Design for Heating & es PCIE Cat i mete RAY ae ae were te | wt Bea eh Pv We yi o E, C,. Pokorny is) Ge VENA Ih 3 1293 01748 8754 This thesis was contributed by Mr. E. Ce Pokorny under the date indicated by the depart- ment stamp, to replace the original which was destroyed in the fire of Mar. 5, 1916. A design for a Heating and Ventilating system for the new Engineering Bullding at the Michigan ae Agricultural College. E. C. Pokorny. GUase 1o'l. THESIS A design for a Heating and Ventilating system for the new Engineering Building at the Michigan Agricultural College. In designing a heating system, there are several things which must be taken into consideration, such as the size of the bullding, its location and its distance from the power plant. = BUILDING = The building in which the sustem is to be installed is rectangular im shape, 184 feet long and 84 feet wide. It is five stories high, the first story of stone and the other stories of brick... (These measurements do not include the laboratory in the rear of the building.) The building is partly protected on the east side by the old Mechanical Building and on the west side by Wells hall. The building has a north and south exposure. = KIND of SYSTEM = As there are several different systems of heating build- ings or the campus, it was possible to determine the efficiency of each system and make a comparison of same. From these results as a basis to: work from, it was decided to use the direct, indirect system of heating. In the direct system, the radiators are placed ir the rooms and heated directly. In the indirect systen, the air is taken from an outside source and drawn in betwwen stean coils, by means of a blower. From the blower, the air is forced through a tunnel to the different ovenings in the wails and then into the rooms. The direct system is to: furnish forty per cent of the required heat and the indirect system sixty per cent. AGAQYR By using these two systems together, a good system of ventilation to the different rooms is provided for. The system is to be arranged so as to heat the rooms at a temperature of seventy degrees Fahrenheit, when it is zero degrees outdoors. As most of the buildings on the campus are heated by steam from the boiler house, it was decided to get the steam in the same manner. = DIRECT RADIATING SURFACE = The amount of heat required for each room, depends upon its size, the amount of air supplied and the glass and exposed wall. surfaces, f§ince there are some losses caused by leakage around the sash and window frames, it was necessary to allow about ten per cent in figuring the amount of radiating surface re- quired. The amount of radiating surface put in depended also on the exposure of the rooms, Where the exposure Was from the north, ten to fifteen per cent was allowed. On a west exposure ten per cent was allowed. This rule was not strictly adhered to because it depended largely on the size of the rooms and the size of the radiators which did not always contain the number of square feet requirede. To find the amount of radiating surface required, the following formula from Carpenter's Heating and Ventilating was usede. R = €0-cscegw) (f=¢_)- 55 T-t+ a N =Number of times air is changed in rooms per hour, C = number of cubic feet in each room. G = number of square feet of glass surface. W = area of exposed walls. = temperature of room taken as seventy degrees. = temperature outdoors " " zero ° = temperature of radiating surface. =heat given off per square foot of radiating surface per hour per degree difference in temperature, @ i ct ct This rule is not as simple as the following rules and a comparison of same shows that Willets rule is equally as good. = ~“MILL®S RULE FOR DIRECT RADIATION = (Monroe's Book) windows. = number of cubic feet in room. Ra .5G + .OSW + .O05C. RK s number of square feet of radiating surface. Gs " glass" Wea * " " " " wall surface not including C This rule holds good when temperature of room is 70 degrees and outside temperature from 10 to 15 degrees below zero. « WILLET'S RULE FOR DIRECT RADIATION = (Monroe's Book) = .9(t-t)(.6G + .1W + .0025C)FU = t Factor depending on method of heating. 