primary NEV 10 V and farm ground resistance 23.7 ohms; (3) primary one rod, primary NEV 10 V and farm ground resistance 10.3 ohms; (4) primary one rod, primary NEV 10 V and farm ground resistance 5.24 ohms; (5) primary two rods, primary NEV 10 V and farm ground open; (6) primary two rods, primary NEV 10 V and farm ground resistance 23.7 ohms; (7) primary two rods, primary NEV 10 V and farm ground resistance 10.3 ohms; (8) primary two rods, primary NEV 10 V and 68 farm ground resistance 5.24 ohms; (9) primary two rods, primary NEV 5 V and farm ground open; (10) primary two rods, primary NEV 5 V and farm ground resistance 23.7 ohms; (11) primary two rods, primary NEV 5 V and farm ground resistance 10.3 ohms; (12) primary two rods, primary NEV 5 V and farm ground resistance 5.24 ohms; (13) primary one rod, primary NEV 5 V and farm ground open; (14) primary one rod, primary NEV 5 V and farm ground resistance 23.7 ohms; (15) primary one rod, primary NEV 5 V and farm ground resistance 10.3 ohms; and (16) primary one rod, primary NEV 5 V and farm ground resistance 5.24 ohms. In each set of the test above, the following physical quantities were measured as shown in Figure 14: (1) Es (primary NEV); (2) I, (the earth current on primary side); (3) II (the earth current on isolated secondary side); (4) E51 (the voltage between separated primary-secondary neutral); (5) E1 (isolated secondary NEV); (6) ED (primary source NEV); (7) E,- (isolated farm NEV). Figure 14 is actually the same circuit as proposed by Althouse (1990) in Figure 2. i 69 Isolation Type Variable Transforner 120 V 60 HI I ITIT I b ED ( Ru :5 Earth Earth P""°'Y Systen Prinary Secondary Forn Systen Resistance Ground Rod Ground Rod Resistance at Transforner at Tronsforner Figure 14. The physical quantities measured in the neutral separation circuit model. V. RESULTS and DISCUSSION 5.1 Results and Analysis of NEV Computer Simulation The computer simulation results of the distribution systems were analyzed to determine the level of the neutral-to-earth voltage produced under various operational conditions. Although the neutral-to-earth voltage profiles were presented as if continuous, only the discrete voltage values at each of the 57 node locations were meaningful. 5.1.0 Normal Operational Condition The profile of the neutral-to-earth voltage along the distribution line for the base case of the single-phase DC model is shown in Figure 15. The profile shows that the magnitude of the neutral-to-earth voltage at the substation (9.2 V) was much higher than at the end of the primary neutral line (4.9 V). Note that the magnitude of the neutral-to-earth voltage decreased as the distance away from the substation increased, reaching zero and experiencing a 180 degree phase angle change at node 12. Then the neutral-to-earth voltage 70 71 BASE CASE NEV, 4.8K 1—PHASE LINE FARM 8: RESIDENTIAL GROUND 1.5 8: 10 OHM, POLE 25 OHM VOLTAGE (V) IiiitiITTii—rriiiriitiiiirfliimiiitittrritTitiiriiiiri '- in O in O in O in 3 in O iOI‘ v- v- N N t') 1') 1' in min NODE # (1 -57) 9405271:- Figure 15, Profile of the neutral-to—earth voltage along the primary distribution line from substation (node 1) to 57th node for the DC single-phase base model 72 increased as the distance from the substation became greater, leveling off toward the end of the neutral line. Along the multi-grounded neutral power distribution systems which are commonly used in rural areas of the United States, some level of neutral-to-earth voltage is always present; it is an inherent phenomenon. Kehrle (1984), Gustafson (1985) and Surbrook et al. (1986) also obtained theoretical profiles of neutral-to-earth voltage similar to Figure 15 . The neutral-to-earth voltage profile along the distribution line for the base case of the single-phase AC model is shown in Figure 16. This profile is about the same as the profile in Figure 15 obtained from the DC model if only the magnitudes of neutral-to-earth voltages are considered. Figure 17 shows the comparisons of two neutral-to-earth voltage magnitude profiles obtained from the DC based model and the AC based model. To make the DC model profile more comparable with that of the AC model, the minus signs of the voltage values near the substation in the DC profile were removed in Figure 17. Although the curve position of the AC model was slightly higher than that of the DC model, the differences between these two profiles were very small and the shapes of these two profiles were almost identical. The profile of the AC model did not experience the ”zero voltage value" point like the DC model did,‘ the reason being that the neutral return currents from the earth could not cancel each other out completely when the AC model distribution line series inductance effect was taken into account. 73 AC BASE CASE NEV, 4.8KV LINE 10 8- > v 6‘ Lu 0 < +— _J O 44 > 2-1 0 IIIIIIIII—ITIITITIITTIIIIIIITTITIIIII[III—ITVIWTIITITFY -- In 0 In 0 10 o in o In o 105 v- s" N N n I") V’ V’ W 101.0 NODE # (1-57) 940526b Figure 16. Profile of the neutral-to-earth voltage along the primary distribution line from substation (node 1) to 57th node for the AC single-phase base model 74 COMPARISON OF AC & DC BASE CASE NEV 4.8 W I—PHASE DISTRIBUTION SYSTEM 10, Ii 80: DC |. A > 6‘ H LLJ 2 “ -‘-':-:'._- u -- - -l .— "".":"""."'_;" ...l | ‘-- O 4‘ a. > I; ‘ 4 |i 2.- p l\ /,‘ \. .l H n 0‘ -[t[lTTTIIIIIIIFITIIIIITIIITFITITIIIIIrrTI'II '- In C n C If) C In C n o ‘0" v- e- N N n l’) v * m an NODE # (I -57) 940527d Figure 17 . Neutral-to-earth voltage profile comparison between the simulations of single-phase AC and DC models 75 In fact, under other operational conditions that have been studied, the neutral-to-earth voltage profiles obtained from single-phase DC model simulations were about the same as the profiles obtained from the corresponding single-phase AC model simulations when only the magnitudes (rms values) of the voltages were considered. In the following sections, the effects of the different operational conditions on the neutral-to-earth voltage were studied primarily through the DC model. The corresponding single-phase AC simulation profiles are provided in the the appendix for reference. 5.1.1 Neutral Conductor Resistance Change Figures 18 through 20 present the neutral-to-earth voltage simulation curves resulting from changing the neutral conductor resistance RD9, RD33 and RD56 (referring to Figure 4) in three different representative locations at normal load demand condition (3 A load), as shown in Figure 21. Figure 18 shows the the primary neutral-to—earth voltage profiles with the variable neutral conductor resistance RD9 between the nodes 9 and 10 near the substation. When RD9 increased, the magnitudes of neutral-to-earth voltages also increased accordingly in most segments along the distribution line. Note the most significant increases of the neutral-to-earth voltage occurred at node 12 which is near the high neutral resistance segment and near the last customer load cut off from the substation by the high resistance segment in the neutral. At this 76 RD9 CHANCE IMPACT ON NEV, 4.8K I—PHASE RD9 0.086, 1, 5, 20 AND IOOK OHM, LOAD 3 A 6 w.’.1-l-l-l,l A . . , . - - .=.=‘:7_’Y:1...Y- 44 II 5=::==="’"JPL 2« 'r“ A - ------------------------------------------- > V LtJ (é) —-i—- 0.086 OHM 5 -a—- 1.00 OHM O > —*— 5.00 OHM + 20.0 OHM + TOOK OHM -12 r—rfilllTTTlflllllTlllIllllllllllllllllerTTTllllTllTllll — In 0 in o to o in o 1.0 o In I\ .— .— N m n n v- v to In In NDDE # (1 —57) 9405280 Figure 18. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 5 7th node with variable neutral conductor resistance RD9 between node 9 and node 10 and a normal customer load of 3A at node 9 (from single-phase DC model simulation) 77 POSS CHANCE IMPACT ON NEV, 4.8K I—PI—IASE RD33 0.086, I, 5, 20 AND 100K OHM, LOAD 3 A —+— 0.086 OHM -a— 1.00 OHM _6 q —~— 5.00 OHM —v— 20.0 OHM -a . + 100K OHM VOLTAGE (V) -10lrlllrllIrlIlTrlllllIlllTlIllllllrlllllllllllllrllIlllll '- 1.0 O in O in O 10 O in NODE # (1-57) 9405270 Figure 19. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable" neutral conductor resistance RD33 between node 33 and node 34 and a normal customer load of 3A at node 33 (from single-phase DC model simulation) 78 node, when neutral resistance RD9 was 0.086 Ohm (normal base case), the magnitude of the neutral-tO-earth voltage was zero. When RD9 increased to 1.0 Ohm, the voltage was increased to 1.9 V. When RD9 increased 5.0 Ohm, the voltage was increased by 2.2 V, to 4.1 V. When RD9 increased to 20 Ohm, the voltage was increased another 1.0 V, to 5.1 V. When RD9 increased tO 100 k-Ohm (open circuit simulated), the voltage was only slightly increased by 3 additional 0.5 V, to 5.6 V. Near the substation, a high resistance segment in the neutral will usually increase the neutral-tO-earth voltage for all customers in the local area. Figure 19 shows the the primary neutral-tO-earth voltage profile with the variable neutral conductor resistance RD33 between node 33 and 34 near the middle of the distribution line. The neutral-to-earth voltage became lower at nodes toward the substation from the location of the abnormal neutral resistance, and higher at nodes toward the end Of the line. As the abnormal resistance RD33 was increased, the voltage drop across this segment also increased. Note in the base case, when normal neutral resistance RD33 was 0.086 Ohm, the voltage drop across this segment was only 0.1 V. (45 V neutral-tO-earth voltage at node 33, 4.6 V at node 34). When RD33 was increased to 1.0 Ohm to simulate an abnormal resistance in the neutral, 0.6 V voltage drop occurred between nodes 33 and 34. The neutral-to-earth voltage decreased by 0.2 V at node 33 toward the substation side, while it increased by 0.3 V at node 34 toward the end Of the line. When neutral resistance RD33 was increased to 20 Ohm, there was a 1.4 V voltage drop between node 33 79 PBS-6 CHANCE IMPACT ON NEV, 4.8K I—PHASE ROSS 0.086, I, S, 20 AND TOOK OHM, LOAD 3 A E Lu 0 <( 5 _+_ o 0.086 OHM > ‘4 ‘ _9_ 1.00 OHM -6 q -*— 5.00 OHM + 20.0 OHM -8 -I + TOOK OHM llrllllllrllllIIIIIITIIITIIIIIITTIITITITTITIITIITIITI — in o In o n o in o In .— .— N N :0 n v- v I?) 8 NODE # (1-57) 940528b !\ t!) Figure 20. Profile of the neutral-tO-earth voltage along the primary distribution line from substation to 57th node with variable neutral conductor resistance RD56 between node 56 and node 57 and a normal customer load of 3A at node 57 (single-phase DC model simulation) 80 and node 34. The neutral-to-earth voltage decreased by 0.5 V at node 33 and it increased by 0.8 V at node 34 as compared with the normal RD33 (0.086 Ohm) condition. Note that the effect on neutral-tO-earth voltage of an abnormal neutral conductor resistance diminished as the distance from the neutral resistance RD33 increased. In the extreme case, when RD33 increased to 100 k-Ohm (open circuit simulated), the voltage drop across this segment reached 1.5 V. The neutral-tO-earth voltage decreased by 0.5 V at node 33 and increased by 0.9 V at node 34. However, the neutral-tO-earth voltage had no change at the substation and was only changed 0.2 V at the end of the line, as compared with the normal RD33 (0.086 Ohm) situation (base case). Figure 20 shows the the primary neutral-tO-earth voltage profile with the variable neutral conductor resistance RD56 between node 56 and 57 near the end Of the distribution line. The neutral-tO-earth voltage became slightly higher at nodes toward the substation from the location Of the abnormal neutral resistance, and slightly lower at nodes toward the end of the line. As the abnormal resistance RD56 was increased, the voltage drop across this segment also slightly increased. But this effect was very small. In the extreme case, when RDS6 increased to 100 k-Ohm (Open circuit simulated), the voltage drop across this segment was only 0.9 V. The neutral-tO-earth voltage decreased by 0.5 V at node 57 and increased by 0.4 V at node 56. However, the neutral-tO—earth voltage had almost no change from the node 50 Of the line all toward the substation as compared with the normal RD56 (0.086 Ohm) situation (base case). 81 .008. < m. 80.2.8 08.8.. .08. .808 .0 00: 00. m00_0 .000000. 0>_.0.00.0.00. 50.0.2. 00.... 0. 0mg 000 30.. find 0000....0. 8.000000 0.0.00 00. M03005 0.0.. m0.._...0. .0m0000 0m0=0> :..00-0.-_0....00 0... .30.. 0. 02.000000 000.00 00... AN 039% 02. mm... on. .. 00oz mm .002 a 00.2 . ~00. 82 With the line segment RD56 open the current at node 57 is 2.94 amperes which is the farm load at that point. All of that current must flow to earth at the farm which in the simulation has a ground resistance of 1.5 ohms. The neutral-to-earth voltage at node 57 is therefore 4.41 volts. But with normal resistance in the neutral segment RD56, even though a portion of the 2.94 amperes at node 57 flows along the line to other grounding electrodes, more current is flowing to the ground at node 57 from the adjacent line, resulting in a current at node 57 of 3.27 amperes. This results in neutral-to-earth voltage at node 57 of 4.9 volts. Therefore, for this situation, the neutral-to-earth voltage at the end of the line is lower when the line segment RD56 is open. This will not necessarily be true in all situations. Figure 18 through 20 indicate that high neutral resistances (poor neutral connections) will cause the neutral-to-earth voltage changes (increase or decrease) along the distribution line. These changes are localized near the places where bad neutral connections occur. The bad neutral connection near the substation will cause more significant neutral-to-earth voltage changes than if near the middle or toward the end of the distribution line. The reason for this is that the neutral line segments near the substation collect more returned currents from the network than the segments toward end of the line. The profiles obtained from the single phase AC model corresponding to Figure 18 through 20 are listed as Figure A1 through A3 in the appendix. 83 5.1.2 Heavily Loaded Power Line on Farm Figures 22 through 24 present the neutral-to-earth voltage simulation curves resulting from the different levels of the heavy load demand in three different representative locations along the power distribution line. Figure 22 shows the neutral-to-earth voltage simulation profiles under the condition of the different levels of the heavy load demand occurred at the transformer branch between node 404 and node 9 near the substation (2000 feet from substation) of the single phase DC circuit model. Compared with the base case, when the load demand current was increased from 3 A (base case) respectively to 6 A, 9 A, 12 A and 15 A, for some locations near the substation, the neutral-to-earth voltage actually decreased as the load was increased. And neutral-to-earth voltage increased on other segments along the distribution line as the load was increased. Note the most significant increases of the neutral-to-earth voltage occurred at node 12 near the heavy load demand took place. At this node, in the base case, when the load demand current was 3 A, the value of the neutral-to-earth voltage was 0 V. When the load demand was increased to 6 A, the voltage increased to 0.6 V. When the load demand was increased to 9 A, the voltage increased by another 0.5 V, to 1.1 V. When the load demand was increased to 12 A, the voltage again increased another 0.6 V, to 1.7 V. When the load demand was increased to 15 A, the voltage reached 2.3 HEAVY LOAD IMPACT ON NEV, 4.8K 1—PHASE LINE LOAD 3, 6, 9, 12 a: 15 A AT 404—9 10 ¢ 3A —B~—6A 9A 12A 15A VOLTAGE (V) -157IIIIIIIITIIIIIlIllllIlllI—ITIITTIIIITIIIITIIITIIIIITIIII .— n o n o in o In 0 II)" n e — N N n n v- V' In 1010 NODE # (1—57) 9405ng ' Figure 22. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 404-9 (single-phase DC model simulation) 85 V. The neutral-to-earth voltage increased almost linearly with the load demand current at a rate of 0.2 V/A near the high load demand node. As the distance toward the end of the line node 57 increased, this neutral-to-earth voltage increase was less and less significant. From the middle toward the end of the line, these neutral-to-earth voltage profiles were nearly unchanged as load was added. ’ Toward the direction of the substation, the neutral-to-earth voltages decreased at some segments and increased at some other segments, the increases near the substation were small. Figure 23 shows the neutral-to-earth voltage simulation curves resulting from the different levels of heavy load demand at the transformer branch between node 416 and 33, near the mid-point of the circuit model. Compared with the base case, when load demand current was increased from 3 A (base case) respectively to 6 A, 9 A, 12 A and 15 A, the neutral-to-earth voltage also increased accordingly along the distribution line. Note the most significant increases of the neutral-to-earth voltage occurred at node 33 where the high load demand took place. At this node, in the base case, when the load demand current was 3 A, the value of the neutral-to-earth voltage was 4.5 V. When the load demand was increased to 6 A, the voltage increased by 1.2 V, to 5.7 V. When the load demand was increased to 9 A, the voltage increased by another 1.2 V, to 6.9 V. When the load demand was increased to 12 A, the voltage again increased another 1.2 V, to 8.1 V. When the load demand was increased to 15 A, the voltage HEAVY LOAD IMPACT ON NEV, 4.8K l-PHASE LINE LOAD 3.6.9.12 81:15 A AT 416-33 VOLTAGE (V) 3A 6A 9A 12A 15A TITIrrTIrrIrIIIIIIIIIIIIIIIIIIIr1IIIIIIrrIITIIIIIIIII .— in O m o to 0 1.0 O In 0 ION v- v- N N n n <- V’ In 1010 NODE # (1 -57) 9405290 Figul'e 23. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 416-33 (single-phase DC model simulation) 87 reached 9.3 V (increased by 1.07 times from the base case of 4.5 V). The neutral-to-earth voltage increased linearly with the load demand current at a rate of 0.4 V/A at the high load demand node 33. In the direction toward the end of the line, node 57, the neutral-to-earth voltage increase was less and less significant. Even when the load demand was 15 A, the voltage at nOde 57 only increased by 0.7 V, to 5.6 V, only increased by 14.3% of the base case value of 4.9 V. ' Toward the direction of the substation, the neutral-to-earth voltage increases first diminished, approaching the values close to those of base case near node 16 (1.7 V). From node 16 to the substation node 1, as the distance increased, the voltages also increased slightly. Near the substation, when the load demand was 15 A, the magnitude of the voltage increased to 13.0 V, 1.41 times of the base case value of 9.2 V. Figure 24 shows the neutral-to-earth voltage simulation curves resulting from the different levels of the heavy load demand occurred at the transformer branch between node 428 and 57, at the end of the circuit model. Compared with the base case, when load demand current was increased from 3 A (base case) respectively to 6 A, 9 A, 12 A and 15 A, the neutral-to-earth voltage also increased accordingly along the distribution line. Note the most significant increase of the neutral-to-earth voltage occurred at node 57 where the high load demand took place. This voltage increase was similar to that of the high load demand at node 33 except that the significant voltage increase HEAVY LOAD IMPACT ON NEV, 4.8K 1-PHASE LINE VOLTAGE (V) LOAD 3, 6, 9, 12 8c 15 A AT 428-57 15 —+— 3 A 6 A 10 _ 9 A 12A 15A 5 .4 O - ---------- ”5?; ------------------------------------- 4.31:0}1/ 5f}? '1"! 431'," -5 D 933", .1?" :12” {gal “1014'; l V 1 -15 ITTTTTIIIIIITIIIIIIIIIIIITTTTIIFIWI[ITIIIIIIIIITIIIIII —~0 2 2 a a .9, a 9 “.2 a :21; NODE # (1 -S7) 9405290 Figure 24. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 428-57 (single-phase DC model simulation) 89 occurred at the different location. At node 57, in the base case, when the load demand current was 3 A, the value of the neutral-to-earth voltage was 4.9 V. When the load demand was increased to 6 A, the voltage increased by 1.9 V, to 6.8 V. When the load demand was increased to 9 A, the voltage increased by another 1.9 V, to 8.7 V. When the load demand was increased to 12 A, the voltage again increased one more 1.9 V, to 10.6 V. When the load demand was increased to 15 A, the voltage reached 12.5 V (increased by 1.55 times from base case 4.9 V). The neutral-to-earth voltage increased linearly with the load demand current at rate 0.63 V/A at the high load demand node 57. Toward the direction of the substation, the neutral-to-earth voltage increases first diminished, approaching the values close to those of the base case near node 25 (3.7 V). From node 25 to the substation node 1, as the distance increased, the voltages also increased slightly. Near the substation, when the load demand was 15 A, the magnitude of the voltage increased to 13.1 V, 1.42 times of the base case value 9.2 V. From Figure 22 through Figure 24, it can be seen that when a primary high load demand occurs somewhere in the distribution line, the neutral-to—earth voltages increased in most segments along the distribution line. These voltage changes are load demand magnitude and load demand location dependent. The voltages increased as the " load demand currents increased. The most significant voltage increase occurs near the high load demand location. This is due to the large neutral current injection from high local load demand current. The 90 same conditions would be created when the phase line to neutral fault occurred at a specific location along the distribution line. The effect of high load demand on neutral-to-earth voltage is equivalent to having a phase line to neutral fault occurred near the high demand location. The faults in equipment on a primary distribution line have been reported to have resulted in a lowering of the neutral-to-earth voltage in a local area when the fault situation was corrected. Previous research did not explain how this phenomenon could occur. The profiles obtained from the single phase AC model corresponding to Figure 22 through 24 are listed as Figure A4 through A6 in the appendix. 5.1.3 The Distribution System Ground Resistance Calculation Table 5 presents the calculation results of the distribution system ground resistance from four different locations along the power distribution line model of Figure 4. In Table 5, the first row discriminates the different node locations and the first column discriminates the different electric parameters. In the first column, the meaning of Thev_R5‘ and TheleO" is the Thevenin equivalent system ground resistances calculated from 5 V and 10 V test voltages, respectively. As described in Section 4.2.3, the grounding electrode resistance at the test location was removed and replaced with a test voltage of 5 91 mm.._ .00. Nmm. 31.. "*O~m>0£.—. 00... .00. 000. .v... .xmm >om» 000.0 000.0. 000.0. «00.0 .0.auovu. 000.0. 000.0. 000.0. 000.0. "0.0.0010 .0..v v.0.0 .00.0 ~00.v .0 «nevi. 000.0 000.0 000.0 000.0 .0 0.0010 000.0 0n..00 . coao 0 .0000. 00: 000000.000 0Q 0.0000300. 00. m00_0 0000000. 03.808030. 00.0.00 .00.. 00. 0.0.. 0000.50. 0000.» 0.0.0.? 000000.000 00. .0 3.0.0. 0000—00—00 .w 030,—. 92 volts and 10 volts. The 4,800 volt substation supply voltage was replaced with a short circuit. Figure 25 shows the test circuit to determine the system resistance from the farm at node 33. The same technique can be used to determine the system resistance from any location along the distribution line. At node 1 (substation), for the test neutral-to-earth voltages 5 and 10 V, respectively, the simulation program output the current 4.382 A and 8.764 A, respectively. Using Ohm’s Law, R = V/I, both levels of the test voltage gave the same results, i.e., the system resistance at node 1 (substation) was 1.141 ohm. At node 9, the first farm transformer location, for the test neutral-to-earth voltages 5 and 10 V, respectively, the simulation program output the current 8.891 A and 17.780 A, respectively. Using Ohm’s Law, R = V / I, both levels of the test voltage gave the same results, i.e., the system resistance at node 9 was 0.562 ohm. At node 33, near the middle of the distribution line, for the test neutral-to-earth voltages 5 and 10 V, respectively, the simulation program output the current 8.314 A and 16.630 A, respectively. Using Ohm’s Law, R = V/I, both levels of the test voltage gave the same results, i.e., the system resistance at node 33 was 0.601 ohm. At node 57, at the end of the distribution line, for the test neutral-to-earth voltages 5 and 10 V, respectively, the simulation program output the current 4.191 A and 8.382 A, respectively. Using Ohm’s Law, R = V/I, both levels of the test voltage gave the same results, i.e., the system resistance at node 57 was 1.193 ohm. 93 mm 0002 .mm 0000 .0 0:0. 0... 0.00 0000.50. 0.0.0». 00. 00.8.0.0“. 0. 0000.0 .00. 00,—. ..nN 0.09m mm 0002 m 0002 _ 0002 94 From the above description, at each node, the two levels of the test voltage, 5 V and 10 V, gave the exact the same result of the distribution system resistance at that node. This has been expected for the linear circuit model. The distribution system ground resistance is an important indicator for some of the abnormalities in the electrical parameters producing neutral-to-earth voltage along the power distribution system. This is illustrated by Figure 26 and Table 6. Figure 26 and Table 6 present the changes of the distribution system ground resistance (Thevenin Equivalent Resistance) and Thevenin Equivalent Open Circuit Voltages at the location of node 33 to earth as well as neutral-to-earth voltage at node 33 with the resistances increased from 0.086 ohm to 100 ohms in the neutral line segments RD4, RD8, RD12, RD16, RD20 RD56, respectively as shown in the circuit model connection of Figure 27. From Figure 26 and Table 6, it can be seen that generally speaking, the primary ground system resistance at the location node 33 to earth was higher with a bad neutral connection on any segment of the neutral conductor than without the bad neutral connection compared to the base case system (all RDs were 0.086 ohm). The increase of this ground system resistance to earth was very significant when the bad neutral connection occurred near the neighborhood of node 33 where the ground systems resistance was observed. In this location, the ground system resistance for the normal base case was 0.601 ohm. With a bad neutral connection of 100 ohms at RD28, near the left neighbor transformer of the 95 PD4, PDB PD56 : IOO OHM, PESPECTIVELY PPIMAPY SYSTEM GROUND RESISTANCE, VOLTACES, NODE 33—O IO [ - i —+—- Voc33 : —0— NEVIS} ; 8 1 —)(—- Lsys ' m —'?- RF033 ' 1.... . __J ‘ W O 6— . > I m 49%;] E I O 2 -1 O I I I I I I I I I I I I I I :IT 10 o o o o o o o o o o o o o 0 (<12 0 o o o o o o o o o o o o o O II II II II II II II n , II II II II II II m m to o 0- m N (a o sr co 01 co < <2- 00 .— .— m N (\l n r) v 0- v to n m D O Q a o o o o c: o o o c: o 0: Ct at o: o: c: o: a: o: 0: cr 0: o: m Figure 26. The simulation plot of changes of the distribution system ground resistance (Thevenin Equivalent Resistance) and Thevenin Equivalent Open Circuit Voltages at the location of node 33 to earth as well as neutral-to-earth voltage at node 33 with the resistances increased from 0.086 ohm to 100 ohms in the neutral line segments RD4, RD8, RD12, RD16, RD20 RD56, respectively in the DC circuit model. 0.9.08.2 .080 .000 .050 0.00 .000 .000 088.9. 00.. .0..000 0... 0. 000.0 8. 0. 00.0 0.8.0 0.0.0 00.00.00. «0000.000. 0... 003 mm 0000 .0 0m0..0> 0..00.0.-.0..000 00 ..03 ...0 0.0.0 0. mm 0000 .0 000000. 0... .0 m0M0..0> 000.5 0000 00.0203. 0.0050... 000 3000.003. .00.0>.0..m. 0.0050,... 0000.30. 0000.» 80.0... 000000.00 0... .0 00m0000 0... 00.00.00 0. 000000000 00000 00... SN 0.00.... 0mg. ~20. 0:... 3.... 0:... 03.. ~83 swam 02... 8:3 0:... ~33 2.8 2... mm 0002 0:0..000. 00.00.00. .0 00000.00. 00: 00:0.m_00. .000000 00.. 00 :0_.000. 0.0. .0 0.0.0.0.00 00000000. 00.. 97 Table 6. The simulation data of changes of the distribution system ground resistance (Thevenin Equivalent Resistance) and Thevenin Equivalent Open Circuit Voltages at the location of node 33 to earth as well as neutral-to-earth voltage at node 33 with the resistances increased from 0.086 ohm to 100 ohms in the neutral line segments RD4, RD8, RD12, RD16, RD20 RD56, respectively in the DC circuit model. 13le SYSTEH BRUNO RESISTME, m 33-0, R0__ : 1m [I'll 94-9-22 RD8:0Hfl lV_opon Vchloso Vings33_0§RF833 0H:*NEV_CflLthost V: 1_tost R: 885 8958 6.283 4.486 .6013 1.50:!) 4.4850 10 16.63 R04 :100 7.3052 5.2041 .6057 1.5000 5.2039 10 16.51 R08 :100 7.2454 5.1586 .6068 1.5013 5.1586 10 16.48 120123121] 7.4034 5.2378 .6192 1.511!) 5.2381 10 16.15 120167.111) 7. 2792 5.1391 .6246 1.5111] 5.1392 10 16.01 9020:1113 7.7194 5.3026 .6835 1.5% 5.3029 10 14.63 120242111] 7.5011 5.0922 .7097 1.51!!! 5.0919 10 14.09 1:028:11!) 9.1786 5.437 1.0323 1.5000 5.4369 10 9.687 $203221“) 8.976 4.9887 1.1989 1.5000 4.%87 10 8.341 R03621m 6. 7569 3.8607 1.1252 1.5000 3.8607 10 8.887 RD40=1CIJ 7.2473 4.3819 .9814 1.5!!) 4.3811 10 10.19 R0443!” 6.2766 4.2%9 .6940 1.5111] 4.2913 10 14.41 R0483“) 6.5343 4.5151 .6707 1.5% 4.5154 10 14.91 9052000 6.2452 4.4245 .6173 1.5011 4.4244 10 16.2 12056211!) 6.3721 4.5248 .6124 1.5000 4.5248 10 16.33 mm svsren mm Resrsrmce, vumsss, none 33-0 RD4, ma, R012 arms a was Ro_u (940922) R0933; : [tut/Lust ' vapon W50. : Vopon'I-RFS33/(RFB334'R39533_O) $933 a -‘9‘ 5633 R056 : too am, RESPECTIVELY 98 observation, the ground system resistance was 1.032 ohms, 71.7% higher than the normal. With a bad neutral connection of 100 ohms at RD32, near the transformer of the observation, the ground system resistance was 1.199 ohms, 99.5% higher than the normal. With a bad neutral connection of 100 ohms at RD36, near the right neighbor transformer of the observation, the ground system resistance was 1.125 ohms, 87.2% higher than the normal. With a bad neutral connection of 100 ohms at RD40, near the second right neighbor transformer of the observation, the ground system resistance was 0.981 ohm, 63.2% higher than the normal. This implies that a bad neutral connection along the line can be detected by the measurement of the local primary ground system resistance. The distribution system ground resistance is very important information for the evaluation of neutral-to-earth voltage changes due to ground resistance changes at a particular location. This can be seen in next sections. 5.1.4 Substation Grounding Resistance Change Figure 28 presents the neutral-to-earth voltage simulation curves resulting from changing the substation grounding resistance. Such a change can occur due to corrosion, nearby earthwork construction, water-table fluctuation, soil surface layer freezing or other natural season effect. Low substation resistance to earth may be difficult to achieve due to soil conditions. CHANGE IMPACT ON NEV, 4.8KV LINE SUBSTATION R61 0.5, 1, 5, 10, 20 8c 40 OHM, DC CASE 10 (55?? ‘ 2 ‘ E '57“ - O-T ........ 555‘. 'h ............................. 55‘ 1'" V _O' A ,1 .0" > n ‘0'" v '1 4' Lu n v; —+-— $2 -103 n 2"; 0.5 OHM ,_ h' I“ —a- 1.0 OHM .J '0" g E .i’ + 5.0 OHM /; + 10 OHM -20fi y.” + 20 OHM _7' + 40 OHM 1; ,m. // -30 fiTTITIIIIT—TrTllllIIIITITIIIIIWIIITTITIIIIITIWIIIlllllr — n o m o n o n o n o m rx '- v- N N 7’) F) V’ 1' n to W) NODE # (1-57) 940531 b Figure 28. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable substation resistance RS (single-phase DC model simulation) 100 Compared with base case, when substation resistance was increased from 0.5 ohm (base case) respectively to 1.0, 5 .0, 10, 20 and 40 ohms, the neutral-to-earth voltages increased accordingly in some segments near the substation and decreased some distance away from the substation toward the end of the line. Note the most significant changes of the neutral-to-earth voltage occurred near node 1 where the substation was located. At the substation, in the base case, when the substation resistance was 05 ohm, the value of neutral-to-earth voltage was 9.2 V. When the substation resistance was increased to 1.0 ohm, the voltage also increased by 4.9 V, to 14.1 V. When the substation resistance was increased to 5 .0 ohms, the voltage increased by another 105 V, to 24.6 V. When the substation resistance was increased to 10 ohms, the voltage increased another 2.5 V, to 27.1 V. When the substation resistance was increased to 20 ohms, the voltage was only increased by 1.4 V, to 28.5 V. When the substation resistance was increased to 40 ohms, the voltage was only increased another 0.8 V, to 29.3 V. Generally, the voltage change was increased near the substation as the substation resistance was increased; the effect was significant in the resistance range from 0.5 to 5 ohms. This effect on the neutral-to-earth voltage diminished rapidly as the distance increased from the substation (node 1) toward the end (node 57) of the line. With 40 ohms substation resistance, at the substation node 1, the neutral-to-earth voltage was 29.3 V, 3.18 times of the base case value of 9.2 V; at the middle node 33, the voltage was 35 101 V, only 77.8% of the base case value of 45 V; at the end node 57, the voltage was 4.7 V, 96% of the base case value of 4.9 V. From Figure 28, it can be seen that when the substation grounding resistance is increased, the neutral-to-earth voltages increased in some segments near the substation and decreased some distance away from the substation toward the end of the line. These voltage changes are related to the distance from and the resistance-value of the substation. The neutral-to-earth voltages are increased significantly near the substation and changed less and less significantly as the distance from the substation increases. Similar results were reported by Kehrle (1984) and Gustafson (1985) in their simulation. Table 7 lists some of the numerical calculation results in this case. Looking inside from node 1 and earth (referring to Figure 4, Chapter 4), the Thevenin equivalent circuit (when RS removed) resistance (Thev_R) was 1.141 ohm and open circuit voltage (V_open) was 30.176 V. The second row lists the calculated values of the substation neutral-to-earth voltages corresponding to different levels of the substation resistances. For example, when substation resistance RS was 1 ohm, the corresponding substation neutral-to-earth voltage can be calculated as NEV_Cal‘ = V_open x RS/(ThevR + R8) = 30.176 x 1000/(1.141 + 1.000) = 14.094 (V) 102 8m + EVE-» u 26-»! «8.8 26.8 98.8. ownéu 8.: 31¢ .28-»! 8.9 8.8 8.2 806 8°; 8. 3.... £18 _ «3-8 :8 8-9.8 8.9.8 2.2.3... ataxia 185.832: «.92: 58-2 5.33. canon... 39 n5 8:325. 3.3.6 «3.8 83338 .358 cc... 8:22:86 OD 823-2»:7. on. we ems—g 38367353: new cog—8&8: 2:55 .omng 55992830: :383 some 62.538 258m 829?. 8:933. mo $.82 cone—=28 38.8952 .5 035. 103 From this, it can be seen that the substation Thevenin equivalent open circuit voltage was divided in series by the substation ground resistance and the system Thevenin equivalent resistance at this location as shown in Figure 29. The level of neutral-to-earth voltage is determined by the open voltage and the proportional relation between the substation ground resistance value and the system Thevenin equivalent resistance value at this location. A lowered substation grounding mat resistance results in a lowered substation neutral-to-earth voltage. The profile obtained from the single-phase AC model corresponding to Figure 28 is listed as Figure A7 in the appendix. 5.1.5 Neutral-to-Earth Resistance Reduction Figure 30 presents the neutral-to—earth voltage simulation curves resulting from reducing neutral-to-earth grounding electrode resistance RFG33 at the middle of the distribution neutral line. Compared with the base case, when the grounding electrode resistance RFGB3 was reduced from 1.5 ohm to 1.2, 0.9, 0.6 and then to 0.3 ohm at node 33, at node 33 and nearby along the distribution line, the neutral-to-earth voltage decreased as the grounding resistance was reduced. However, this reduction of neutral-to—earth voltage was localized. The most significant neutral-to-earth voltage reduction occurred at node 33 itself. At node 33, in the base case, when RFG33 was 1.5 ohms, the value of neutral-to-earth voltage was 4.5 V. When the RFG33 was decreased to 1.2 ohms, the voltage also decreased by 0.3 V, 104 NUDE l NUDE l l l if e [7 e RS Thev-R RS Thev-R .S ohn J. .5 ohn Figure 29. The substation Thevenin equivalent open circuit voltage is divided in series by the substation { ground resistance and the system Thevenin equivalent resistance at this location. 105 8033 CHANCE IMPACT ON NEV, 4.8KV LINE GROUND R033 1.5, 1.2, 0.9, 0.6 8: 0.3 OHM, DC CASE A > V Lu 0 < ..— 5‘ +0.90HM -6‘ +0.60HM +0.3OHM -8. “'10IIIIIIITIITIIIIIlllIlIllllFIIITIIITTlllllllITIIITIIITI .-— Ln O In C in 0 t0 0 .- ._ a. N n n 4 9 8 :25 NODE # (1-57) 940530-1 Figure 30. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. ground resistance RFG33 change at node 33 (single-phase DC model simulation) 106 to 4.2 V. When RFG33 was decreased to 0.9 ohm, the voltage decreased by another 0.4 V, to 3.8 V. When RFG33 was decreased to 0.6 ohm, the voltage decreased still by another 0.7 V, to 3.1 V. When RFG33 was decreased to 0.3 ohm, the voltage decreased again by another 1.0 V, to 2.1 V. The neutral-to-earth voltage decreased more drastically at this node when RFG33 was reduced from 0.9 ohm to 0.3 ohm than from 1.5 ohms to 0.9 ohm. This voltage reduction effect was less and less significant as the distance increased from node 33 toward both the substation and the end of the distribution line. When RFG33 was 0.3 ohm, at node 33, the voltage was 2.1 V, 46.7% of the base case value of 4.5 V; at the end node 57, the voltage was 4.5 V, 91.8% of the base case value of 4.9 V; however, at the substation node 1, a very small neutral-to—earth voltage change was experienced with the voltage at 9.3 V, slightly changing in the contrary directions to those of nodes 33 and 57, 101.1% of the base case value 9.2 V. From Figure 30, it can be seen that when the neutral-to-earth resistance is decreased somewhere in the middle location of the distribution line, the voltage reduction effect is localized. The most significant voltage reduction occurs at the location where the grounding resistance is reduced. The voltage reduction is less and less significant as the distance increases from that location in either direction. Similar results were also reported by Kehrle (1984) and Surbrook et al., (1988) in their simulation. 