8 for low pressure systems. , z@ = factor depending on exposure of building, =z 1 for south and east exposure and 1.4 for north and. west ayy oD When t is taken at 8 degrees below zero, t at 70 degrees, F at .8 and J at 1, the formula redues to the following. R = ,486 + .O8W + .002C = MONROE'S RULE FOR DIRECT RADIATION = = (1.3G + .25W + .008C} J (t-t) © (Teta = depends om exposure and taker as l... = temperature o¢ steam im radiator. = " room. = " " outside air, 2 R J T t t a coefficient of heat transmission from a radiator which varies from 1.7 for low pressure steam to 1.9 for 40# steam pressure. This reduces the formula to the following. R= ,42G + ,O8W + .O0026C. = STEAM MAINS = (Mills System) To get the best results and on account of the location of the rooms, it was thought best to have the mains run from the tunnel west to the main entrance. From each corner of the entr= ance the mains extend pp to the attic floor and then in an east= erly and westerly direction. These mains cphtinue around the building to the south side where they decrease in size, The return mains are to be placed in the basement and run im the same direction as the steam mains. Between the steam mains and the returns are the risers and from the risers, extend the branches to the different radiators. fhe return main is to be some what larger 80 as to equalize the pressure, in case there should be an excess of steam in the returns. The highestpoint of the return is to: be near the main entrance, The lowest point of the returns will lead into two steam taps which are to. be fitted with by-pass valves. From here the two pipes lead into one and continue on to the tunnel. The total amount of radiating surface is 11677 square feet, but as 40% of this is to be direct, we have 40% of 11677 or 4671 sqe ft. of radiating surface for direct heating. To figure. the size of main required Carpenter's table om page 223 was usede. Assuming a velocity of 50 feet per second for steam and a pressure of about 3 lbs, we use the tables as follows: Column lL gives the velocity. 3 " " factor for diameter of pipe. " 5 " " steam pressure in lbs, Then the square root of the number of sq. feet. of radiation x .092 gives the diameter of the steam main.,. 4671 x .0O92 = 6.25 inches diameter, The area of a pipe 6.25 in. in diameter « 380.6 square ine " " two pipes 4 " = 25.0 "*" It was decided to. use the two: four inch mains and put on a little more steam pressure if necessary. The returns were figured wome what larger to:allow for any excess of steam that may. pass through the risers and into the returns. This would give the surplus steam a chance to flow up some o¢her riser and thus equalize the pressure. = SIZE OF RETURN MAINS # Prof. Carpenter says that the size of a return pipe should be about one size less than one half the size of the steam main, Since the diameter of the steam main is 6.25 inches, the diameter of the return main would be about 3 inches. «= SIZE OF BRANCHES LEADING TO RADIATORS, ® » wthe pipes running between the risers and radiators are called branches. As there is no fixed rule for determining the sizes of them, we have figured the sizes on the following basis. For 20 fty.or less of radiating surface Ltt. each radiator use 1" pipe " 20 to 60 ft. " " "12" * v 60° Lo 8D : 7 | ve 7 7 ve 1 " ve J 80: to OOM a] Ls] t? Ls] A] " t Qn i] The above sizes wiil evidently give good results, since they are generally used in the ordinary practice of steam heating. Carpenter's, Mills and Monroe's Books om: Heating and Ventilating were used as reference hooks for this thesis. = SIZE OF RISERS = To determine the size of a riser, it is necessary to: know the amount of radiating surface to:be heated by the riser... This amount should not exceed 400 sq. feet. In our case, we intend to use a 2" riser throughout the building, although in some places the 2 in. riser is a little larger than necessary and in other places, it is a little smaller. By using the 2 in. risers, it simplifies the piping and equalizes the steam pressure in the risers. = RADIATORS = Yaving determined the amount of radiating surface reguired in each room, the number of radiators required was figured as follows: Each room is to have a certain number of radiators, depending on the number of sq. feet of radiating surface. Divide this amount into certain parts, each part corresponding to the size of the radiator wanted.. The size of radiator depends on its location, for if the radiator is to be near the north or west wall, it should be larger than if placed near an inner wall. Where the radiator has a west or north exposure, we have allowed from 10 to 15% more, to allow for losses due to such exposures, (See .data sheet for number of radiators