107 Table 8 lists some of the numerical calculation results in this case. Looking inside from node 33 and earth (referring to Figure 4, Chapter 4), the Thevenin equivalent circuit (when RFG33 removed) resistance (Thev_R) was 0.601 ohm and open circuit voltage (V_open) was 6.283 V. The second row lists the calculated values of the neutral-to-earth voltages corresponding to different levels of the ground resistances at this location. For example, when ground resistance RFG33 was 0.9 ohm, the corresponding neutral-to-earth voltage can be calculated as NEV_Cal" = V_open x RFG33/(ThevR + RFG33) = 6.283 x 0.9/(0.601 + 0.9) = 3.767 (V) From this, it can be seen that actually at any ground connection location of the distribution line, the system ground Thevenin equivalent open circuit voltage was divided in series by the ground resistance and the Thevenin equivalent resistance (system ground resistance) at this location. Generally speaking, a lowered ground resistance at a particular location along the line will results in a lowered local neutral-to-earth voltage. Prothero et al. (1988) also reported from their field measurement data that their tests showed a net resistance of less than 0.5 ohm for the primary neutral network. The measured resistance of farm ground systems ranged from 2.0 to 5 .0 ohms per farm. The connection of these low resistance farm grounds to the primary neutral network was found 108 Snob. + Eekmohi-a .. .84.! ~8.~ 8....” Sad 3.... 84... Eco->9. 8m. 8. 8o. 8.... 8a.. .8. 8...... ...3-8 “no mmoufiv. mmouafi. mmoH—SN. nab—:0 finch!— ¢t>OF= coco-.3. 08—308 K-o-u a! ..5 ouioui... 9.3.6 80.8 .89.... .002: 0:: coasts... OD omega-0&5... on. we ESQ-BE .a owes? 580-03830: new 35.3.8. 958» dug—9. stun-9-1.330: .583 some .3536... 959% 88»? ..o 3.82 norm—=28 ...Otofizz .m nigh. 109 to have a larger influence over primary neutral-to-earth voltage levels than the additional ground electrodes or counterpoise. This is consistent with the theoretical analysis in this research. Figure 31 presents the neutral-to-earth voltage simulation curves resulting from improving neutral-to-earth grounding by adding an extra grounding electrode of 25 ohms at every node on the neutral conductor where the resistance was previously set at 100 k-ohms. See Figure 4 and Table 2. For this simulation, there is a grounding electrode of not more than 25 ohms at each pole along the distribution line. Compared with the base case, when the grounding electrode number was doubled, the neutral-to-earth voltage was lowered at most nodes (from node 13 to node 57) along the distribution line from the middle to the end. This voltage reduction effect was significant from the end to the middle location of the distribution line. At the end (node 57), the value of neutral-to-earth voltage decreased by 0.6 V, to 4.3 V, 87.8% of the base case value 4.9 V; at the middle node 33, voltage was 3.9 V, 86.7% of the base case value 45 V; at the substation node 1, very small neutral-to-earth voltage decrease (0.1 V) was experienced with the voltage 9.1 V, compared with 9.2 V of the base case. From Figure 31, it can be seen that when the grounding electrode number was doubled uniformly along the neutral line, the neutral-to-earth voltage was lowered a small amount from the middle to 5 the end of the line. This voltage change was insignificant near the substation. 110 INCREASE GROUND ROD NUMBER IMPACT ON NEV ALL GROUND RESISTANCES 100K CHANGED TO 25 OHMS VOLTAGE (V) '10‘rrlllIIIIIIIrITrTrTrIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII .— In 0 In 0 in O in O in O ION .— .— N N r’) n 1' 1' in min NODE # (1 -57) 940530-15 Figure 31. Profile of the neutral-to-earth voltage along the primary distribution line fi'om substation to 57th node with base case vs. ground rod number increasing along the entire system (single-phase DC model simulation) 111 Reduction of the grounding electrode resistance at node 33 in the middle of the line decreased the local neutral-to-earth voltage. Addition of extra grounding electrodes was equivalent to increasing the parallel resistance number and decreasing the actual overall resultant ground resistance. Prothero et al. (1988) also reported from their field measurement that the addition of numerous supplemental grounding electrodes, to the extent that every distribution pole was grounded, had only a slight effect on reducing primary neutral-to-earth voltage. Although increasing the number of grounding electrodes can decrease the neutral-to-earth voltage to some extent, a large number of ground rods will be costly and the effect may not be as good as expected. For this simulation, doubling the number of grounding electrodes along the primary line only resulted in approximately a 12.2 percent reduction in neutral-to-earth voltage at the end of the line. The profiles obtained from the single-phase AC model corresponding to Figure 30 and 31 are listed as Figure A8 and A9 in the appendix. 5.1.6 Primary Operating Voltage Level Change Figure 32 presents the neutral-to-earth voltage simulation curves resulted from changing the primary operating voltage levels. The base case simulation assumes a primary ungrounded conductor operating at 4.8 kV. 112 SUBSTATION SOURCE VOLTAGE CHANCE IMPACT v SOURCE VOLTAGE 2.4, 4.8, 7.2 s- 26.4 KV 10 5“ 01 ______ -. ..::_ A ,-" . > 1 a v -5. < I .— _‘ +2.4KV O >-10‘ +4.8KV +7.2KV +26.4KV -15. -20 llllImIIlTTrllIIITIIIIIIFTIITIIIIITIIIIIITTIITIIIITT v- In 0 In O tn 0 In 0 n v— v- N N '0 n 1' V 8 iii-'3 NODE # (1 -57) 940531 c Figure 32. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case 4.8 kV operating voltage vs. 2.4, 7.2 and 26.4 kV operating voltages (single-phase DC model simulation) 113 When the primary operating voltage levels were increased from 2.4 kV respectively to 4.8 kV, 7.2 kV and 26.4 kV with power unchanged, the neutral-to-earth voltages in all these four distribution systems decreased correspondingly along the distribution line. These voltage profiles had the similar shapes with the different proportion scales. All four voltage profiles approached convergence near node 12. The neutral-to-earth voltages of all four systems decreased as the distance away from the substation increased, reaching zero and changing 180 degree in phase angle near node 12. Then the voltages increased as the distance toward the end of the line increased. The neutral-to-earth voltage profiles changed sharply at first, then leveled off toward the end of the neutral line. At node 12, the neutral-to-earth voltages corresponding to the systems of 2.4 kV, 4.8 kV, 7.2 kV and 26.4 kV were 0.1 V, 0 V, 0 V and 0 V, respectively. At the substation node 1, the neutral-to-earth voltages corresponding to the systems of 2.4 kV, 4,8 kV, 7.2 kV and 26.4 kV were 17.6 V, 9.2 V, 6.2 V and 1.7 V, respectively. At the end (node 57), the neutral-to-earth voltages corresponding to the systems of 2.4 kV, 4.8 kV, 7.2 kV and 26.4 kV were 9.3 V, 4.9 V, 3.3 V and 0.9 V, respectively. Generally, the higher the operating voltage, the lower the neutral-to-earth voltage. This is due to the constant power situation: the higher the operating voltage, the lower the current on the primary side of the transformer. Lower transformer primary current leads to lower current injection to the neutral line and parallel ground path. 114 This neutral-to-earth voltage change effect due to the primary operating voltage change was much more significant in the operating voltage level range from 2.4 -- 4.8 kV than the range from 7.2 -- 26.4 kV. The neutral-to-earth voltage decreased 20% per kV on the average in the operating voltage level range from 2.4 -- 4.8 kV, 13.6% per kV on the average in the range 4.8 -- 7.2 kV, and only 3.8% per kV on the average in the range 7.2 -- 26.4 kV. This implies that striving for high operating voltage levels may not reduce the neutral-to-earth voltage as much as expected. 5.1.7 Secondary Earth Fault Figures 33 through 38 present the neutral-to-earth voltage simulation curves resulting from normal line loading plus a ground fault on the secondary side of one of the transformers. The simulation network used in this case is shown in Figure 7. When the out-of-phase secondary ground faults of 3, 6, 9 and 12 amperes were introduced at the transformer between nodes 416 and 33, at the middle of the distribution line, from Figure 33, compared with the base case, some changes in the neutral-to-earth voltage were observed. The most significant voltage changes occurred near node 33 where the faulted secondary network was attached. At node 33, the voltage increased significantly as the fault current increased. In the base case, when the fault current was zero, the value of neutral-to-earth voltage was 4.5 V. When the fault current was increased to 3 A, the voltage 115 Secondary Ground Fault, Out-of-Phase IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 416 VOLTAGE (V) -1OTT—TITTIIITTIITTTITITTTTTITTITTITTITTIII-TIjTTTT'IT'TTTr -n o In C n o 10 0 ton '— ‘n 53 .— N N n n 1' wt in mm NODE # (1 --57) 940504—4 Figure 33. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 33 (out-of-phase, single-phase DC model simulation) 116 increased by 1.2 V. to 5.7 V. When the fault current was increased to 6 A, the voltage increased by another 1.2 V, to 6.9 V. When the fault current increased to 9 A, the voltage increased an additional 1.1 V, to 8.0 V. When the fault current increased to 12 A, the voltage increased still an additional 1.2 V, to 9.2 V. The neutral-to-earth voltage increased linearly with the fault current at a rate about 0.4 V/A at the faulted location node 33. This voltage change effect was less and less significant as the distance increased from node 33 toward both the substation and the end along the distribution line. When the fault was 12 A, at node 33, the voltage was 9.2 V, 2.04 times of the base case value 4.5 V; at the end node 57, the voltage was 5.7 V, 116% of the base case value 4.9 V; however, at the substation node 1, very small neutral-to-earth voltage change was experienced with the voltage 9.0 V, slightly changing in the contrary directions, 97.8% of the base case value 9.2 V. When the in-phase secondary ground faults of 3, 6, 9 and 12 amperes were introduced at the transformer between node 416 -- 33, at the middle of the distribution line, from Figure 34, compared with the base case, it can be seen that neutral-to-earth voltage changed in a similar way to the out-of-phase secondary ground fault situation except the voltage changes were in the contrary direction. Note in Figure 34 that a 12 ampere secondary in-phase ground fault is subtractive with the primary load which produced base neutral-to-earth voltage resulting in a net neutral-to-earth voltage value near zero at node 33. 117 Secondary Ground Fault, In-Phase IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 416 10 5-1 A > V 8 0d --------- < '5' -B-—SA -54 +6A +9A +12A ...10 I v- 10 0 1n 0 tn 0 In C In O ION '- v- N N I") n V Q' In IOU-D NODE # (1 -57) 940604-3 Figure 34. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 33 (in-phase, single-phase DC model simulation) 118 When the out-of-phase secondary ground faults of 3, 6, 9 and 12 amperes were introduced at the transformer between node 404 -- 9, the first farm transformer location along the distribution line, from Figure 35, compared with the base case, it also can be seen that there were changes in the neutral-to-earth voltage. The significant voltage changes occurred at the node 12 near the faulted location node 9. At node 12, the voltage was increased significantly as the fault current increased. In the base case, when the fault current was zero, the value of neutral-to-earth voltage was 0 V. When the fault current was increased to 3 A, the voltage also increased by 0.9 V, to 0.9 V. When the fault current was increased to 6 A, the voltage increased by another 1.0 V, to 1.9 V. When the fault current was increased to 9 A, the voltage increased an additional 0.9 V, to 2.8 V. When the fault current was increased to 12 A, the voltage increased still an additional 0.9 V, to 3.7 V. The neutral-to-earth voltage increased linearly with the fault current at a rate about 0.3 V/ A near the faulted location. This voltage change effect was less significant as the distance increased from node 12 in either direction of the distribution line. When the fault was 12 A, at node 12, the voltage was 3.7 V, much higher than the base case value 0 V; at the end node 57, the voltage was 5 .0 V, 102% of the base case value 4.9 V; however, at the substation node 1, the voltage was 7.3 V, changing in the contrary directions to those of nodes 33 and 57, 79.3% of the base case value 9.2 V. When the in-phase secondary ground faults of 3, 6, 9 and 12 amperes were introduced at the transformer between node 404 -- 9, the 119 Secondary Ground Fault, Out-of-Phase IMPACT ON NEV, FAULT .3, 6, 9 8c 12 AT 404 10 -+—BASE +3A VOLTAGE (V) -x—-BA +9A +12A -10 IIITTTTVTTIVTTTIIIITTTTTTIIIIIIIITTTIIIIIIIIIIITITTIIIT '- 10 C 1n 0 IO 0 1n 0 1n 0 ION v— v- N N I") F) 1’ V’ In 1010 NODE # (1 -57) 940604-2 Figure 35. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 9 (out-of-phase, single-phase DC model simulation) 120 the first farm transformer location of the distribution line, from Figure 36, compared with the base case, it can be seen that the neutral-to-earth voltage changed in a similar way to the out-of-phase ground fault situation except the voltage changes went to the contrary direction. With an out-of-phase secondary ground fault at node 33 in the middle of the line, most customers experienced an increase in neutral-to-earth voltage as shown in Figure 33. When there was an in-phase secondary ground fault at node 33 in the middle of the line, most customers experienced a decrease in the neutral-to-earth voltage (Figure 34). But this was not true when the secondary ground fault was at a location near the substation. Examination of Figures 35 and 36 shows that some customers experience a lowering of the neutral-to-earth voltage while others experience an increase whether the secondary ground fault was in-phase or out-of-phase with the primary load which produced the base neutral-to-earth voltage. When the out-of-phase secondary ground faults of 3, 6, 9 and 12 amperes were introduced at the transformer between node 428 -- 57, the last farm transformer location of the distribution line, from Figure 37, compared with the base case, it still can be seen that there was some changes in the neutral-to-earth voltage. The most significant voltage changes occurred near the end node 57 where the faulted secondary network was attached. At node 57, the voltage was increased significantly as the fault current increased. In the base case, when the fault current was zero, the value of the neutral-to-earth voltage was 4.9 V. When the fault current was increased to 3 A, the voltage also 10 VOLTAGE (v) 121 Secondary Ground Fault, In-Phase IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 404 -15IIITI[ITIIIIITIITTTITIFTIIIITIIIITIITIIITIIIIlllllrill v- 10 O In 0 in O n o 10 0 v- v- N N n n v 1' In 31'?- Figure 36. NODE # (1 -57) 940504-1 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 9 (in-phase, single-phase DC model simulation) - 122 Secondary Ground Fault, Out-of-Phase IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 428 15 F 10« ' t 1"{':'- '—:::‘J A l't'f,.-+:’-:::===‘- \>_/ 5 q .. f- ~.‘ : ;;:r=-="; F LIJ 0 <1 1.— _l O 011- ----------------------------------------------- > +BASE +12A -10 IIIIIIIIIIIIIIIITTII1IIIIIIIIIIIIIIIIIIITIIIIITIITIIlllr '- 1.0 O n O n o m o m o n" v- v- N N n n 1’ 1' In IDIO NODE # (1 -57) 940604-6 Figure 37. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 57 (out-of-phase, single-phase DC model simulation) 123 increased by 1.9 V, to 6.8 V. When the fault current was increased to 6 A, the voltage increased by another 1.7 V, to 8.5 V. When the fault current was increased to 9 A, the voltage increased by an additional 1.8 V, to 10.3 V. When the fault current was increased to 12 A, the voltage increased by still an additional 1.6 V, to 11.9 V. The neutral-to-earth voltage increased linearly with the fault current at a rate about 0.53 -- 0.63 V/A at the faulted location node 57. This voltage change effect was less significant as the distance increased from the end node 57 toward the substation node 1 along the distribution line. When the fault was 12 A, at the end node 57, the voltage was 11.9 V, 2.43 times of the base case value 4.9 V; at node 33, the voltage was 5 .2 V, 116% of the base case value 4.5 V; however, from the node 10 to substation node 1, the voltage had almost no change. When the in-phase secondary ground faults of 3, 6, 9 and 12 amperes were introduced at the last farm transformer location node 428 -- 57, from Figure 38, compared with the base case, it can be seen that the neutral-to-earth voltage changed in a similar way to the out-of-phase ground fault situation except the voltage changes went to the contrary direction. The net effect of the in-phase secondary ground fault was to reduce the neutral-to-earth voltage. From Figure 33 through Figure 38, it can be seen that for a ground fault on the secondary side of a transformer, the neutral-to—earth voltages along the distribution line were changed to some extent. Generally, this kind of change is fault-size, fault-phase and fault-location dependent. The heavier the fault currents, the more 124 Secondary Ground Fault, In-Phase IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 428 10 51 , ...... .. _..._ 1 .' OQ“<;:“ ‘-::::===‘ A --a > V 8 K 0.1 ------------------------------------------- - - <( 1— 7 _.| O +BASE > +315- ...5-1 +6A +12A -1OTTTTTITTTTTTIITTIIITIITITIIIIlllllll‘lllIIIIIIIITTITTIrl '— ID 0 In 0 In C in O ID O on v- P N N l’) n V V 10 1011') NODE # (1 -57) 940604-5 Figure 38. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 57 (in-phase, single-phase DC model simulation) . 