and amount of radiating surface). Also see specifications. =.THE INDIRECT SYSTEM = | The indirect system is to be installed with the direct System for the purpose of furnishing 60% of the heat when it is required and also to give good ventilation. Tou get the best ree Bults, it was thought best to place a thermostatic valve on each radiator, so that in case it got to warm, the thermo-stat would close the valve. It is intended to operate this system without opening any of the windows, Of course there is a limit to the amount of hot air entering the room. fhat is, on cold days, it will probably be necessary to. use all the four section of steam coils, which are to heat the air, but on warmer days, it will not. There are to be four sections, conmected so - that any one section or alli of the sections can be shut off. The hot and cold air registers will also furnish a method of shutting off excess of heat, although this method is to be avoided if possible. =z AMOUNT OF INDIRECT YEATING SURFACE REQUIRED = First Method. See Carpenter's book on Heating and Ventilating, page 292. No. of square feet of radiation = -ne(t-t) = R 56a(T-t.) T = temperature of heated surface 220° t= " " air in the room 70° t's " " outside air 0° t"= tomperature of air leaving heated surface 120° t.2 mean"temperature of air surrond heating surface 60° tag (tt! n * number of times air is changed in room per hour C = number of cubic feet in rooms. a= coefficient giving number of heat units per degree aifference of tempprature per square foot per hour from heating surface, ne # 3 x 800000 = 2400000 cubic feet, Oo T= 220 t= 70° t.= 60° t.##(120°-0)=60 t' #0 3 x 800000(70°) | Ro maS eee os. - = 2850 square feet radiatin. 58 (10) 180 a ° né surface, The number of hea .t units given off per degree difference of temperature per square foot of surface per hour is equal to twice the square root of the velocity of the air in feet per second. Assuming a velocity of 25 feet per secon, we have 2V25 #:10. A= 10. « SECOND METHOD = Carpenter's, Page 293. Amount of air delivered per hour # 40000 x 60 = 2400000 cu. ft. Temperature of air to be delivered into room = 130° Steam pressure in coils = 3 Temperature of condensed water = 213° At 3# pressure Qbove atmosphere = 17.7 = 1181 BTU. 1181 BTU in 1# steam 213 \" =" 1# water 968 " given off by heating surface. See Garpenter's table 8, page 382.At 70° one heat unit willi warm 56 cu. ft. ofair one degree and to heat one cubic foot 130° will require 2.32 heat units. Each pound of steam gives off 968 heat units and will. heat 450 cu. fset of air from O zero to 130°. To heat 2400000 cu. feet of air to 130° will require 5334# of stean. The indirect heater with blower attachment will: condense about 2# of water per square foot ofsurface per hour, 4aence the total amount of square feet of surface is equal to.5334 lbs. divided by, 2 = 2660 square feet of radiating surface,. = AIR SUPPLIED PER OUR = The amount of air supplied per how to each room was figured as follows, Allowing 40000 cubic feet per minute as the canacity of the blower, the total number of square feet in the warm air registers was found. Then dividing the number of cubic feet by the area gives the number of cubic feet per ome square foot of register area, Multiplying this by the area of each register gives the amount of air flowing through register per one minute. 2 0000 eee eee x size ofregister in sq. feet x 60 Area of registers in sq. feet =z amt of air per hours. = SIZE OF HOT AIR REGISTER = See Carpenter's, page 53. Velocity of air taken at 3 ft. per secondand air is to be changed 3 times per hour. mrhen from the tables we have 40 square inches in area per 1000 cu. ft. of air. Divide the total volume of each room by 1000 and multiply by 40, and the result will: be the area of the register. The net area of the register should be from .5 to..7 of the nominal area, To get the best results with the circulation of air in the rooms, it is necessary to have the hot air register about 7 feet above the floor and the cold air register on the same side of room and near the floor. (See data sheet for size of registers) = THE MAIN DUCT AND BRANCHES = To get the best results and to save as much space as possible, it was decided to have the hot air duct run under the Ground floor in an easterly and westerly, direction. At the east end the duct branches north and south, being some what smaller in size than the main duct. The blower is to be located in the fan room, which is the first room east of the main entrance. The duct is to come to a piace directly under the blower, and from here, the duct runs dus west and then makes a large turn to the south and into the main duct. = SIZE OF TUNNEL = Toodeterminethe size of duct required.(See Carpenter's page 53). The nundver of cubic feet of air per hour is 2400000. Assuming the velocity to be 15 feet per second, we find in the tables the factor 26.6, which ia to be multiplied by(2400000 os 10000) which is equal to 6384, This amount 6384 — 144 gives 45 square feet, which would be equal tothe cross sectional area of the tunnel. This would enable us to use a tunnel about 64 x 7 feet in size, | « SIZE OF BLOWER =» There is one thing that must not be overlooked, figuring out the sige of the blower and that is that it should run without making too. nuch noise. To be able to do this and get the best results, the blower should run from 180 to 200 revolutions per minute. To figure out the size of the blower,, we know that it must be able to deliver about 40000 cubic feet of air per one ninute. Since the blower is to stand im am open room and have a free out- let, it will) be able to discharge air at a velocity nearly 10% greater than the peripheral velocity of the fan blades. When the blower is arranged so it will draw its supply ofair through banks of heated colls and discharge tHrough the tumrel, the resistance due to friction is so great that it reduces the velocity about 50%. a ey To allow for this loss and to:retain a factor of safety, it 18 necessary tovhave the peripheral velocity of the fan blades equal to the linear velocity of the air and the efficiency of delivery is to: be 50% of the latter amount. Assuming the diameter of the fan as 8 feet, we will seeif it willl fufull our conditions, : 8 ft. x 3.1416 x 180 = 4536 ft. using 180 RPM But since we must ailow 50% for friction, we have 4536+ 2 = 2268 ft. per minute. The size of opening for an eight foot fan is about 19 square feet. Multinlying 2268 feet per minute by 19 sq. ft. gives 43092 cubic feet. This willibe the amount of air delivered per minute, which is somewhat larger than we used. = POWER REQUIRED = According to Carpenter's tables of capacity and power of blowers, a 7 3. YP. engine would run the blower. But the blower igs to be run by: an electric motor instead of an engine. To be on the safe side in case a greater speed is desired, al2to 16 i,?r. motor was thought sufficiently large enough to run the blower. Specification for a Yeating and Ventilating system to: be installed in the New Engineering Building at the Michigan Agricultural College. = CONSTRUCTION = The heating system proposed i8 to be a direct, indirect System and to include the furnishing, delivery and complete erection, in said building and at the above place, all material and labor which shall. enter into othe construction of the above system. All work lis to be first class and done in a workmanlike marner and according to the following specifications, The words "Owner" and "Contractor" refer respectively. to owning the building and the party doing the work. The system is to be erected in twc parts,(See drawings of elevations) the east and west half. It is to be a low pressure, gravity system and sovarranged that the radiators car be shut off without interfering with the ctrculation system. All main risers leading from the basement to the top floor are to be properly supported and fastened by wrought iron straps. All mains running in the direction, as the flow of the steam are to have a fall of one inch in every twelve feet. = PIPES AND FITTINGS = All necessary pipes and fittings are to be of such sizes and connected as shown on drawings, so as to give a free and noiseless circulation. The system is to be free from all water pocketse Wrought irom shall be of standard quality and as follows: All pipes 14" in diameter and above are to be lap welded and tested to 300 per square inch. All piping and fittings are to be exposed. All: mains and returns passing through walls are to have wrought iron thimbles with cast iron flanges on each side of the wall. A two pipe coil is to be placed along the east wall of the dark and wash rooms located on the top floor. This coil is to be about 30 ft. long and made up of 14" pipe. It is to have a Fairbanks Radiator valve and Allen's automatic air valve, All mains to be 3" = 33" and 4" as shown on elevation dravings. " returns " * 3" n ' of tt tt Ui risers | fe Off oN" ” La] ? ve wv = HEATING COILS = The heating coils which are to be used far the indirect system are to: be erected in the basement and placed in their proper Place... The pipes are to:be 1" in diameter and 2%" from center to center. These coils are to be made into 20 sections, each section being made up of a cast iron header with holes tapped for pipes and.an.opening for the feed pipe om the front end and an air pipe on the rear end.