125 significantly the neutral-to-earth voltages change. The voltages change in contrary directions when the in-phase or out-of-phase fault occurs. Much more significant changes in neutral-to-earth voltage occur at and near the node at which the faulted secondary circuit is attached. The farther the distance along the line away from the fault node, the less significant the neutral-to-earth voltages change. A similar result was also reported by Kehrle (1984) and Dick et al. (1987) in their simulation. And Bodman et al. (1981) reported from their field survey and measurement process that in one installation, a short circuit within the milk pump resulted in a constant 21.3 V voltage between the milk pump and the milk house floor. In this simulation, a significant neutral-to-earth voltage change due to a secondary ground fault was confined to the distribution system within a limited distance of approximately one-half mile of the fault location. As the level of fault current increased, the neutral-to-earth voltage change on the distribution line increased to approximately one mile for a heavy ground fault. The change in level of neutral-to-earth voltage due to a secondary ground fault is greater when the fault occurred at the end of the line than at the middle of the line as can be seen from Figures 35 through 38. Near the substation the amount of change was less, but whether a particular location would experience a net increase or decrease in neutral-to-earth voltage was difficult to predict. When a secondary fault occurred at the end of the line as was the case at the middle of the line, an out-of—phase secondary ground fault caused an increase in 126 neutral-to-earth voltage for all customers. For the in-phase secondary ground fault, customers experienced a reduction of neutral-to-earth voltage unless the amount of reduction was great enough to result in a phase angle change in the neutral-to-earth voltage. In this latter situation, it is possible for the net rms value of the voltage to actually become higher. It is important to note that a secondary ground fault produced neutral-to-earth voltage can be additive or subtractive to the primary line load produced neutral-to-earth voltage. The elimination of a secondary ground fault at one location resulting in a lowering of neutral-to-earth voltage at that location may indeed cause a significant increase in the neutral-to-earth voltage at other locations. When a secondary ground fault is discovered, it is recommended that voltage measurements be taken along the distribution line in the area after the elimination of the secondary ground fault to determine if any customers have experienced an increase in neutral-to-earth voltage. The out-of-phase and in-phase secondary ground fault condition at the end of the distribution line is illustrated in Figures 39 and 40. Figure 39 shows the end of the distribution line with the simulated secondary electrical system attached. The out-of-phase fault condition with respect to the primary line is defined by observing the phase relationship of the phase angle of the fault current of the secondary ground fault circuit with respect to the primary current. It is important to note that the fault current and the normal line load current flowing through the grounding electrodes is in-phase thus resulting in a net 0:: 6:22.36 2: ..O can 2.. .a 5n one: .a vogue... .38 2:55 3.29.9.6 .3662... .53 30:3 2.8.00.0 9:05.03 0:... 5.26:8 .8502 an 9.33 page 3.. .II' page p.53. l-I'. 127 ..- 3 . -II A" 5 5;: m u. m m as. mmam ¢mfi _ an: N m f 2.... 52 Mm ‘III. ‘III omv am?— omv muse 128 0:: 5:353.» 0.: go 0:0 05 .0 5. 0.3: .0 @0583 .38 9:5... 00.23;: b09500» 55 30:30 03:00.0 9.6.50.3 can 3.03:3 .8302 .3 0:85 mi m 39 an. 28. RV II' ..l' .ll m w II D“ —m TI I Name .22 ‘III was. mmac 33. «max when .33 m m .0 >8. lulu“ In... I! ‘ 1111'—1—d1”1¢* m ‘ aunt ’ ..l 02.! a m“. ; 129 increase in grounding electrode current at the end of the line. Figure 37 shows the increase in neutral-to-earth voltage at the end of the line as a result of the increase in grounding electrode current. Figure 40 shows the end of the distribution line with simulated secondary network attached at node 57. In this case the secondary ground fault is in-phase with respect to the primary load. Note in Figure 40 that the normal line load produced grounding electrode current is out-of-phase with the secondary ground fault current flowing on the grounding electrodes. There will be a net reduction of the grounding electrode current at the end of the line when there is an in-phase secondary ground fault and the neutral-to-earth voltage will be reduced as shown in Figure 38. The previous analysis of secondary ground faults assumes a 0 degree or a 180 degree phase difference between the current flowing in the neutral, grounding electrodes and earth as a result of normal line loading and secondary ground fault current. This will only occur if the power factor of the primary distribution line and of the secondary ground fault circuit are unity. This analysis shows the maximum changes possible as a result of a secondary ground fault. If the primary neutral grounding electrode current and the secondary fault current flowing on the grounding electrode are at some phase angle difference other than 0 degrees or 180 degrees, the resultant current flowing in the grounding electrode will be at some magnitude less than the maximum shown here and more than the minimum values. It would, therefore, be 130 expected that less extreme results would occur for a secondary ground fault on an actual operating single-phase distribution line. The profiles obtained from the single-phase AC model corresponding to Figure 33 through Figure 38 are listed as Figure All through Figure A16 in the appendix. 5.1.8 Primary Phase-to-Earth Fault Distribution line faults can occur because the lines are exposed to the natural elements. Strong winds, heavy rains, lightening and tornado-like weather are facts of life in most parts of the United States. Figure 41 presents the neutral-to-earth voltage simulation curves resulting from fault current through a resistance between the primary ungrounded line conductor at node 416 and the earth in the single phase distribution line model (circuit connection in Figure 8). Compared with the base case, when fault current was increased from 0 A (base case) respectively to 3 A, 6 A, 9 A and 12 A, the neutral-to-earth voltages increased accordingly in some segments near the substation and decreased some distance away from the substation toward the end of the line. This is shown in Figure 41. Note the most significant changes of the neutral-to-earth voltage occurred near node 1 where the substation was located. Near the substation, in the base case, when fault current was zero, the value of neutral-to-earth voltage was 9.2 V. When the fault was increased to 3 A, the voltage also increased by 1.0 V, to 10.2 V. When the fault was increased to 6 A, the voltage 131 PRIMARY-GROUND FAULT IMPACT ON NEV 10 VOLTAGE (V) Figure 41. DC MODEL, FAULT 3, 6, 9 8c 12 A AT 416-O TjTrT—TllTIITIITTTTWIITTTTITTTTITIITTTTTTTIIITTTTTIITVTT .— n o in o n o in o n o tnrx .— -- N N n n vr v. in non NODE # (1 -57) 9405300 Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with an ungrounded phase conductor to earth fault at node 416 compared with the normal line (single-phase DC model simulation) 132 increased by another 1.0 V, to 11.2 V. When the fault was increased to 9 A, the voltage increased again by 1.0 V, to a level of 12.2 V. When the fault was increased to 12 A, the voltage reached 13.2 V (increased by 43.5% from the base case of 9.2 V). The neutral-to-earth voltage increased linearly with the fault current at a rate of 0.33 V/A near the substation node 1. This effect of the change of the neutral-to-earth voltage diminished rapidly as the distance increased from substation node 1 toward the end (node 57) of the line. In a 12 A fault, at the middle (node 33) of the line, the voltage was 4.3 V, 95.6% of base case value 4.5 V; at the end node 57, the voltage was 4.8 V, 98% of the base case value of 4.9 V. Figure 42 presents the comparison of the neutral-to-earth voltage simulation curves resulting from a 12 A simulated fault from the primary line conductor to earth introduced at three locations -- node 404, node 416, and at node 428. It can be seen that the neutral-to-earth voltage profiles along the distribution line were identical for all three fault cases. An observed abnormally high neutral-to-earth voltage near the substation may be caused by a primary ungrounded line conductor to earth fault at any point along the whole single phase distribution system. It is important to note from Figure 41 and 42 that the neutral-to-earth voltage decreased from node 15 to the end of the line when a primary ungrounded line conductor to earth fault occurred at any location along the single phase distribution line. ‘Even when the 133 PRIMARY-GROUND FAULT IMPACT ON NEV DC MODEL, FAULT 12 A AT 404-0, 416-O & 428-O lO 5- A 2, 0+ -------- - ------------------------------------ LJJ O < ’— _J o -5. > —+— BASE —a— 404 . . -I— 416 _10-1 .’ + 423 '15 FTFTIIIITIITIIIlIIIFIITIIIIIIIIIIIIIIIIIIIIIITIIIITTTTTT '- W O In C tn 0 in O I!) O n l\ v— r- N N f") n V V’ L0 L01") NODE # (1 -57) 94053013 Figure 42. Profile of the neutral-to—earth voltage along the primary distribution line from substation to 5 7th node with 12 A phase conductor to earth fault at node 404, 416, or 428 compared with normal line (single-phase DC model simulation) 134 primary fault to earth occurred near the end of the line (node 428) the neutral-to-earth voltage was still decreased at the fault node as compared to the base case without a fault condition. From Figure 41 it also can be seen that it is not possible to determine that a primary phase line to earth fault is actually present (node 416) by observing a neutral-to-earth voltage abnormalities in the area of the fault. Figure 43 presents the neutral-to-earth voltage simulation curves resulting from fault current through a resistance between the one primary phase line conductor (phase A, referring to Figure 9) at node 416A and the earth in the three-phase four-wire distribution line model (Yo/Y0 connection). From Figure 43, it can be seen that under normal balanced and no fault operational condition (base case), the neutral-to-earth voltages in the three-phase four-wire (Yo/Yo connection) distribution system were zero all along the neutral line. Compared with the base case, when fault current was increased from O A (base case) respectively to 3 A, 6 A, 9 A and 12 A, the neutral-to-earth voltages increased accordingly all along the distribution line. Note the most significant changes of the neutral-to-earth voltage occurred near node 1 where the substation was located. Near the substation, in the base case, when fault current was zero, the value of neutral-to-earth voltage was also zero. When the fault was increased to 3 A, the voltage increased by 1.0 V, to 1.0 V. When the fault was increased to 6 A, the voltage increased by another 1.0 V, to 2.0 V. When the fault was increased to 9 A, the voltage increased again by 1.0 V, to a level of 3.0 V. When the fault was increased to 12 A, the 135 SINGLE LINE TO GROUND FAULT ON NEV, 4.8KV 3-PHASE MODEL, FAULT 3, 6, 9 8c 12 A AT 416-O 5 —~+—BASE 4 —a—:5A +6A 34 +9A A - > +12A v 8 2 < 1.— .1 O > -1 111[IITITITTTTIIIIIITTTIIIIIIIIIITITTIIITITIFTTTTITIIII '- In O 10 O in O to O in O 1.05 .- — N N n n v- v- 1:1 mm NODE # (1 —57) 9405301d Figure 43. Profile of the neutral-to-earth voltage along the three-phase primary distribution line from substation to 57th node with an ungrounded phase conductor (phase A) to earth fault at node 416A compared with the normal line (three-phase AC model simulation, also referring to Figure 6 and Figure 9 for the circuit connection) 136 voltage still increased by 1.0 V, to 4.0 V. The neutral-to-earth voltage increased linearly with the fault current at a rate of 0.33 V/A near the substation node 1. This effect of the change of the neutral-to-earth voltage diminished rapidly as the distance increased from substation node 1 toward the end (node 57) of the line. In a 12 A fault, at the middle (node 33) of the line, the voltage was 0.2 V, a very slight increase compared with base case value of 0 V. From the node 40 toward the end node 57, the voltages were 0.1 V, very close to the base case value of O V. Figure 44 presents the comparison of the neutral-to-earth voltage simulation curves resulting from a 12 A simulated fault from the primary single phase-line conductor to earth in the three-phase distribution system introduced at three locations -- nodes 404A, 416A, and 428A. It can be seen that the neutral-to-earth voltage profiles along the distribution line were almost identical for all three fault cases. An observed abnormally high neutral-to-earth voltage near the substation may be caused by a primary single line conductor to earth fault at any point along the whole three-phase distribution system. From Figure 41 through Figure 44, it can be seen that primary phase line to earth fault occurred somewhere in the distribution line systems (single-phase or three-phase system) will cause the neutral-to-earth voltage changes all along the lines. These voltage changes are fault-size dependent and fault-location independent. The voltage changes increase as the fault currents increase. The most 137 SINGLE LINE T0 GROUND FAULT ON NEV, 4.8KV S-PHASE MODEL, FAULT 12 A AT 404, 416 a 428 -0 5 n —+—BASE 4 1 \‘ +404 \\‘_ +416 3-4 '3“ A +428 > V \‘ LL] 3 2‘ .—. ..J O > 1-1 0. '- ++++++++++++++++++ -1 Ill[ITTrTrTlTTTTTTI[IT]TTIIITIlTjTUIIIIII'TTTTWUIIIIF '- In C In C In C In C In 0 In '- v— N N n n V V In 1011': NODE # (1 -57) 940531 e Figure 44. Profile of the neutral-to-earth voltage along the three-phase primary distribution line from substation to 5 7th node with 12 A phase conductor (phase A) to earth fault at node 404A, 416A, or 428A compared with normal line (three-phase AC model simulation, also referring to Figure 6 and Figure 9 for the circuit connection) 138 significant changes of the neutral-to-earth voltage occur near the substation. The voltage profiles of the same faults occurred at the three different locations (the middle and the both ends of the line) are almost identical for the corresponding single- or three- phase models. Between the single-phase and three-phase distribution system, the neutral-to-earth voltage changes caused by a primary phase line to earth fault are different on the following two aspects: 1. Along the single-phase distribution system, the voltages increase in some segments near the substation and decrease some distance away from the substation toward the end of the line compared with the corresponding base case; while along the three-phase distribution system, the voltages increase all along the distribution line compared with the corresponding base case. 2. The overall neutral-to-earth voltages were substantially lower along the electric power distribution system of the three-phase four-wire Yo/Yo connection than that of the single-phase. This also should be true for other case studies in preceding sections. The reason is that along the neutral line of the three-phase system, the neutral current consists of three-phase components with different phase angles 120 degrees out-of-phase and the sum. of these three vectors (or phasors) under the balanced operational condition should be zero. This greatly reduces the base 139 neutral-toearth voltages or neutral-to-earth voltages in the base cases. The behaviors of neutral-to-earth voltages along the three-phase distribution systems under different operational conditions have not been well documented prior to this study. The profiles obtained from the single-phase AC model corresponding to Figure 41 and Figure 42 are listed as Figure A17 and Figure A18 in the appendix. 5.2 Guidelines to Identify NEV along the Distribution Systems Based upon the research analysis of the computer simulation results on neutral-to-earth voltage in the preceding sections, the following guidelines can be established to identify the sources of neutral-to-earth voltage originating from the parameter changes of the power distribution systems. A. Excessive Neutral-to-Earth Voltage Occurs near Substation If the field investigation reveals the excessive neutral-to-earth voltage near the substation, the possible reasons are: 1. load demand imbalance in primary three-phases. 140 2. high resistance primary neutral connection or undersized neutral conductor near the substation. 3. secondary in-phase ground fault near the substation. 4. primary ground faults at any point along the distribution line. 5. high resistance substation grounding (e.g., possible ground mat corrosion). 6. Heavy load demands (or line to neutral faults) at any point along the distribution line. B. Excessive Neutral-to-Earth Voltage Occurs away from the Substation If the field investigation reveals the excessive neutral-to-earth voltage away from the substation, the possible reasons are: 1. load demand imbalance in primary three phases. 2. high resistance primary neutral connection or undersized neutral conductor near that location. 141 3. high resistance grounding or inadequate grounding (e.g., ground rod corrosion) near that location. 4. secondary out-of-phase ground fault near that location, either at the sight or at a neighbor location in the immediate area. 5. heavy load demand (or primary line to neutral fault) near that location. Standard neutral-to-earth voltage measurement and diagnostic techniques are appropriate and should be followed at the location where neutral-to-earth voltage has an elevated level. Procedures published by Surbrook et al. (1988) are good procedures to follow. If these procedures fail to find the source of the elevated neutral-to-earth voltage at the farm, then these guidelines can be used to more efficiently identify an off-farm cause for the elevated neutral-to-earth voltage. 5.3 Field Tests and Analysis of Neutral-to-Earth Voltage Gradient Farm field tests were conducted to study the neutral-to-earth voltage gradient distribution near grounding electrodes on the primary and secondary sides of a neutral isolated distribution transformer. Because the secondary ground rod is most likely placed in the gradient of the primary ground rod, and that the earth has a finite 142 resistance, a purpose of this study was to determine how much secondary neutral-to-earth voltage would arise from the primary electrical system. And finally, what are parameters which influence the amount of primary neutral-to-earth voltage which will appear on the isolated secondary electrical system neutral. The equivalent circuit of the isolated primary and secondary electrical system neutrals and grounds as proposed by Althouse (1990) was studied to determine if it was accurate, and if modifications were necessary. 5.3.1 Test of NEV Gradient Distribution, Primary One Ground Rod A specific test voltage was applied to the ground rod utilized as the primary transformer ground rod. This was done using a variable transformer between the test ground rod and a 6.2 ohm grounding electrode system located 400 feet from the test ground rod. The distance was made large so that the earth voltage gradient would not influence each other. The primary ground rod resistance measured by the three point fall of potential method was 18.6 ohms. Voltages in the following tables and figures are ground rod to reference ground voltages. The reference ground representing true earth was located 400 feet from the test ground rod and more than 400 feet from any other grounding electrode. The utility distribution system in the area was an ungrounded delta system and there were no underground pipelines or overhead transmission lines in the area. 143 Table 9 presents the test data of the neutral-to-earth voltage gradient distribution resulting from one earth electrode rod as the primary ground rod at a distribution transformer. Figure 45 shows the corresponding three dimensional graphic plot of the voltage gradient distribution and Figure 46 shows the equi-potential lines of the voltage gradient distribution in this case. For detailed analysis, the voltage gradient distribution in the smaller inner square ABCD of the test plot (referring to Section 4.3.1) is presented here. Table 9, Figure 45 and Figure 46 show that the ground rod neutral-to-earth voltage created the highest peak at the very immediate vicinity of the ground rod and then diminished very rapidly along all directions. Nearly 60% of the voltage dropped within the distance of 1 foot (0.3 m) from the ground rod and nearly 80% of the voltage dropped within the distance 6 feet (1.83 m) from the ground rod. The voltage distribution was symmetric along all directions. In order to confirm the symmetric distribution of the voltage gradient of the single rod, from the center (20, 20) of the test plot, along the four radial directions of straight north, straight south, straight west and straight east, the earth voltage measurements were taken up to 100 feet (30.48 m) distance. Table 10 shows the measurement data and Figure 42 shows the graphic plot of the data. From Table 10 and Figure 47, it can seen that the voltage gradient distributions along four directions are almost identical and symmetrical. 144 N¢.~ NO.— so.— so.“ no.“ 08.“ ms.— mo.“ o.~ on.— an.“ ad vo.N OO.N NO.N Na." ha.— am." «0.. hh.~ oo.— to.~ on.~ ~— w~.~ NN.N -.N v«.N oo.~ a0.— '0._ no.“ as.“ an." no." N— .v.~ vv.~ om.~ m.N MN.“ ou.N nO.N 00.— 50.. o.— 00.« mg no.N vo.~ 0.N 0v.N on.“ 0N.N 0—.N vo.~ 06.— v0.— nh.— Va oa.~ NO.N no.~ uh.N on.~ NQ.N ~m.~ o—.N 0O.— v¢.~ o." n“ NM.M 0N.m uo.m nO.N o.N on.N Nv.N vN.N 0°.N no.“ '0.“ o— No.m v¢.m Nv.m c—.m so.“ on.“ Nfl.~ NM.N vu.N OO.N oo.~ Nu v.v ~N.v mo.m on.m «u.m NO.N mo.N Nv.N N.N oo.~ «0.— on mv.n No.n hfl.v kh.m 0N.m OO.N wo.N ov.~ MN.N oo.~ n5.~ on vs.~— on.» n.v n0.m om.n mo.n vs.“ ov.~ VN.N oO.N 06.“ ON nm.n «o.n v.1 o.m an.m «o.m oo.N nv.~ QN.N NO.N na.¢ —N n. v.v to.v va.m o—.m O.N 0.N hm.N «N.N mo.~ no.“ «N oo.m 0&.m m¢.m NN.m no.m nu.~ on.N mm.N v~.N 00.« a.— MN ~v.m om.m VN.m on.~ on.~ ~0.N nm.~ v~.N to.“ ‘0." no.~ vfl ~6.m 00.N ~0.N «N.N on.~ nv.~ NM.N n—.N 00.. 00.— ON.— nu -.~ oo.~ vo.~ ~n.~ ~v.~ m.~ o~.N ~0.N do.“ N¢.~ MN.— 0N o¢.N nv.N om.N nm.~ VN.N n—.N vo.~ vo.~ do.“ mn.~ 00.— NN VN.N MN.N 1N.N o—.~ co.“ «O.N o.« mo.~ vs.— oo.— o.— ON oo.~ no.“ vo.N «o.— to.“ n¢.— vo.— as.” no.« kn.“ nn.~ 0N oo._ ao.— oo.~ oo.~ no.— on.“ «5.. v0.— mn.~ mn.— ov.~ on ON a“ o— s— 0‘ n— Cu mu N— «a on nasv x .Aasv > «Immhova .068 azaoam uzo >¢¢t~¢t .CFCO haw» h2fi~a¢¢a >mz Coo“ & :5. Ease: no. 035020 .836 03:7. Bo: cozantfio 2.060% 093.9 Eager—830: 05 .3 San 20805308 amok. d 0305. 145 vv.. .0.. 00.. 00.. 00.. ms.. 0.. N0.. 00.. 00.. 0. .0.. 00.. 00.. N5.. 05.. 00.. .0.. 00.. '0.N 00.N .. 00.. 00.. Nn.. 05.. 00.. N0.. ~0.N m..N v..N .N.N N. 00.. .~.. N0.. .0.. 00.. ...N N.N 0N.N 00.N 0v.N m. 00.. 0h.. 00.. 00.. 00.N 0N.N 0N.N 0v.N v0.N h0.N v. 05.. .0.. .0.. 00.N NN.N v.N v0.N 00.N m0.N v0.N 0. 0b.. .0.. 00.N m..N m. 00.N .N.N .0.N no.0 NN.m 0. .0.. 00.. 00.N N.N Nv.N 00.N N0.n NN.m 00.0 .h.m N. 0.. .0.N ...N MN.N '0.N v&.N m..m .v.m 00.0 MN.v 0. N0.. N0.N N.N v.N N0.N 00.N VN.m v0.0 .m.v N..0 0. 00.. N0.N 0..N mn.N .0.N 0.N 5N.m .~.m 00.0 mv.0 ON 00.. N 0..N NM.N 0.N N0.N .N.m N0.m N.v v0.v .N 00.. .0.N 0..N 00.N 00.N MN.N 00.0 Nv.m 00.0 0N.v NN 00.. 00.. ...N 0N.N 0v.N v0.N .0.N 0..m v0.0 mn.m MN 08.. 00.. N0.N 0..N 0M.N N0.N N&.N N0.N v..0 .m.m 0N 05.. 05.. 00.. ~0.N 0N.N Nm.N '0.N N0.N 00.N ~0.N 0N .h.. 00.. 00.. 00.. '0.N NN.N 00.N 0Q.N s0.N v0.N 0N N0.. 00.. 0.. 00.. 00.0 00.N N.N 0N.N vm.N v.N NN 00.. 00.. .h.. 00.. 00.. 00.. 00.N ...N 0..N .N.N 0N .0.. 00.. N0.. 05.. 0b.. «0.. 0.. n0.. 00.. '0.N 0N Nv.. 09.. 00.. 00.. 00.. mu.. 0.. .0.. 00.. 00.. 00 00 0N 0N sN 0N 0N vN 0N NN .N “at. x ..ubv > .imNhov0 .000 020000 020 >¢¢t.¢0 .0h00 hmmb h20.0¢¢0 :02 0.233 a .2: 146 AEUTRAL—TO—EAPTH VOL TAGE ( l/J Figure 45- Three dimensional graphic plot of the neutral-to-earth voltage gradient distribution from single driven electrode rod (length unit is foot) 147 EQUl—ROTENTIAL LINES, ONE ROD, DETAIL, 6—9—94 10 1s 20 25 30 30 r I r 30 25 *- - 25 W 10 n] N 20 - 20 1s - ~ 15 e 10 1 1 1 1o 10 1s 20 25 30 Figure 46. Equi-potential lines of the neutral-to-earth voltage gradient distribution from single driven electrode rod (length unit is foot) 148 Table 10. Test measurement data of neutral-to-earth voltage gradient distributions from single driven electrode rod along four directions The NEV Gradiont with 5109!. Rod along 4 diroctions 940808-1 DistancozNorth :East :South :Uost 3 (inch) 0 12.64 12.8 12.72 13.09 1 8.94 9.03 8.75 8.96 2 7.99 7.86 7.76 8.4 3 7.51 7.37 7.41 7.74 4 7.08 7.05 7.09 7.41 5 6.75 6.74 6.85 7.15 6 6.53 6.47 6.6 6.72 7 6.4 6.22 6.21 6.5 8 6.3 6.01 5.82 5.96 9 6.24 5.83 5.76 5.72 10 5.56 5.63 5.68 5.62 11 5.42 5.52 5.63 5.54 12 5.33 5.44 5.5 5.47 15 5.05 5.15 5.27 5.24 18 4.88 4.84 4.92 5.04 21 4.71 4.58 4.67 4.74 24 4.47 4.4 4.52 4.6 30 4.14 4.04 4.15 4.25 36 3.9 3.82 3.84 3.96 42 3.6 3.47 3.57 3.68 (Foot) 4 3.39 3.25 3.36 3.47 S 3.02 2.91 3.03 3.11 6 2.7 2.63 2.73 2.82 7 2.43 2.39 2.46 2.51 8 2.22 2.17 2.31 2.31 9 2.04 1.98 2.08 2.15 10 1.89 1.88 1.96 1.99 15 1.35 1.38 1.45 1.43 20 1.07 1.11 1.15 1.15 30 .79 .78 .81 .79 40 .58 .59 .61 .62 50 .47 .46 .48 .49 60 .39 .36 .4 .42 70 .31 .29 .33 .33 80 .27 .24 .27 .28 90 .22 .21 .23 .24 100 .21 .18 .2 .21 149 The NEV Gradient along 4 directions SINGLE ROD ELECTRODE 151 “‘B—- N + E 10* A “F S > v + w LiJ O < }_.. __1 O > 5.. O T T T T O 20 4O 60 80 100 DISTANCE FROM CENTER (FEET) 940606-1 Figure 47. Neutral-to-earth voltage gradient distributions from single driven electrode rod along four directions (length unit is foot) 150 Theoretically speaking, (IEEE, 1983; IEEE, 1991; Tag, 1964 and Kraus, 1953) for the single-driven ground rod electrode in a uniform soil, its earth resistance is given by the formula: R = 1’ Ln 4 x L (5.1) 2 x «XL D and its ground electrical potential away from the rod is v: ”P (1.114"L _Ln X2 _Ln X3 ...) (5.2) 2 x 1r x L D X1 X2 where p is resistivity, L is the length of the rod, D is diameter of the rod, X1, X2, X3, are horizontal distances from the rod, I is the current, R is ground resistance, and V is the ground potential away from the rod. Taking the voltage at the ground rod as reference base, the equation (5.2) divided by I x R will yield the per unit normalized neutral-to-earth voltage: U (per unit) = 1 - [Ln(X2/X1) - Ln(X3/X2) - ]/Ln(4xL/D) (5.3) The test rod length is 8 feet (2.44 m) and the diameter D is 5 / 8 inch (0.0159 m). Plotting out the voltage profile up to 15 feet (4.6 111) defined by (5.3) with the comparison to the test measurement data along the east direction, the result is shown in Figure 48 and the corresponding numeric values is shown in Table 11. The test data from Table 10 was normalized by dividing all values by the "voltage at the Table 11. 151 Data comparison between theoretical value calculated from equation (5.3) and field measured value of neutral-to-earth voltage gradient distributions from single driven electrode rod along east direction (length unit is inch) Comparison 0? NEU Grodiont to tho Colculotod with 1 Rod 6-19-94-1 Diot.-inlEootTootholcu1ot:Toot-Col1 .3125 1.0000 1.0000 .0000 LN(4§L/d) = 6.4206 1 .7055 .8189 -.1134 d/2 (inch) = .3125 2 .6141 .7109 -.0968 L (Foot) = 8.0000 3 .5758 .6478 -.0720 4 .5508 .6030 -.0522 5 .5266 .5682 -.O416 6 .5055 .5398 -.0343 7 .4859 .5158 -.0299 8 .4695 .4950 -.0255 9 .4555 .4767 -.0212 10 .4398 .4602 -.0204 11 .4313 .4454 -.0142 12 .4250 .4319 -.0069 15 .4023 .3971 .0052 18 .3781 .3687 .0094 21 .3578 .3447 .0131 24 .3438 .3239 .0198 30 .3156 .2892 .0265 36 .2984 .2608 .0377 42 .2711 .2368 .0343 48 .2539 .2160 .0380 60 .2273 .1812 .0461 72 .2055 .1528 .0527 84 .1867 .1286 .0579 96 .1695 .1080 .0615 106 .1547 .0897 .0650 120 .1469 .0733 .0736 180 .1078 .0101 .0977 TEST 0 U_:o1 = 1-(LN(X2/X1)-LN(X3/X2)-...)/LN(4§L/d) CHLC 180 Cooporioon of NEV Grodiont to tho Colou1otod SINGLE ROD ELECTRODE For Unit Noroolixd DISTflNCE FROM CENTER (INCH) 940619-1 152 Comparison of NEV Gradient to the Calculated SINCLE ROD ELECTRODE, TO EAST DIRECTION 1 0 I --8— TEST .8 ‘ + CALC > LL] I Z 1. o I N .1 '3 .6 d '. o 11 g “I. 0 ii; 2 . f: .41 C :3 "5 .2 6 F = = C1. : .2 " = = ‘ - a O T T T r T T I T 1 O 20 40 50 80 100 120 I40 160 180 DISTANCE FROM CENTER (INCH) 940619-1 Figure 48. Comparison between theoretical value calculated from equation (5.3) and field measured value of neutral-to-earth voltage gradient distributions from single driven electrode rod along east direction (length unit is inch) 153 ground rod. In Table 11, the first column is the distance (inch) from the center of the rod, the second column is the per unit voltage from the test measurement, third column is the per unit voltage calculated from (5.3) and third column is the difference of the two values (test value - calculated value). From Figure 48 and Table 11, it can be seen that within the first 20 inch (0.51 m) from the ground rod, the test value and the theoretical calculated value of the earth voltage were very close. After this point, the discrepancy increased as the distance from the center of the rod increased. The test results indicate that gradients extend out further distances than determined by the theoretical calculation. For example, at 15 feet (180 inches), the theoretical calculation indicates that the voltage is only 1% of the ground rod voltage while the test data indicates the voltage is 10%. Althouse (1990) conducted similar measurements of the voltage gradient in the immediate area of a single ground rod. That research only shows the gradient out to a distance of 84 inches from the ground rod. For a ground rod with a resistance to earth of 20.6 ohms, the voltage at 84 inches was 18% of the voltage at the ground rod. When the ground rod to earth resistance was 118 ohms, the voltage at 84 inches was only 6% of the voltage at the ground rod. The results from this research (Table 11) with a ground rod resistance to earth of 18.6 ohms at 84 inches was 19% of the voltage at the ground rod. The calculated value from the theoretical formula showed that at 84 inches 154 the voltage was 13% of the voltage at the ground rod. The formula is approximately true, but does not take into consideration the influence of earth resistivity at distance away from the ground rod. In low resistance soils, the voltage gradient extends out from the ground rod a greater distance than for high resistance soils. 5.3.2 Test of NEV Gradient Distribution, Primary Two Ground Rods Table 12 presents the test data of the neutral-to-earth voltage gradient distribution resulting from two earth electrode rods acting as the primary isolated ground at the transformer. Figure 49 shows the corresponding three dimensional graphic plot of the voltage gradient distribution and Figure 50 shows the equi-potential lines of the voltage gradient distribution in this case. For detailed analysis, only the voltage gradient distribution in the smaller inner square ABCD of the test plot (referring to Section 4.3.1 and 4.3.2) is presented. Table 12, Figure 49 and Figure 50 show that the neutral-to-earth voltage created two peaks at the very immediate vicinity of the two ground rods and then diminished rapidly along all directions. The resistance to earth of the two ground rods as measured by three point fall of potential method was 11.4 ohm. More than 55% of the voltage dropped within the distance of 3 feet (0.91 m) from each of two ground rods. In order to detect the altering of the voltage gradient distribution compared to that of the single rod, from the center (20, 20) of the test 155 0v.N Nv .N v.N 0.N 0.N .0.N VN.N N.N .. .N 8N N0.N 0. 00.N .0.N 00.N .0.N 00.N 0v.N 8N 0.N .N.N 5. .N ..N .. 00.N 55 .N 05.N 5.N N0.N 00.N 59.0. 00.N 00.N 0N.N 0. .N N. 0 .0.0 50 .N 00.N 05.N 00 .N .0.N 00.N 00.N 8N 0N.N 0. 0N.0 MN .0 0. .0 8.0 50 .N 50 .N 55.N 00.N 00.N 0v.N N0.N v. 00.0 N0.0 3.0 0N.0 0. .0 50.0 N0.N 05 .N N0.N 00.N 0.N 0. 00 .0 0.0 .5 .0 00.0 00.0 NN.0 8.0 00.N '5 .N N0.N 00.N 0. Nv... 00... 000 N0.0 N0.0 0v.0 .N.0 v0.0 .40.... 05.N 0.N 5. N0... .0.v 09.0 .N.v N0.0 00.0 8.0 v. .0 N0.N 05.N 0.N 0. 00.0 .0.0 00.0 0.0 No.0 '5 .0 00.0 0N.0 8N .0.N 00.N 0. 00.N. .0.0 0. .0 5.0 0. .v 00.0 00.0 .0 .0 00.0 8N 00.N ON 00.0 N0.0 0N.0 '5 .v vN.v N0.0 .0.0 0.0 .. .0 00.N N5.N .N 00.0 00.0 N. .0 .5.v 0N.0 00.0 N0.0 .0.0 N. .0 00.N 05.N NN 5v.0 00.0 50.0 00.0 0N0 00.0 N0.0 00.0 .. .0 8N 05.N 0N v0.0 3.0 8.0 00.? NN.v 50.0 00.0 00.0 6.0 8N .5.N 0N 00.0 05 .0 8.0 N0; 0. .v 00.0 00 .0 0 .0 00.N .0.N 50.N 0N 50.N. 5. .0 .0.0 00.0 8.? 05 .0 Nv.0 0. .0 RN .0.N N0.N 0N 50.0 .0.0 N0.v 006 00.0 00.0 00.0 v. .0 00.N N5.N 00.N 5N .0.v N0... :6 0. .v '5 .0 50.0 N.0 No.0 0.N 00.N 0.N 0N VN.v NN.v '0; 00.0 50 .0 .N.0 8.0 50 .N 5.N 00.N :.N 0N 0.0 55.0 0.0 3.0 0N.0 N. .0 00.N 55 .N .0.N 00.N 00.N 8 ON 0. 0. 5. 0. 0. v. 0. N. .. 0. 350 xzvuv > N10N5000 .080 2600 g $.00 :38 #00... 5.20.9.6 0U. Coo. a. 5.2: 50:00 00:80.0 6080000 .00. 0 5.3 60: 0:090 0.008020 a»; 806.00 80:. 60.5505 60580 008.9 5000-00-70.50: 05 .o 0.00 6060:3008 80... .N. 030.... 156 00.. N0.N 50.N 0. .N NN.N 0N.N 00.N *.N 00.N 00.N 0. 00.N N. .N 0. .N 5N .N N0.N 00.N 00 .N 00.N .0.N N0.N .. .. .N 0. .N .0 .N *.N N0.N 00.N 00.N 5.N 05.N 05.N N. N.N 0N.N 00.N 00 .N 50.N 5.N .0.N 50 .N 50.N 00.0 0. 0N.N 00.N 50 .N 0.N N5.N 00.N 00 .0 50 .0 0. .0 0N.0 0. 00.N 00.N 00.N 5.N 00.N 00.0 0. .0 0.0 00 .0 00.0 0. .0.N 50.N N5.N 0.N 3N 0. .0 0.0 00.0 05.0 00.0 0. 00.N 00.N 05.N 0.N 0. .0 8.0 05.0 00.0 0. .0 0N.0 5. 00 .N 05 .N 00.N N0.N .0 .0 0.0 .0 .0 N. .0 00.0 .0.0 0. 00.N 05.N 00.N NN.0 00.0 00.0 8.0 N0 .0 00.0 0.0 0. 00.N .0.N 00.0 NN.0 00.0 0.0 .N.0 0.0 0. .0 8.0 0N 00.N 00.N 00.0 0N.0 N0.0 0.0 0N.0 00.0 N.0 05.0 .N 00 .N 00.N 0. .0 8.0 00.0 00.0 5N.0 00.0 N. .0 .0 .0 N .5.N 50.N ..0 5N.0 .0.0 50.0 0.0 00.0 00.0 0N.0 0N 00.N 00.N 50.0 .0 .0 00.0 00.0 0. .0 00.0 00.0 0.0 0N 00.N 05.N .0.0 N.0 N0.0 0.0 0. .0 N0.0 8.0 00 .0 0N 00.N 05 .N 00.N 0. .0 00.0 00.0 00.0 00.0 8.0 00.0 0N 00.N 00.N 0.N .. .0 50 .0 00.0 00.0 0. .0 55.0 00.0 5N 00.N 00.N .0.N 0.N 0N.0 0.0 55.0 00.0 00.0 05.0 0N 00 .N .0 .N 00.N 00.N . .0 N.0 0.0 05 .0 50 .0 0. .0 0N .0.N 00.N 0.N 05.N 00 .N 50.0 0N.0 0.0 N0.0 05 .0 8 a 0N 0N 5.N 0N 0N 0N 0N NN .N A»: x. no: > NI0N5000 .088 2g 9.... $.80 .02! #00... 5.98 0! 5.83 ,2 «a... 157 3 l ‘6‘ E 9 ~ 9i i \ CE \. é “ ‘ /4,‘::3i) ET?“ / \‘EEE: é! 7251”‘I:“II ‘ k§§$i§§3 \\ E ‘ \ '555’1ll’ 'I’ '0 Q Q ‘\\\§§§§&:§ 6': I to .0 w 0 ‘fi '242'5:"$:'o'0.'o’o’&:s“§‘i‘a 383% ‘ 0 O .2 I. .‘0 <) NEV GRADIENT. TLJO RODS. TEST B. 6-1—94 Figure 49. Three dimensional graphic plot of the neutral-to-earth voltage gradient distnbution from two electrode ground rods with 6 feet separation distance (length unit is foot) 158 EQUl—POTENTIAL LINES WITH TWO RODS (DETAIL), 6—9— 10 30 30 25*- 20 - 20 to P 1 l 10 Figure 50. Equi-potential lines of the neutral-to-earth voltage gradient distribution from two electrode ground rods with 6 feet separation distance (length unit is foot) 159 plot, along the four radial directions of straight north, straight south, straight west and straight east, the earth voltage measurements were taken up to a 100 foot (30.48 m) distance. Table 13 shows the voltage profile data of the two-rod primary ground system along the north direction and the Figure 51 shows the graphic plot of the voltage profile data comparison (per unit normalized) between one rod and two rods of the primary ground systems along the north direction. Table 14 and Figure 52 show the voltage comparison (per unit normalized) along the other three directions. From Table 12, Table 13, Table 14, Figure 49, Figure 50, Figure 51 and Figure 52, compared with that of one primary ground rod connection, it can seen that the most significant altering of the neutral-to-earth voltage gradient by the primary two-rod ground system occurred within the 30 foot distance along the north direction which is the direction of straight connection line of two rods. The second peak created by the additional primary ground rod not only elevated the neutral-to-earth voltage along the north direction, but also elevated neutral-to—earth voltage along other three directions to some extent. This elevation diminished as the distance increased away from the both rods. At a distance of 100 feet the voltage as measured to the reference ground was approximately the same when there was a two ground rod system as compared to a single ground rod. At closer distance the voltage was higher than for a single ground rod. At six feet from either of the two ground rods in any direction, the voltage was approximately 160 Table 13. Neutral-to—earth voltage test data (per unit normalized) from primary ground systems of two electrode rods along the north direction The lEV Gradient with Two Rods along N directions (Per Wit) 940609-3 Distance! North 1 Distance! North 1 (inch) 0 1.000 76 ~57“ 1 .721 77 5“ 2 .610 7° "'32 3 .578 79 e521 4 .560 80 .5‘3 5 .544 81 .491 6 .535 82 . .493 7 _532 83 .464 a .530 94 “‘75 9 .527 (Feet) 8 .403 10 .509 9 -3“7 11 .501 10 .302 12 .493 13 .1” 15 .486 2° 45° 19 .430 30 .107 21 .472 4° -°79 24 .464 5° -°52 27 .459 6° -°52 30 .453 7° -°42 33 .452 80 -°35 36 .450 90 -°3° 39 .450 10° -°27 42 .452 45 .454 4a .456 51 .461 54 .472 57 .465 60 .500 61 .501 62 .514 63 .517 64 .525 65 .534 66 .549 67 .593 6a .618 69 .643 70 .686 71 .766 72 .990 73 .736 74 .675 75 .625 161 The NEV Grodient OIOng N direction COMPARISON OF TWO RODS 8c 1 ROD, NORTH DIRECTION 1% . > .a 3 L1J Z + 2RD 8 + 1RD .2 .6 « O E H I] o 1..., t' z ._. .4« .. 'E .. 3 v a O- .2 '1 u o . r H 9 fl 0 20 4o 60 80 _ 100 DISTANCE FROM CENTER (FEET) 940714-1 Figure 51. Graphic plot of the neutral-to-earth voltage profile data comparison (per unit normalized) between one rod and two rods of primary ground systems along the north direction (length unit is foot) 162 Table 14. Test measurement data of the neutral-to-earth voltage profile data comparison (per unit normalized) between one rod and two rods of primary ground systems along the other three directions The NEV Gradient Cooparison along different directions 940615-4 Dist.-inlEast 2Rdl$outh2RdIHost 2RdIHorth1RdiEast 1RdlSouth1Rleost lel (inch) 0 1.000 1.” 1.” 1.000 1.!!!) I.” 1.11!) 1 .641 .648 .654 .707 .705 .688 .684 2 .602 .601 .585 .632 .614 .610 .642 3 .564 .557 .562 .594 .576 .583 .591 4 .555 .546 .553 .560 .551 .557 .566 5 .544 .536 .544 .534 .527 .539 .546 6 .533 .523 .531 .517 .505 .519 .513 7 .523 .509 .522 .506 .486 .488 .497 8 .517 .494 .501 .498 .470 .458 .455 9 .508 .491 .491 .494 .455 .453 .437 10 .498 .488 .488 .440 .440 .447 .429 11 .492 .480 .487 .429 .431 .443 .423 12 .488 .477 .483 .422 .425 .432 .418 15 .468 .464 .470 .400 .402 .414 .400 18 .454 .438 .459 .386 .378 .387 .385 21 .425 .424 .439 .373 .358 .367 .362 24 .425 .410 .431 .354 .344 .355 .351 30 .398 .382 .404 .328 .316 .326 .325 36 .376 .360 .384 .309 .298 .302 .303 42 .358 .337 .364 .285 .271 .281 .281 (foot) 4 .341 .321 .348 .268 .254 .264 .265 5 .313 .294 .322 .239 .227 .238 .238 6 .290 .268 .296 .214 .205 .215 .215 7 .268 .246 .273 .192 .187 .193 .192 8 .249 .233 .251 .176 .170 .182 .176 9 .230 .213 .237 .161 .155 .164 .164 10 .219 .202 .221 .150 .147 .154 .152 15 .165 .155 .164 .107 .108 .114 .109 20 .134 .125 .134 .085 .087 .090 .088 30 .095 .089 .094 .063 .061 .064 .060 40 .072 .069 .073 .046 .046 .048 .047 50 .056 .05! .059 .037 .036 .038 .037 60 .046 .045 .049 .031 .028 .031 .032 70 .037 .039 .041 .025 .023 .026 .025 80 .030 .032 .034 .021 .019 .021 .021 90 .024 .026 .030 .017 .016 .018 .018 100 .022 .024 .026 .017 .014 .016 .016 940615-4 The EU Gradient along Different Directions CDHPRRISDN BETHEEN i 6 2 ROD PRIMER? GROUNDS Per Unit Nornaiized DISTRNCE FRDH CENTER (FEET) 940615-4 163 The IE.” Grodient olong Different Directions ‘ ‘ EET‘.‘.’EEI~I I a. 2 ROO PRIMARY OROONOS Per Unit Normalized NEV DISTANCE FROM CENTER (FEET) 940615-4 Figure 52. Graphic plot of the neutral-to-earth voltage profile data comparison (per unit normalized) between one rod and two rods of primary ground systems along the other three directions (length unit is foot) 164 8% of the total voltage higher than for a single ground rod. For the two ground rods, the voltage was 29% of the total as compared to 21% for the single ground rod. At 20 feet, the voltage was 13% of the total for the two ground rods as compared to 9% for the single ground rod. At 30 feet, the voltage was 9% of the total for the two ground rods as compared to 6% for the single ground rod. When comparing these results with those of Althouse (1990), it appears the voltage is higher in the immediate area of the ground rods when the resistance of the grounding electrode is lowered. 5.3.3 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod Without Farm Ground Connection Table 15 presents the test data of the neutral-to—earth voltage gradient distribution resulting from one primary ground rod, and one secondary isolated ground rod without the farm grounding system connected. The circuit is illustrated in Figure 53. Figure 54 shows the corresponding three dimensional graphic plot of the voltage gradient distribution and Figure 55 shows the equi-potential lines of the voltage gradient distribution in this case. From the Figure 54 and Figure 55, it can be seen that the voltage gradient originating from the single primary ground rod created the highest peak at the very immediate vicinity of the primary ground rod and then diminished very rapidly along all directions. Note in this case F 165 .0.. .0.. N0.. 00.. 00.. 00.. 00.. N0.. 00.. 0. 00.. 00.. 0.. 0.. .0.. .0.. .0.. N0.. .0.. 0.0 00.. 00.. 00.. 00.. 00.. N 00.. 8.. 00.. 0 00.N 00.N 8N 00.N 50.N 00.N 8N 8.N 00.N 0.0 N. .N .. .N 0. .N 0. .N N 0. .N 0. .N 0. .N 0. .N 0 0N.N 0N.N 0N.N 0N.N 0N.N 0. .0.N 0N.N 0N.N . 0.5 00.N 00.N 0.N .0.N 00.N 00.N 00.N 00.N 00.N 5 00.N 0. N0.N 50.N .0.N 0. 00.N 00.N 00.N 0.0 00.N 00.N 50.N 05 .N 05 .N 05.N . 05 .N 00.N N0.N 0 .5.N 55.N N0.N 0.N .0.N N0.N 0.N 00.N 55.N 0.0 50.N 00.N 00 .0 50 .0 .. .0 50 .0 50 .0 00.0 00.N 0 RN 0. .0 0. .0 0.0 00.0 .0 .0 0N.0 0N.0 00.0 0.0 .. 0N .0 00 .0 00.0 00.0 00 .0 .0.0 0.0 .N.0 0 0N.0 00.0 00.0 N0.0 00.0 00.0 N5.0 0.0 00.0 0.0 00.0 00.0 50 .0 00.0 0. .0 0. .0 00.0 .0.0 00.0 0 00.0 0.0 .N.0 00.0 0.0 00.0 0. .0 .0.0 00.0 0.N 00.0 00.0 0.0 50.0 N0.0. N0.0 N.0 00.0 N0.0 N 00.0 00.0 0N.0 .0.0 5. .0 00.0 0. .0 .0.0 00.0 0.. 00.0 N5.0 00.0 0N.0 0N.0 0. .0 00.0 0.0 00.0 . 00.0 50.0 00.0 00.0 .0.0 55.0 00.0 00.0 00.0 0. 5.0 0N.0 00.0 0.0 50.0 00.0 .0.0 N0.0 N. .0 0 0 0.0 0 0.N N 0.. . 0. 0 a»: x205. > 0|0N5000 $0.00? 258 g..— E... 000.0150. $00 a $.00 :38 hmmb 0.20.85 3! Coo. a. an: 50:00 5.8288 2320 8:0 30:23 .8536 50883 «on. 8 no. 055..» 28 08205 .0.N—6:88 68 2580 use .095... :80 5033...... 25:30 008:; 5.3-9-3230: 05 .o «:3 208333.: 3.0... .n. 03a... 166 Prlnory Systen Voltage Source I000 —~ / f Prlnoryl 7 ground '7 current No current PrInory FI0' '" Forn Systen secondary Grounding Reststonce Systen Prlnory Secondary Ground Rod Ground Rod It 400 F!" -l. 6 Feet 4. 600 feet 4 Figure 53. The test circuit for the neutral-to-earth voltage gradient distribution resulting from one primary ground rod, and one secondary isolated ground rod without the farm grounding system connected. Figure S4. 167 NEUTRAL—TO—EAE’TH VOL TAGE ( L/J Q" NEV ORAOIENT.6-Io-94 TEST.°PARI~I R OPEN Three dimensional graphic plot of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) without farm ground connection (length unit is foot) 168 V LINES, 6—10—94 TEST, FARM R OPEN T 2.8 / 3.2 /’ V. . l o 1 2 3 4 Z Figure 55. Equi-potential lines of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) without farm ground connection (length unit is foot) 169 from Figure 54, the voltage gradient experienced some slight reduction near the north side mid-point of the test plot. This is due to the influence from the other isolated secondary ground rod (6 feet from the primary rod) even without connection to any primary or farm ground system. The voltage reduction near the secondary ground rod was very slight as can be seen by the data in Table 15. It can be concluded that the voltage gradient produced by the voltage on the primary ground rod is basically undisturbed by the presence of the secondary ground rod not connected to an electrical system. 5.3.4 Test of NEV Gradient Distribution, Primary One Ground Rod, Secondary Isolated One Ground Rod With Farm Ground Connection Table 16 presents the test data of the neutral-to-earth voltage gradient distribution resulting from one primary ground rod, and an isolated secondary ground rod connected to a 5.24 ohm farm ground resistance. The circuit is illustrated in Figure 56. Figure 57 shows the corresponding three dimensional graphic plot of the voltage gradient distribution and Figure 58 shows the equi-potential lines of the voltage gradient distribution in this case. From Figure 57 and Figure 58, it can be seen that the secondary isolated ground rod with the farm ground system attached created a sharp voltage decrease near the immediate vicinity of the secondary isolated ground rod. 170 00.. N0.. .0.. 0.. 0.. .0.. .0.. 00.. 50.. 0. 00.. 00.. 00.. 00.. 00.. 00.. 00.. 0.. 0.. 0.0 00.. N0.. 00.. 00.. 00.. 00.. 0.. 00.. 50.. 0 .0.. 00.. N0.. 00.. 0.. 50.. 00.. N0.. 00.. 0.0 .5.. 00.. .0.. 00.. 00. 00.. 00.. N5.. 05.. 0 N0.. 00.. 55.. 05.. 00.. 55.. .0.. 00.. 50.. 0.5 50.. N 00.. 50.. 00.. 00.. 00.. 00.. N 5 0N.N 0..N 0..N 0..N .N.N 0..N .N.N 0..N 0..N 0.0 0N.N 00.N 00.N 00.N 0.N 00.N 00.N 00.N .0.N 0 00.N 50.N 0.N 50.N 00.N 00.N 00.N 50.N 0.N 0.0 00.N 00.N 05.N .0.N 00.N 05.N 05.N 05.N .5.N 0 05.N 00.N 00.N N..0 00.0 00.0 00.0 0 50.N 0.0 00.N 00.0 00.0 0.0 0.0 0N.0 0N.0 .N.0 0 0 00.0 0N.0 00.0 00.0 5.0 00.0 00.0 00.0 5..0 0.0 N.0 00 .0 00.0 00.0 0 00.0 05.0 00.0 00.0 0 .0.0 00.0 00.0 00.0 55.0 0.0 00.0 05.0 00.0 0.N 50.0 00.0 0..0 .5.0 5N.0. 05.0 No.0 00.0 50.0 N 00.0 00.0 00.0 0.0 05.0 0N.0 00.0 0.0 00.0 0.. 0N.0 00.0 00.0 00.0 0..0 00.0 50.0 50.0 5N.0 . 0N.0 0.0 00.0 0.0 00.0 00.0 00.0 N0.0 0..0 0. .0.0 00.0 0N.0 00.0 00.0 .0.0 5N.0 0..0 50.N 0 0 0.0 0 0.N N 0.. . 0. 0 .308 x_500v > 010N5000 .20.5002200 020000 £000 1h.3 00h¢400. >00020000 a >0¢t.00 .0500 500» 520.0000 :02 98. a. :3 50:0: 3.80586 9590 85.. 3223 Ace—.80.. 508.503 .08 8 co.— 039.0 25 38.0.... bag—80m 6o. 2590 use b.2520 Soc Sanctum? 28680 008.? 5399-333: 2: 00 San Eon—2:32: =0... .0. 03a... Prinary Systen Voltage Source IumI 171 —-. f Prinary 1? ground current Prinary Systen ReSIstance Prinary Ground Rod I‘T 400 feet Figure 56. 1 Current fron i prinary flowing .__ In secondary T grounding systen Farn Grounding Systen Secondary Ground Rod ’l. 6 feet -I- 600 feet ’ The test circuit for the neutral-to-earth voltage gradient distribution resulting from one primary ground rod, and an isolated secondary ground rod connected to a 5.24 ohm farm ground resistance. Figure 57. 172 AEUTR’AL-TO-EARTH VOL 73465 ( V) 1 0) 4%; 5%. WI. ° i C. ‘5’ ’2) . " «3’ 0 Q NEV GRADIENT. 6-18—94 TEST.FARI‘1 R 5 OHM Three dimensional graphic plot of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) with farm ground connection resistance 5.2 ohm (length unit is foot) Figure 58. 173 V LINES, 6—IO—94 TEST, FARM R 5 OHM o I 2 .1 4 I0 I W I 10 9r- +9 A a—\ - Equi-potential lines of the neutral-to-earth voltage gradient distribution from primary one ground rod, secondary isolated one ground rod (6 feet separation distance) with farm ground connection resistance 5.2 ohm (length unit is foot) 174 In order to reveal the altering of the voltage gradient distribution compared to that of the open farm ground connection of the secondary isolated ground, the neutral-to-earth voltage measurements were compared in these two cases along the connection line from the south side center (2, 0) to north side center (2, 10) of the test plot (referring to sections 4.3.3 and 4.3.4). Table 17 shows this comparison (per unit normalized) and Figure 59 is the corresponding plot. From Table 17 and Figure 59, it can be seen that, generally speaking, secondary isolated ground electrode connected with farm ground system decreased the local neutral-to-earth voltage gradient distribution originating from the primary ground connection. The most significant decrease occurred at the point where the secondary isolated ground rod was located. At this point (8 feet), the per unit voltage decreased 72.2%, from 0.194 to 0.054. This decrease is due to the opposite polarity of the voltage drop on the effective secondary ground resistance R1 with respect to the voltage gradient that the secondary ground coupled from the primary ground. This will be discussed in more detail in next sections. 5.3.5 Verification of the Neutral Isolation Circuit Model Table 18 and Table 19 present the test results for the circuit model described in section 2.4 (referring to Figure 2), Chapter 2. The method used to conduct this research is described in Section 4.3.5. Refer to Figure 14 of that section to identify the quantities measured 175 Table 17. Data comparison between neutral-to-earth voltage gradient distributions (per unit normalized) from secondary isolated ground systems with and without farm ground connection along the direction of primary and secondary isolated connection line 00190215014 m Fare_R OPEN 6 Far.) 5 on. 940615-3 Dist.-inlDist.-ft10ponPerU15 WIWItH 0'. Volt” .267 .226 2.75 2.32 0 .0) .343 .331 3.54 3.4 3 .25 .357 .343 3.68 3.53 6 .50 .371 .359 3. 83 3. 69 9 .75 .41!) .385 4.12 3.96 12 1.00 .411 .399 4.24 4.1 13 1.08 .414 .402 4.27 4.13 14 1. 17 .415 .412 4.28 4.24 15 1.25 .429 .417 4.42 4.29 16 1.33 .418 .419 4.31 4.31 17 1.42 .431 .426 4.44 4.38 18 1.50 .468 .460 4.82 4.73 19 1.58 .483 .475 4.98 4.88 20 1.67 .490 .482 5.5 4.96 21 1.75 .498 .4” 5.13 5.04 22 1.83 .525 .519 5.41 5.34 23 1.92 .632 .613 6.52 .3 24 2.00 1.” 1.“ 10.31 10.28 25 2.08 .839 .825 8.65 8.48 26 2. 17 .593 .569 6. 11 5.85 27 2.25 .524 .5123 5.4 5. 19 28 2.33 .500 .481 5.15 4.94 29 2.42 .474 .458 4.89 4.71 30 2.50 .468 .452 4.83 4.65 31 2.58 .466 .451 4.8 4.64 32 2. 67 .459 .446 4.73 4.59 33 2.75 .453 .441 4.67 4.53 34 2.83 .420 .397 4.33 4.“ 35 2.92 .413 .391 4.26 4.02 x 3.00 .405 .36 4. 18 3.96 39 3.25 .388 .39 4 3.79 42 3.50 .376 .356 3.88 3.66 45 3.75 .363 .343 3. 74 3.53 48 4.00 .349 .326 3.6 3.35 51 4.25 .335 .310 3. 45 3.19 54 4.50 .322 .296 3.32 3.04 57 4.75 .312 .284 3.22 2.92 60 5.N .303 .272 3. 12 2.8 63 5.25 .292 .258 3.01 2.65 66 5.50 .281 .247 2.9 2.54 69 5.75 .275 .237 2.84 2.44 6 CD 75 6.25 .259 .220 2.67 2.26 78 6.50 .249 . 197 2.57 2.03 81 6.75 .242 . 1“ 2.5 1.91 176 Table 17. (cont’d) Dist.-inloist.-Ft:Wor-Ul5 Mlmltls 01. Volt.” 84 7.00 .236 .184 2.43 1.89 85 7.08 .232 .181 2.39 1.86 86 7.17 .223 .175 .3 1.8 87 7.25 .226 .161 2.33 1.65 88 7.33 .224 .166 2.31 1.71 89 7.42 .219 .162 2.26 1.67 90 7.50 .220 .157 2.27 1.61 91 7.58 .218 .138 2.25 1.42 92 7.67 .204 .146 .1 1.5 93 7.75 .212 .138 2.19 1.42 94 7.83 .209 .127 2.15 1.31 95 7.92 .203 .106 2.09 1.09 96 8.00 .194 .054 2 .55 97 8.08 .196 .091 2.02 .94 98 8.17 .196 .116 2.02 1.19 99 8.25 .189 .123 1.95 1.26 100 8.33 .195 .131 2.01 1.35 101 8.42 .197 .135 2.03 1.39 102 8.50 .193 .136 1.99 1.4 103 8.58 .195 .133 2.01 1.37 104 8.67 .192 .136 1.98 1.4 105 8.75 .194 .138 2 1.42 106 8.83 .192 .138 1.98 1.42 107 8.92 .191 .136 1.97 1.4 108 9.00 .190 .138 1.96 1.42 111 9.25 .179 .135 1.85 1.39 114 9.50 .182 .138 1.88 1.42 117 9.75 .180 .134 1.86 1.38 120 10.00 .174 .107 1.79 1.1 177 NEV GRADIENT SOUTH-NORTH DIRECTION COMPARISON BETWEEN Form_R OPEN & Form_R 5 Ohms 1 a a d E? —9— OPEN 2 . + 5 OHM U Q) .'_‘_‘ O E '6 1 ' O n z x“ E .4 - {I}; ‘ D E ~?.;.; : ‘ a - = = .1 ‘ D- - = T = : - .2 -+ - 1‘- : = : J I o , r , r o 2 4 6 8 1o DISTANCE FROM SOUTH (FEET) 940615-3 Figure 59- Comparison between neutral-tooearth voltage gradient distributions (per unit normalized) from secondary isolated ground systems with and without farm ground connection along the direction of primary and secondary isolated connection line (length unit is foot) 178 < 386 > 36 > 36 > 2.6 > 8.... < 2&6 > 3.— o 3.... a < 886 > 36 > 36 > and > v66 < E6 > an; .- n6~ h (36 >96 >326 >36 >84». (2&6 >34 Chg o (36 >86 > 86 > :6 >26 (2&6 >$J 2&3 m (886 >36 >96 >36 >62: («36 >56 can v (2.36 >96 >26 >36 >26— (and >36 and— n (:36 >86 >34 >86 >86— <3n6 >nfln on.“ ~ < 86 > 86 > a; > 36 > 26. < n36 > and INA—O — = mm .m am am .5 am .3 .350 MEX .a 0.8—.5 g .a .850 8.53 .5335 >mz >mz 9388 >mz 33.80 E I85 €2.88 .5... 6.388 a. has... has... has... 82.8 E... .8... doaaaom .8“. em a .23 8... 9:55 E2583 2.0 was com 6.520 ban—ta 0:0 953 so... :ozflaaom .3502 .8 Sun— .3 03.5. 179 < 236 > 6N6 > 666 > 606 > ...n < 866 > 36 a 3.6 o. < 9666 > .66 > 3.6 > 066 > 6.6 ( 366 > a a .6. n. < 6686 > 2.6 > 86 > 6N6 > 2.... < 366 > a a ...MN 6. < 366 > 86 > 66.. > an > 6.6 < 366 > N0.N ZNmO n. < n8... > 666 > 86 > 36 > «.6. < :66 > an... a 36 N. < .686 > 36 > 8.. > 86 > 666. < 866 > an a n6. .. < 6.86 > 9.. > 3.. > 666 > 666. < N66 > an a ...Q. 6. < 9:66 > 86 > 36 > an... > a6. < 266 > «Nd 29.0 6 _. ...m .m 8m «m. ..— 8 ...d 32.30 g .n nus—.5 ”.2"... .a .355 8'53 2.3.2... >mz >mz 5388 >mz 3.3.20 >mz 5...... $388 .5... 5388 9 55... has... has... 8.8... .5... =8. 62.2.2.3 .00.... Am a 5.3 new. 6.59.0 E3503 2.0 new 83. 6:220 .025... 03... as“: .3... 3:833 .8502 .o. 5.0 6— 26a... 180 and calculated. The 16 sets of tests described in 4.3.5 were performed. The animal simulation resistors, R M and R M were not connected. Tests 1 through 8 were connected with the one primary ground rod and with primary neutral-to-earth voltage approximately 10 and 5 V, respectively. These data are shown in Table 18. Tests 9 through 16 were connected with the two primary ground rods and with primary neutral-to-earth voltage approximately 10 and 5 V, respectively. These data are shown in Table 19. The resistance of the primary ground rod RS was measured to be 18.6 ohms by the three-point fall of potential method; the resistance of the two primary ground rods was measured to be 11.4 ohms; and resistance of the isolated secondary ground rod was measured to be 22.0 ohms. The quantities measured for this testing were: primary source neutral-to-earth voltage (V); farm ground resistance (ohm); .neutral-to-earth voltage at the transformer primary ground (V); the neutral-to-earth voltage between the primary ground and the isolated secondary ground (V); neutral-to-earth voltage at the transformer isolated secondary ground (V); neutral-to-earth voltage at the farm ground (V); neutral-to-earth current on the primary ground (A); and the neutral-to-earth current on the isolated secondary grounds (A). The circuit model for the primary and secondary electrical system with the neutrals separated is shown in Figure 14 of Section 4.35. If the separation distance is reduced to the point where there is contact between the primary and secondary ground rods for their entire length, then R1 as a separate quantity disappears and the points between which 181 E51 are measured merge to become one point. In this situation, the farm resistance Ri: is simply in parallel with the primary transformer ground rod Rs- When the primary and secondary ground rods are separated by a large distance then the only connection between the ground rods is the earth. The primary circuit and the secondary circuit will act independent of each other simply connected at one point which is true earth. In this situation the secondary is no longer a part of the primary circuit. Between these two extremes the Secondary ground rod is electrically connected to the primary ground rod. This must be true because the secondary ground rod is not far enough away from the primary ground rod to be connected by the full value of the primary ground rod to earth resistance. There is a primary to secondary ground rod resistance which if Figure 14 is valid in Section 4.3.5, is made up of R51 plus R1 which will be less than the primary plus secondary ground rod resistance to earth RS plus R1. Also if this circuit model is correct, the measured data from the field can be used to calculate other measured quantities as well as quantities that cannot be measured. These calculated quantities will be correct for all conditions if the circuit model is correct and not just for special cases. Table 20 provides calculated values of grounding electrode resistances, circuit resistances, and some voltages. Figure 60 is the same as Figure 14 of Section 4.3.5, except it is arranged vertically so that all quantities can be visualized more easily. The resistance to earth of the primary ground rod at the transformer (Rs) and the farm system grounding resistance to earth 182 JAAA Figure 60 The circuit model of Figure 14 of Section 4.3.5 is arranged vertically so that all quantities can be visualized more easily. ..36. I I > ..6. > 8.... :36 on...” a 2...». I o. .3... I I. >2 .2 >2 .. .2... 2.... .2... I n. 2...... I I > n. .2 > N. .n .8... 3... .2... I z I 2.... .8... >2... > 2 .n I I .2... ..n: n. .3... I I >2... >2... .2... .8. .2. I a. .2... I I >8... >2 .2 .2. .2... .2... I .. .8... I I >8... > 2.2 .3... .8. 3... I 2 I .2... 2.... > a... > 8.2. I I .2... .8... . .2... I I > 8.... > 8.. .2... .8. .2... I . .8... I I > 3.. > x... .n... .8. .2... I .. .8... I I > 8.. > 8.. .92.. .1... 3...... I . Mm I .8. .8... >2 .n >8. I I. .8. .8 2 a 1 .8... I I >2 .2 > ...2 3.... 3... .2... I v .3: I I > ...2 >2 .2 .8... 2.... .2... I a .8... I I > 8.2 > ...2 .3... 3... .2... I N I 3.... .8... > n. .2 > n. .2 I I 3... .8... . 2 5. 5. m. ..m + an. .2 2.. 5. a. .2"... .. 83...... 8.3.1... 8.5.1... >mz 3.5.... 13...... al.-1... 3. 1.86 9...... E... has... 8....» bl... ...p .2 0...... .3. .2 .3... a. ...o 82. 825...... .32.... 2520 .5 82.82 .2520 .o 82.5 858.6 .8 .1..— 184 (RF) is important for accurate calculations. These resistances to earth were measured using the three point fall of potential method which is reasonably accurate but is subject to some error. The accuracy of these measurements can be checked by using Ohm’s Law to calculate the resistance when an accurate measurement is made of neutral-to-earth voltage (Es and Br) and grounding electrode current (IT and 11). When the circuit to the farm grounding resistance is open as shown in Figure 61 all of the primary ground current (Ir) will flow through the primary grounding electrode (RS), therefore, the resistance to earth will be Es divided by the current IT. For the cases where there is current flowing to the farm grounding electrodes the farm grounding system resistance to earth will be the farm neutral-to-earth voltage (BF) divided by the farm grounding system current (11)- The method of calculating the various other quantities was performed as follows: 1. With the farm grounding open as shown in Figure 61, take the measurements of Bs (primary neutral-to-earth voltage), B51 (the voltage between separated primary-secondary neutral), E1 (neutral-to—earth voltage of the secondary isolated ground) and Rs (the primary ground rod resistance, RS = R31 + R82), and then use the voltage division law to calculate the resistance R81 and R52 in the circuit model (the results are shown in Table 16c for tests 1, 5, 9 and 13): R51 = Rs x (E51 /1~:S) _ (2.1) 185 - H q *— ‘AAA VVT ” M — ["0 AAAAA (p—f‘ -—-———UI¢—[."—. Figure 61 The circuit model of Figure 14 of Section 4.3.5 without farm ground system connection is arranged vertically so that all quantities can be visualized more easily. 186 R52 = Rs X (El / Es) (2.2) For Test 1, RS = 18.29 ohm, E8 = 10.15 V, E8] = 8.19 V, and E1 = 1.96 V, hence: Rsl = 18.29 x (8.19/10.15) = 14.76 (ohm) R52 = 18.29 x (1.96/10.15) = 3.53 (ohm) For Test 9, R8 = 11.22 ohm, E8 = 10.23 V, E3] = 7.28 V, and E1 = 2.94 V, hence: Rsl = 11.22 x (7.28/10.23) = 7.98 (ohm) R52 = 11.22 x (2.94/10.23) = 3.22 (ohm) According to Kirchhoff’s Voltage Law (KVL), with the farm grounding closed as shown in Figure 60: E8 = ITXRSI +leR1-I-E1 (2.3) and R1 = (Es - E1 - I.r x R51) / II (2.4) Where 1,. and 11 are primary and secondary neutral-to-earth currents, respectively; and R1 is effective secondary isolated ground resistance. Take Test 2 as the example, ES = 10.06 V, E1 = 1.09 V, 187 I, = 0561 A, R51 = 14.76 ohm, and I] = 0.0414 A, from equation (2.4): R1 = (10.06 -109 - 0.561 x 14.76)/0.0414 = 16.66 (ohm) The effective secondary ground rod resistances R1 are shown in Table 20. Other values in Table 20 were calculated from the measured values of Table 18 and Table 19. The source resistance (RD) was determined by dividing the source NEV (ED) by the primary grounding current (11.). The secondary neutral resistance (RN) was determined by dividing the voltage drop on the conductor (E1 - BF) by the secondary grounding current (11). From Figure 60 it can be seen that the primary neutral-to-earth voltage (Es) is equal to the sum of the primary to secondary neutral voltage (E51) and the secondary neutral-to-earth voltage (E1). Keep in mind that these are all measured values from field tests. Note in Table 20 that E51 plus 131 is very close to the measured value of E. It is also important to note that the resistance to earth of the secondary ground rod at the transformer was 22 ohm. The mean value calculated for the effective secondary ground rod resistance (R1) was 18.69 ohm. Assuming that the resistance to earth value of 22 ohm is accurate, the effective resistance of the secondary ground rod in these tests was 85 percent of the ground rod resistance to earth. Althouse (1990) conducted similar tests but with the primary and secondary ground rods spaced only six inches apart and with a primary ground rod 188 resistance of 18.9 ohm and secondary ground rod resistance of 21.4 ohm. These are nearly the same ground rod to earth resistances used in this research. The Althouse (1990) data is shown in Table 21 tests 1 through 12. Values for the effective secondary ground rod resistance (RI) for the Althouse (1990) data are shown in Table 22. The mean value of the effective secondary ground rod resistance was 11.4 ohm. Compared with the resistance to earth of the secondary ground rod of 21.4 ohm, the effective resistance with only a six inch separation is 53 percent. The closer the spacing of the secondary ground rod to the primary ground rod the smaller will be the effective secondary ground rod resistance. 5.3.6. Parameters Influencing Effectiveness of Neutral Separation In order to determine the parameters that influence the effectiveness of separation of primary and secondary neutrals at a distribution transformer, it is necessary to develop an accurate circuit model for the primary and secondary neutral and grounding systems. The circuit model proposed by Althouse (1990) was subjected to field testing and the model was found to be an accurate representation of the data under all field conditions. That circuit model is reproduced here as Figure 62 in a slightly altered form to aid in examination of some of the circuit parameters. The previous analysis of the data collected in this research along with some data collected by Althouse (1990) indicate‘that the values of 189 < ...... ...... > .... ...... > ... < ...... I . .. 2 < ...... ...... > .... ..... > .... < .... I... . ... .. < ...... ..... > ...... I. > ... < .... I . .. 2 < .8... ...... > .... .. > .2 < ...... I . .. .. < .8... ...... > a... ..... > ... < ...... I . .. .. < ...... ...... > 8.. I > 3.. < ...... I . .. .. < ...... ...... > .... -.. > 5. < ...... I . ... .. < ...... ..... > 8.. > .... > .... < ...... I . ... .. < ...... ...... > .... > .... > .... < .... I. . .. .. < .8... I > .... > .... > .... < ...... I . .. 2 < ...... ...... > .... > ... > .... < 8... I . .. . < ...... I > ...... > .... > .... < 8... I . .. . < 8.... -- > .... > .... > ...... < .... I . .... .. < ...... ...... > .... > .... > .... < ...... I . .... . < ...... ...... > .... > 8.. > .3 < ..... I . ... . < 2.8.. ..... > .... > .... > .2. < .... I . .... . < 88.. ...... > 2.. > .... > .3. < ...... . I . .... . < ..8... .- > .... > 8.. > 8.. < .... I . .... . < 88.. ...... > .... > .... > .... < 8... I 29.6 . _. .m .m ...... m. a. am .... 322.0 g .. on...o> g .. 322.0 8.53 ......an >mz >mz e886. >mz ......an >mz In... 88.8.. a... ...-.38.. a 9a.... .53.... .36.... 8.... I... a... 2...... 85...... ...... .. 2. .. 5.2... ... .2 5.2... .... .6222... .8". .... .... ... 5.2... .. 8.3... .2. ... . 5.3 ...... 8.20 ......80. ..o .... com 3.5.0 38....— ueo 9...: 58: 0.3052 .0 30,—. cough...“ .3282 .... ...-D ..N 03:. 190 > 2. .. .... .. I I 2 ... > .... -.. a .... I I I .. -.. > ... ... a .... I I I .. I > .... ..... a 8. ... I I 2 .. > ... ..... .. .... x I I 2 -.. > .... ..... .. a... .. I I .. .... > .... .. ... .. I I .. . .... > ... > ... a F. .. I I .. ...... I ,>.... >8. ...... I I I .. .. .... I > .... > .... a 2... I. I I 2 .. .... .. > ...... > .... a 2.. .. I I o a .... ...- > .... > .... a 2.. I I . .. .... > .... > .2. .. .... ..... I I .. .. .... .... > 2... > 2.... a .2 .. I I o .. .... I > .3. > .... a on. .. I I. . a ..2 > .... > .... . ... I .. .... . .. .2 I > .... > .... .. ... I .. .... . .. ... a 8.. > 8. > .2 a .2. ..... I a 2.. . .. ... . .... > .... > ...... ... I a 2.. . ... .3. 5. .... .... + ...... .... z. 9. .... 5...... .. 8.5.8.. 8.528.. 815...... >mz .3335 .532 2138.. .5. 385 baa... 3...". 588 82.8 in .8... ... 22.9 5 a... 8.2. 3.552 80.. 82.223”. 23.6 .2590 ...... 80..qu 92.2.3.0 .o .o:_a> “.0..—3.6 Na 031,—. 191 Figure 62. Slightly altered form of the neutral separation circuit model (Althouse,1990) 192 resistances (RD, R51, R52, R1, and RN) in the circuit model are nearly constant for a particular location and installation. The data show that the level of voltage and current flow do not result in a significant change in these resistances. The farm grounding resistance in the circuit model of Figure 62 has been separated from the circuit so that it can be studied separately with different values. All voltages in the circuit model are variable as the value of farm grounding resistance (RF) changes. This is evident by examining the voltages in Table 18 and Table 19. However, the open circuit voltage (VOC) and the neutral-to-earth voltage at the primary ground rod (Es) were held as constant as practical. But the voltage across the components of the primary ground rod resistance (Rs) which were R51 and R52 were not necessarily constant. Note from Table 18 and Table 19 that the total current flowing in the primary grounding circuit (11') increased only slightly as the farm grounding resistance (RF) was decreased. Also note from Table 18 and Table 19 that as the farm grounding resistance increased, the secondary grounding current increased. But note that the increase in secondary grounding current (11) was much greater than the primary grounding current (IT). The reason is evident in the circuit of Figure 62. The portion of the primary ground rod resistance R32 is in parallel with the secondary neutral and grounding circuit. As the farm grounding resistance is decreased, 3 larger proportion of the current from the primary takes the farm grounding circuit path rather than completing the circuit to earth through R52. 193 As was seen in the previous section, and as shown in Table 18, Table 19, and Table 20, the field test data can be used to determine the values of all of the resistances of the circuits. If the open circuit voltage (VOC) is known, the primary side and secondary side neutral-to-earth voltages can be determined for any value of farm grounding system resistance to earth using simple circuit solving techniques. The voltage E52 of Figure 62 is the value of the earth gradient voltage as measured to a reference ground at any distance from the primary ground rod. In this research the secondary ground rod was located a distance of six feet from the primary ground rod. The resistance Rs2 will decrease and the resistance R51 will increase in value as the secondary ground rod distance from the primary ground rod is increased. The converse is true as the distance between these two ground rods in decreased. Note that for the Althouse (1990) data for ground rods located only six inches apart that the value of R32 in Table 22 becomes larger. Also note that a greater portion of the primary neutral-to-earth voltage (Es) appears at the secondary (E1). Clearly the distance of separation is one parameter involved in the effectiveness of neutral separation. In this research the ratio of farm neutral-to-earth voltage (BF) to primary ground rod neutral-to-earth voltage (Es) was plotted against the value of farm grounding system resistance to earth (RF). Figure 63 is a plot of the data from Table 18 and Table 19 for two levels of primary grounding resistance. In Figure 63 each point is the average of two tests, one at approximately 10 volts on the primary ground rod and 194 25 .4 U .3. ..‘1 20 — M U m g: 15 2 M 5 z: 22 1:10 - § .. Each nork Is the mrm of no punts g 5 _ 0 Primary proud 10.29 chm g I Prlnnry grand 11.25 m L. o I 0.00 0.05 0310 OTIS 0’50 r,/E, Figure 63. The ratio of farm neutral-to-earth voltage (Er) to primary ground rod neutral-to-earth voltage (E8) was plotted against the value of farm grounding system resistance to earth (RF). The data was from Table 18 and Table 19 for two levels of primary grounding resistance. 195 the other 5 volts. ‘The two values were nearly identical indicating that voltage level does not influence the parameters in this circuit model. Note in Figure 63 that a slightly higher percentage of the primary neutral-to-earth voltage appears at the farm neutral as the primary grounding resistance to earth is decreased. The data for Figure 63 and later figures is shown in Table 23. As was discussed earlier, field data can be used to determine all of the circuit model resistances. If the open circuit voltage is known, then the ratio of farm neutral-to-earth voltage to primary ground rod neutral-to-earth voltage can be determined for any desired value of farm ground system resistance to earth. That data is plotted in Figure 64. Note that as the farm ground system resistance to earth approaches zero the ratio Br to Es approaches zero. Clearly a low farm grounding resistance to earth is extremely important for effective neutral separation. Note that as the farm ground system resistance to earth becomes large, the ratio BF to Es approaches a maximum value. Actually the voltages BF and E1 approach the voltage of the earth gradient E32. Note in the circuit model of Figure 62 that the effective secondary ground rod resistance (R1) and the secondary neutral resistance (RN) are in series with the farm ground system resistance to earth. As the farm ground system resistance to earth is decreased and the current in the secondary ground circuit increases the voltage drop across R1 and RN increase thus leaving a smaller portion of the earth gradient voltage (E52) to appear at the farm building neutral (BF). 196 a...” 26 3.3 a 0.2 .3 o a land? a R .3 3.: a 2: .... o a. 88.3. a 8. 8.8 3.; a a: .3 o o 1.2.2 a SN 85 3.: a a... .... o n .832 :3 was a a on... f. 2.2 a and. 83 a a an... .5 2.: .J 2mm :3 a a on... .3 2.2 .J 298 :3 a 2 one: ... o as 3 3.. 33 a «N .5... .5 ... 3 3.2 .38 a 2 «a... do 2 ... 3.8 so... a a 3N... ... a a." 3 220 83 a 2 32: do a. 3 5. new a £3.20 3. 385 3. 356 i E... has}, al.... 13. 336 ....F .5233 3.5882? 3.83% 05 .a 8.8:; 5.3.9-3332 com 9520 bag...— o. .0352“ we 0.35— 93 $3381 3262mm 9.6.590 $5225 tom 939.0 Figure 64. 197 75" ’ 1 a '4 g '1 '6; .4 E a: 50« o t . U .- 9‘ )‘,_ " V, 3 + is 3" 1 as; 251 p O _‘ g 20+ ..t h- 15-1 .5. toq -' U 54 .... o 0' 0.00 0105 0‘40 oils oTzo r,/E, The ratio of farm neutral-to-earth voltage (BF) to primary ground rod neutral-to-earth voltage (Es) was plotted against the value of farm grounding system resistance to earth (RF). The data was calculated from the circuit model in Figure 62. 198 The measured data for the single primary ground rod (Tests 1 through 8) are plotted in Figure 65 as the ratio 13F to Es and farm grounding system resistance. The circuit model is used to calculate the ratio corresponding to other values of farm grounding resistance. Note that the calculated values fit the measured data. Data was plotted from the data of Althouse (1990) for a primary and secondary ground rod of nearly identical resistances to earth, but the separation distance between the ground rods was six inches. The same type of curve is produced by the data but because of the close spacing of the ground rods in low resistance earth, the ratio BF to Es slightly exceeds 0.5. But also note that as the farm grounding system resistance to earth is decreased, the ratio decreases rapidly approaching zero as the resistance RF becomes small. From the data of this research and the data of Althouse (1990) and the verification of the circuit model, it is evident that there are several parameters which are important in determining the effectiveness of neutral separation. These factors are: 1. The resistance to earth of the farm grounding system as seen from the transformer pole. 2. The spacing between the primary and secondary ground rods at the transformer pole. FARR BRDUNDING SYSIEH RESISTANCE Figure 65. 199 Calculated value I) ------ Insured value o———A : § 5' g 3 a t; 5 _.' .- 5 .. f2 5 i i :- : . 3 3 5 g °' : .3 .a' .n' 0105 0.10 0115 0120 0T2: 0330 alas 0.100 0145 030 50": The ratio of farm neutral-to-earth voltage (BF) to primary ground rod neutral-to-earth voltage (Es) was plotted against the value of farm grounding system resistance to earth (RF) for 6 inch and 6 foot separation distance. The calculated data was from the circuit model in Figure 62. 200 3. The resistance to earth of the primary grounding electrode when the secondary grounding electrode resistance to earth is maintained at a constant value. 4. The resistivity of the earth in the area of the primary and secondary ground rods as it determines their resistance to earth. It could not be determined from the data collected what influence the resistance to earth of the secondary ground rod would have when the primary ground rod resistance was held constant. Clearly, the most important of the parameters is the resistance to earth of the farm grounding system. VI. CONCLUSIONS The computer simulation models were developed and used to study the neutral-to-earth voltage profile along both single-phase and three-phase radial distribution line systems with different normal and abnormal operating conditions. The farm field tests were conducted to reveal the neutral-to-earth voltage gradient distribution near the ground electrode systems on the primary and secondary sides of the neutral isolated distribution transformer. An equivalent circuit of the isolated primary and secondary ground systems was proposed to study the parameters that influence the effectiveness of neutral separation. The conclusions "drawn from this study are: 1. The single-phase DC circuit model developed in this research is sufficiently valid to predict the changing trends of the neutral-to-earth voltage profile along a single-phase primary distribution line. The single-phase AC distribution line model developed with line inductance and an equivalent transformer Circuit replacing the load resistor in the DC model produced a neutral-to-earth voltage profile which was slightly higher in magnitude and similar in shape to the DC profile. 201 202 The overall neutral-to-earth voltages were substantially lower along the electric power distribution system of the three-phase four-wire Yo/Yo connection than that of the single-phase. The effect of high load demand on neutral-to-earth voltage is equivalent to having a phase line to neutral fault occurred near the high demand location and will result in a local increase in the neutral-to-earth voltage. Neutral-to-earth voltage change caused by a high resistance segment in the neutral conductor (bad neutral connection) of a primary distribution line will be greatest in the local area of the high resistance segment and will decrease in magnitude as the distance increases away from the high resistance segment. The bad neutral connection can be detected by the measurement of the local primary ground system impedance which presents the significantly higher value than the normal value. A high substation resistance-to-earth for a single-phase radial distribution line will result in an increase in_ neutral-to-earth voltage along the line near the substation when load current is carried on the primary neutral. At any grounding electrode location of the distribution line, the system ground Thevenin equivalent open circuit voltage was 203 divided in series by the ground resistance and the Thevenin equivalent resistance (system ground resistance) at this location. Generally speaking, a lowered ground resistance at a particular location along the line results in a lowered local neutral-to-earth voltage. The actual level of neutral-to-earth voltage is determined by the open voltage and the proportional relation between the local ground resistance value and the system Thevenin equivalent resistance value at this location. Increasing the number of grounding electrodes can decrease the neutral-to-earth voltage to some extent. A large number of ground rods could be costly and the result may not be as good as expected. Increasing the primary distribution line operating voltage resulted in a decrease in primary line current and thus the neutral-to-earth voltage along the line. The reduction of neutral-to-earth voltage was less significant when the voltage increased above 7 .2 kV than when the voltage was increase from a lower value up to 7 .2 kV. A secondary ground fault may cause a significant increase or decrease in the neutral-to-earth voltage along the distribution line in the local area of the ground fault depending upon whether the secondary ground fault current is in-phase or out-of-phase with 10. 11. 12. 13. 204 the primary current. The change in neutral-to-earth voltage is location dependent along the distribution line. When a primary phase-to-earth fault occurs anywhere along the single-phase distribution line, the neutral-to-earth voltages will increase in line segments near the substation and decrease for line segments from the middle to the end of the line with the most significant changes near the substation. When a primary phase-to-earth fault occurs anywhere along the distribution line system of a three-phase four-wire Yo/Yo circuit, the neutral-to-earth voltages will increase in all line segments of the system with the most significant increases near the substation. For the earth voltage gradient resulting from a single primary ground rod electrode, the test value and the theoretical value calculated from the equation (5.3) were very close within the first 20 inch (051 m) from the ground rod. After this point, the discrepancy increased as the distance from the center of the rod increased. The earth voltage gradient resulting from a single primary ground rod electrode will be altered with one more additional primary ground rod 6 feet (1.83 m) away. The two voltage peaks near each rod will be present. The second peak created by the additional 14. 15. 205 primary ground rod not only elevated the neutral-toearth voltage significantly along the direction of the straight connection line of two rods, but also elevated neutral-to-earth voltage along all other directions to some extent. This elevation diminished as the distance increased away from the both rods. The secondary isolated ground electrode connected with the farm ground system will decrease the local neutral-to-earth voltage gradient distribution originating from the primary ground. The most significant decrease occurred at the point where the secondary isolated ground rod was located. This decrease is due to the opposite polarity of the voltage drop on effective secondary ground resistance R1 with respect to the voltage gradient that secondary ground coupled from the primary ground. Effectiveness of separation of primary and secondary neutrals is a function of resistance to earth of the primary grounding electrode, separation distance between the primary and secondary grounding electrodes, and the resistance to earth of the farm grounding system. The most important parameter is the resistance to earth of the farm grounding system. A low farm grounding system resistance to earth insures effective neutral separation. APPENDIX 206 AC CASE, RD9 CHANCE IMPACT ON NEV, 4.8KV R09 0.086, 1, 5, 20 AND lOOK OHM, LOAD .3 A 15 —+— 0.086 OHM —B-— 1.00 OHM +5.000HM +20.00HM + 100K OHM 1.0:" A > v LJJ (D <( *— _J O > 5-1 0 trtITrtTHHIIHIIrrrTWIItIrtrthttrrrtflntrtrttlnn '- LO Q in 0 Ln 0 In 0 n O IDIN '- v- N N f’) n ‘3' V’ In LOU) NODE # (1—57) 940528c Figure A1. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 5 7th node with variable neutral conductor resistance RD9 between node 9 and node 10 and a normal customer load of 3A at node 9 (single-phase AC model simulation) 207 AC CASE, P1333 CHANCE IMPACT ON NEV, 4810/ VOLTAGE (v) RD33 0.086, 1, 5, 20 AND 1OOK OHM, LOAD :5 A _B_ + _q_ O 111111111llllTTfiT—TTITITTITIIIIITIITIIITTTITITIIIIIIIIT v- LO 0 LO Q in O Ln 0 LO Q lDl\ '— v— N N I") 1”) V V L0 1.011) Figure A2. NODE # (1—57) 9405260 0.086 OHM 1.00 OHM 5.00 OHM 20.0 OHM 100K OHM Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable neutral conductor resistance RD33 between node 33 and node 34 and a normal customer load of 3A at node 33 (single-phase AC model simulation) 208 PDSB CHANGE IMPACT ON NEV, 4.8K 1-PHASE AC 10 AC MODEL, RD56 0.086, 1, 5, 20 AND 100K OHM, LOAD 3 A 0.086 OHM —a— 1.00 OHM —x— 5.00 OHM 8 ‘ 4— 20.0 OHM —-¢—— 100K OHM A a 6 ~ to ..... o < [.— ..l O 4 ‘ > 2-1 0 TIIITTWTITTIIITIIlIITIIITIIIIITIIIIIIIIITIITIFTTIIIIII -- in 0 tn 0 In 0 l!) O In 0 In I\ v- — N N F) F) V’ V' In In In NODE # (1 -57) 940530 Figure A3. Prole of the neutral-to-earth voltage along the primary distn'bution line from substation to 57th node with variable neutral conductor resistance RD56 between node 56 and node 57 and a normal customer load of 3A at node 57 (single-phase AC model simulation) 209 HEAVY LOAD IMPACT ON NEV, 4.8K 1—PHASE [LINE AC MODEL, LOAD 3, 6, 9, 12 8c 15 A AT 404-9 15 —+- 3 A —B-—6A +9A +12A +15A O VOLTAGE (v) U1 1 O TIITIITIIIIIITITIIITITIIIIIIITTIIITjIIITTIIIIITITIIIlrl v— I!) O In 0 ID 0 I05 NODE # (1 —57) 940529f Figure A4. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 404-9 (single-phase AC model simulation) 210 HEAVY LOAD IMPACT ON NEV, 4.8K 1—PHASE LINE AC MODEL, LOAD 3, 6, 9, 12 8c 15 A AT 416—33 15 —-t—3A +611 I ——-—9A 12A 15A VOLTAGE (v) o IlllllllllllllllIlflrrlllllllllllllllllllIIllllllllIlTT '- 10 0 l0 0 In 0 In C) In C ION '- — N N I") I") ‘1' V ID no NODE # (1 -57) 940529e Figure A5. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with variable load demand conditions at node 416-33 (single-phase AC model simulation) 211 HEAVY LOAD IMPACT ON NEV, 4.8K 1—PHASE LINE AC MODEL, LOAD 3, 6. 9, 12 80 15 A AT 428-57 15 + 3 A —B— 6 A i + 9 A 1 1 ix + 12A d” r + 15A 101 .. A d > n V . K DJ 00 . 3 ‘1 +_ n "=:2| _1 .. '5‘- O {‘1‘ ‘43" '==::::‘ > ‘. .:,:Yéygg::=‘ 5" 0“ -'.+.L t‘x‘ V‘§b 3' , \‘.\¢ lazfl' §é¥§¥w «'1' f O IIIIIIIIIIIIIIIITTTIIIITTIIIIIIIIIIFIIIIIIIITTIUIITrI—rf '- 1n 0 in O 10 O In 0 In C) 10 l\ '- "' N N f') l’) V“ V l0 In In NODE # (1—57) 940529d Figure A6. Profile of the neutral-to-earth voltage along the ‘primary distribution line from substation to 57th node with variable load demand conditions at node 428-57 (single-phase AC model simulation) 212 RG1 CHANGE IMPACT ON NEV, 4.8KV LINE AC CS SUBSTATION R01 0.5, 1, 5, 1O, 20 a: 40 OHM, AC CASE 30 —+-—O.50HM I —B—1.00HM \\ +5.00HM ‘1‘ +100HM ‘-,' +200HM Azod \‘3 +4OOHM > ‘\ 5 V <151: ', t: .. ‘i O u \. > A 10: “ \ u ‘ fl ‘. v 1‘ 5« ~ 0 IIIflIIIIIIIIIIIIIIIllIITTIIIIIIIIIIIITTIIIIITIIIITTII '- In 0 In 0 1n O 10 O n O 0.05 e— v- N N f’) f’) V V 10 Inln NODE # (1 -57) 9405311: Figure A7. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable substation resistance RS (single-phase AC model simulation) 213 ROSS CHANGE IMPACT ON NEV, 4.8KV LINE AC CS GROUND R633 1.5, 1.2, 0.9, 0.6 8: 0.3 OHM, AC CASE 10 ¢ _.8._ + a4 ...-... + /'\ a 6~ LIJ O < ’— _J Q In > 2.. O IllI]III111ITITIITTIIIIIITITIII]lllTTlllIlllTIlTlTlllrl .— In 0 1n 0 In C 10 O n O ION v- v— N N f") f’) V’ V Ln mm NODE # (1 -57) 940530—2 1.5 OHM 1.2 OHM 0.9 OHM 0.6 OHM 0.3 OHM Figure A8. Pro-e of the neutral-to-carth voltage along the primary distribution line from substation to 57th node with base case vs. ground resistance RFGBB change at node 33 (single-phase AC model simulation) 214 INCREASE GROUND ROD NUMBER IMPACT ON NEV ALI. GROUND RESISTANCES 100K CHANGED TO 25 OHMS 10 -'+'“' BASE C —B— AD__RD n 8'I u A > 6.. u LLJ O u < P— --'= —l 3: ,.,:::: ---- Linc-.1 O 4‘ 5::5“ > '5'. U 5’4" 7.“ '4 2" 46' o"‘ 4'1 O llllrlrlTITIlUTIllelllIlITTIIrTIlljllllTlTIjlIII][III '- tn 0 In D n O in O 10 O IDIN — — N N n n v 1- 10 1am NODE # (1 —57) 940530-5 Figure A9. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. ground rod number increasing along the entire system (single-phase AC model simulation) 215 SEASONAL GROUND R CHANGE IMPACT ON NEV ALL GROUND RESISTANCES INCREASE TO 2, 3 8c 4 TIMES 25’ * BASE -—B— 200% +3007. 20 +4007; A 2,15. LIJ (D < '3 0‘01 ----- I > --==========“'"‘ ’_,"‘=‘ 5" 35" ,’)- 0 IIIIIIITIIrIrIITWTFrITIITrTrIrllrrllIIIIIIITIIIIIIIT P In 0 In C In C In C In 0 Inl\ '- v- N N n I") V V In InIn NDDE # (1-57) 940530-4 Figure A10. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. seasonal variations of ground rod resistances all along the entire system (single-phase AC model simulation) 216 AC MODEL, OUT—OF—PHASE SECONDARY TO EARTH IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 416 10 + BASE -B—3A +6A 34 +9A + 12A A Z. 5« LrJ 2 ... .J O 41 > 2.1 O TTTYITTTTITIIIIIIIIIFTTITIITIIIIIIIIIIIIIIIIITIIIIIII F In 0 In 0 In 0 In C In 0 101x '- v- N N n n V V In Inln NDDE # (1—57) 940603-4 Figure All. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 33 (out-of-phase, single-phase AC model simulation) 217 AC MODEL, IN-PHASE SECONDARY TO EARTH FAUL IMPACT ON NEv, FAULT 3, 5, 9 8c 12 AT 416 10 + BASE - —-a—3A 8‘ +911. +12A A a 6« LJJ O < l.— ‘J \ O 4* > . \ 1\ \. 2‘ A \‘iz “4‘ ‘1 O TTIIITIIHIIIIlIIIIWT—rllITIITIITTIIIIIIIITTIIIITIIIII — In 0 In 0 In 0 In 0 In 0 on .- — N N n n v ¢ In InIn NDDE # (1-57) 940603-3 Figure A12. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 33 (in-phase, single-phase AC model simulation) 218 AC MODEL, OUT-OF-PHASE SECONDARY TO EARTI— IMPACT DN NEV, FAULT 3, 6, 9 8c 12 AT 404 10 I II I\ I A > v Lu 0 ..... < ... ..l O —*—-BASE > +3A +6A +9A +12A O TITITFFTIIIFTIWI—FTIIIIIIllllIIIIIIITIIIITIIIIIIIIIIITIT — In o In 0 n o In 0 In 0 Inl'\ .— v- N N n n 1' v n Inln NDDE # (1 -57) 940603-2 Figure A13. Profile of the neutral-to-earth voltage along the primary distrrbution line from substation to 5 7th node with base case vs. variable secondary ground fault attached to node 9 (out-of-phase, single-phase AC model ~ simulation) 219 AC MODEL, IN—PHASE SECONDARY TO EARTH FAUL IMPACT ON NEv, FAULT 3, 6, 9 8c 12 AT 404 15 —+—BASE —B—3A —*—-SA +9A 1 1 +12A } 10: A y > v LAJ O < I'— _I O > 5-I 0 TIVTIIIIIWITIITIIIIIIWIIIFITIITTIITIITIFTITIIIIIIIIIT .- In 0 In 0 In 0 In o In 0 Inrx .- .— N N n n v:- «r In Inn NODE # (1 —57) 940603-1 Figure A14. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 9 (in-phase, single-phase AC model - simulation) 220 AC MODEL, OUT-OF—PHASE SECONDARY TO EARTH IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 428 15 P BASE .8— 3A +6A 1t # +9A # # 7+12A 10" f . l \ I '0 > v v I LLJ O < .:3 +— " ’55:.u S “(33!“ -:=::=T > oi:,«.:Y:-Yé:;:==: 5‘ T'}:j’on"")* 0 IITITTTTITTTTIFIIIIITIIITTITITIIITTIIIrTTIIITTIIITTFIiI '— In C In C n O In!" ‘D 9 9 8 m n n <- «- In InIn NDDE # (1—57) 940603—6 Figure A15. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 57 (out-of-phase, single-phase AC model simulation) 221 AC MODEL, IN—PHASE SECONDARY TO EARTH FAULT IMPACT ON NEV, FAULT 3, 6, 9 8c 12 AT 428 10 —‘I—' BASE +3A 8T +9A +12A 9 V 6" LIJ O 1‘5 .. -’ .. :{e-Tz'g'fé ‘ ---------- O 4 ‘ ,_.,-.'é;_:g=:;;'.'€n’."- - > 7. ,., 21 O TlllllllrlllllrlllllTlllIITIlIrTITIIITTIIIIIWIIIIIII NDDE # (1 -57) 940503-5 Figure A16. Profile of the neutral-tocearth voltage along the' primary distribution line from substation to 57th node with base case vs. variable secondary ground fault attached to node 57 (in-phase, single-phase AC model simulation) 222 PRIIxIARY—GROUND EAULT IMPACT ON NEV, 4.8KV AC MODEL, FAULT 3, 6, 9 8c 12 A AT 416-O NDDE # (1-57) 94053Dc —-+——BASE -—8—-:SA +6A +12A 10 A > V LLJ O E n _J . O u‘ > \. 5“ “. A 11‘ 3‘33. ., \Q‘L ak‘g La}; ‘12“ it" -. 4'4. 8“." '4; 52'“ O lTTlTlllrllTFlllTllTTTllllllllllllllllTII—ITIIITIIIIII '— In C) In C In 0 In C In 0 Inl\ '— v— N N n I”) V V In InIn Figure A17. Profile of the neutral-to-earth voltage along the “primary distribution line from substation to 57th node with an ungrounded phase conductor to earth fault at node 416 compared with the normal line (single-phase AC model simulation) 223 PRIMARY—GROUND EAULT IMPACT ON NEV, 4.811in 5 AC MODEL, FAULT 12 A AT 404—O, 416-O 8c 428-O 1 , +BASE —a—404 +416 +428 10" A .4 > v LLJ O <( l.— __J O > 5.1 dLV‘T-l. O r1111lI[IIITTIIIITIIrI[ITIITTITTTrlrrIIIIII]llllllerT '— In 0 In 0 In C In C In O on -— -— or N n n v- v- In 1010 NDDE # (1-57) 94053od Figure A18. Profile of the neutral-to-earth voltage along the primary distribution line from substation to 57th node with 12 A phase conductor to earth fault at node 404, 416, or 428 compared with normal line (single-phase AC model simulation) REFERENCES REFERENCES Althouse, J .R. and T.C. Surbrook, 1990. Voltage Gradient Modifications near Equipotential Planes. IEEE Paper No. 90CH2823-3-A3, Institute of Electrical and Electronic Engineers. Althouse, J .R., 1990. Affecting Neutral-to-Earth Voltage Levels through Modifications of the Farm Electrical Grounding System. Master’s Thesis, Unpublished, Michigan State University. Aneshansley, D.J., R.C. Gorewit, L. R. Price and C. S. Czarniecki, 1990. Milk Production with Voltage Exposure during Entire Lactation. American Society of Agricultural Engineers, Paper No. 90-3502, 2950 Niles Rd., St. Joseph, MI 49085-9659. Aneshansley and C. S. Czarniecki, 1990. Complex Electrical Impedance of Cows: Measurement and Significance. American Society of Agricultural Engineers, Paper No. 90-3509, 2950 Niles Rd., St. Joseph, MI 49085-9659. Aneshansley, D.J., R.C. Gorewit, D.C. Ludingdon and Z. Xin, 1987. Effects of Neutral-to-Earth Voltage on Behavior, Production and Water Intake in Dairy Cattle. American Society of Agricultural Engineers, Paper No. 87-3034, 2950 Niles Rd., St. Joseph, MI 49085-9659. Appleman, RD. and RJ. Gustafson. Source of Stray Voltage and Effect on Cow Health and Performance. Journal of Dairy Science, Vol. 68, No. 6, 1985. Biddle, J. G. Co. Megger Earth Testers (Null Balance). The Instruction Manual. Bodman, G. R., L. E. Stetson, H. Shull and H. Benes, 1981. Extraneous Voltages Incidence in Nebraska Milking Centers. American Society of Agricultural Engineers, Paper No. MCR-81-502, 2950 Niles Rd., St. Joseph, MI 49085-9659. 224 10. 11. 12. 13. 14. 15. 16. 17. 225 Cloud, H. A., R. D. Appleman, and R. J. Gustafson, 1987. Stray Voltage Problems with Dairy Cows. AG-BU-1359. Minnesota Extension Service, University of Minnesota. Currence, H.D., B.J. Steevens, D.F. Winter, WK. Dick and GP. Krause, 1987. Dairy Cow and Human sensitivity to 60 Hertz Currents. American Society of Agricultural Engineers, Paper No. 87-3036, 2950 Niles Rd., St. Joseph, MI 49085-9659. Dick, W. K. and D. F. Winter, 1987. Computation, Measurement and Mitigation of N eutral-to-Earth Potentials on Electrical Distribution Systems. IEEE Paper No. 0885-8977/87, Institute of Electrical and Electronic Engineers. Drenkard, D.V., R.C. Gorewit, N .R. Scott, and R. Sagi, 1985. Milk Production, Health, Behavior, and Endocrine Responses of Cows Exposed to Electrical Current during Milking. Journal of Dairy Science, Vol. 68, No.10, pp 2694-2702, 1985. Gorewit, R. C., D. J. Aneshansley, L. R. Price and C. S. Czarniecki, 1990. Holsteins’ Reproductive Performance during Long-Term Voltage Exposure. American Society of Agricultural Engineers, Paper No. 90-3503, 2950 Niles Rd., St. Joseph, MI 49085-9659. Gorewit, R. C., D. v. Drenkard and N. R. Scott, 1984. Physiological EffeCts of Electrical Current on Dairy Cows. National Stray Voltage Symposium, Oct. 10-12, 1984, Syracuse, NY. ASAE Pub. 3-85. American Society of Agricultural Engineers, 2950 Niles Rd., St. Joseph, MI 49085-9659. Gustafson, RJ., Z. Sun and TD. Brennan, 1988. Dairy Cow sensitivity to Short Duration Electrical Current. American Society of Agricultural Engineers, Paper No. 88-3522, 2950 Niles Rd., St. Joseph, MI 49085-9659. Gustafson, RJ., T.M. Brennan and RD. Appleman, 1985. Behavioral Studies of Dairy Cows Sensitivity to AC and DC Electric Currents. Transaction of the ASAE, Vol. 28, No. 5, pp. 1680-1685, 1985. American Society of Agricultural Engineers, 2950 Niles Rd., St. Joseph, MI 49085-9659. Gustafson, RJ, 1985. Understanding and Dealing with Stray Voltage in Livestock Facilities. IEEE Paper Catalog No. 85CH2126-1-CZ, Institute of Electrical and Electronic Engineers. 18. 19. 20. 21. 22. 23. 24. 26. 27. 226 Gustafson, R.J., H.A. Cloud, 1982. Circuit Analysis of Stray Voltage Sources and Solutions. Transaction of the ASAE, Vol. 25, No. 5, pp. 1418-1424, 1982. American Society of Agricultural Engineers, 2950 Niles Rd., St. Joseph, MI 49085-9659. The Institute of Electrical and Electronic Engineers, 1991. IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems -IEEE Std 142-1991. IEEE, 345 East 47th Street, New York, NY 10017 USA. The Institute of Electrical and Electronic Engineers, 1986. IEEE Guide for Safety in AC Substation Grounding. IEEE, 345 East 47th Street, New York, NY 10017 USA. The Institute of Electrical and Electronic Engineers, 1983. IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System- IEEE Std 81- 1983. IEEE, 345 East 47th Street, New York, NY 10017 USA. Kehrle, AM, 1984. Neutral-to-Earth Voltage Analysis of A Single-Phase Primary Electrical Distrrbution System. Master’s Thesis, Unpublished, Michigan State University. Kraus, J. D., 1953. Electromagrretics. McGRAW-HILL BOOK COMPANY, INC. New York. The Institute of Electrical and Electronic Engineers, 1990. National Electrical Safety Code. IEEE, 345 East 47th Street, New York, NY 10017 USA. Norell, R.J., RJ. Gustafson and RD. Appleman, 1982. Behavioral Studies of Dairy Cattle'Sensitivity to Electric Currents. American Society of Agricultural Engineers, Paper No. 82-3530, 2950 Niles Rd., St. Joseph, MI 49085-9659 Pearce, J .A., J .D. Bourland, W. Neilsen, LA. Geddes, and M. Voelz, 1982. Myocardial stimulation with ultrashort duration current pulses. PACE, Volume 5, pp 52-58. Phillips, D.S.M, 1969. Production Losses from Milking Plant Voltage. New Zealand Journal of Agriculture Vol. 119, No. 2, pp.45-47. 29. 30. 31. 32. 33. 34. 35. 36. 227 Phillips, D.S.M. and R.D.J. Parkinson, 1963. The Effects of Small Voltages on Milking Plants; Their Detection and Elimination. Dairy Farming Annual, pp. 79-90, New Zealand. Prothero, J.N., B.W. Lukecart and CM. DeNardo, 1988. Primary N eutral-to-Earth Voltage Levels as Impacted by Various Wiring System Treatments. American Society of Agricultural Engineers, Paper No. 88-3528, 2950 Niles Rd., St. Joseph, MI 49085-9659. Reinemann, D. J ., L. E. Stetson and N. K. Laughlin, 1994. Response of Dairy Cattle to Transient Voltages and Magnetic Fields. EBB Rural Electric Power Conference Paper No. 94-C5. Sodcrholm, LH., 1982. Stray-Voltage Problems in Dairy Milking Parlors. Transaction of the ASAE, Vol. 25, pp. 1763-1767, 1774, 1982. American Society of Agricultural Engineers, 2950 Niles Rd., St. Joseph, MI 49085-9659. Stetson, LE, G.R. Bodman and H. Shull, 1984. An Analog Model of Neutral-to-earth Voltages in a Single-Phase Distribution System. Transaction of the Industry Applications Society of the Institute of Electrical and Electronic Engineers, Volume IA-20, Number 2, Pages 418-424, EBB, New York, NY. Stetson, LE, G.R. Bodman and H. Shull, 1982. Digital Voltrneter for Checking Connections in Neutral Conductors. American Society of Agricultural Engineers, Paper No. 82-3506, 2950 Niles Rd., St. Joseph, MI 49085-9659. Surbrook, T.C., N.D. Reese and CM. Li, 1989. Trouble-shooting Neutral-to-Earth Voltage. Conference Record of the 1989 EBB Industry Applications Society Annual Meeting, Paper No. 89CH2792-0. Surbrook, T.C., N .D. Reese and J .R. Althouse, 1988. Parameters Affecting Neutral-to-Earth Voltage along Primary Distribution Circuits. Transaction of the Industry Applications Society of the Institute of Electrical and Electronic Engineers, Volume 24, Number 5, pp. 798-804, EBB, New York, NY. Surbrook, T.C., J .R. Althouse and ND. Reese, 1988. Stray Voltage Diagnostic Procedure. American Society of Agricultural Engineers, Paper No. 88-3520, 2950 Niles Rd., St. Joseph, MI 49085-9659. 37. 38. 39. 41. 42. 43. 228 Surbrook, T.C., N.D. Reese and J .R. Althouse, 1987. Training Power Supplier Personnel to Find NEV. Sources. American Society of Agricultural Engineers, Paper No. 87-3549, 2950 Niles Rd., St. Joseph, MI 49085-9659. Surbrook, T.C., N.D. Reese and A.M. Kehrle, 1986. Stray Voltage: Sources and Solutions. Transaction of the Industry Applications Society of the Institute of Electrical and Electronic Engineers, Volume IA-22, Number 2, Pages 210-215, EEE, New York, NY. Surbrook, T.C. and ND. Reese, 1981. Stray Voltage on Farms. American Society of Agricultural Engineers, Paper No. 81-3612, 2950 Niles Rd., St. Joseph, MI 49085-9659. Tagg, C. F., 1964. Earth Resistances. George N ewnes Limited, London. U. S. Department of Agriculture - Agricultural Research Service, 1991. Efiects of Electrical Voltage/Current on Farm Animals - How to Detect and Remedy Problems. Agricultural Hand Book No. 696. Woolford, M.W., 1972. Small Voltages on Milking Plants. Proceedings of the Second Seminar on Farm Machinery and Engineering. Ruakura Agricultural Research Center, Hamilton, New Zealand. pp. 41-47. Woolford, M.W., 1971. Recording Transient Voltage Pulses in Milking Plants. New Zealand Journal of Agricultural Research, Vol. 14, No. 1, February, p. 248. HICHIGAN STATE UNIV. LIBRARIES IIIII IIIIII III IIIIIII IIIIII IIII III III IIII III IIII IIIII IIIIII 31293014099372