(See drawings for same.) All air pipes to.extend above the sheet iron covering and connected with automatic vacum valves. Each section is tobe tested long enough to see if coils are free from leaks. Each section is to be connected to the feed pipe which is conrected to the main header above. This header connects tovthe main leading touthe tunnel. « HBUSING THE COILS = The contractor is to:;house in the coils with No. 18 gauge sheet steel, all properly riveted and supported. The east end of housing to be left open for the supply of cold air. The front portion of the housing is to be so arranged that the sheets can be taken off and any desired sectiom removed without disturbing the other. part of the housing. The housing to be made tight aroumil the blower. The housimg:.is to-be painted with one coat of asphaltum varnish on the inside and two coats on the outside. For the sizes of angle and tee irons to:-be used in the construction of the housing. (See drawings and details of same.) = RADIATORS = The radiators are to be of Berfectiom pattern and of such size as specified.. All radiators carrying 20 ft. or less of radiation tohave 1" radiator valves. All radiators carrying 20 to 60 ft of radi&tion to have 13" radiator valves. All radiators carrying 60 to 80 ft. of radiation to have 1#" radiator valves. All radiators carrying 80 to 100 ft. of radiation to have 2" radiator valvese All radiators to be fitted with Allen automatic air valve. = FLOOR AND CEILING PLATES = All pipes passing through walls, partitions and floors must be provided with galvanized iron sleeves and all necessary floor and ceiling plates. The Crane cast iron floor and ceiling plates to be used. =z VALVES = The Fairbanks Radiator Valve with thermostatic conrections is to be used throughout the building on all direct radiation. All radiator valves to have ground joints and union eouplings. = PIPE COVERING = All mains to be covered with pipe covering composed of 85 % magnesia and 15% asbestos and to be 1" :hhick.e After the mains are covered, they are to be painted with one coat of fire proof mineral paint. * CARPENTER AND MASON WORK = All necessary mason and carpenter work to be done by _the masorr and carpenter contractors on the building.. The steam fitter must give the contractor sufficient time to docany. cutting or changing that he orders,. providing that the changes ordered are approved by the superintendent of the tuilding. = DECORATING = All painting and decorating(not includingthe mains) is to be done by the owner, = TEMPORARY HEAT = Temporary heat is to be furnished when the owner thinks it is necessary and he is to take the responsibility for any damage to the work that may be caused from same, =. CHANGES IN THE WORK = Any changes made im the plans or specifications are to be submitted to: the owner or his superintendent who is to. have charge of the work. Upon his consent for any change, a written request for this change must be handed to the superintendent and he is to keep a record of same. If any of these changes are extra, or the change im the work is a saving for the owner,. then they are to be allowed for at the same rate as the contract price... «= COMPLETION OF THE CONTRACT.= When the heating system is completed and ready for testing, the contractor is to notify the owner, who is to. make the final inspectiom of the work. If for any reason that the ownexp should overlook some detail of the work and said work not being acdording to plans or specifications, the contractor is to:-be held responsibl¢ for same. The contractor is not ta be held responsible for any delay in his work it is caused by other contractors or by, changes im the work which are suggested and ordered done by, the owner. @ PAYMENTS = No work is to be paid for unless same is inspected by the owner or his superintendent. ‘The payments are to be made as the work proceeds and om a basis of 70% of the value of the work at the time of payment.. = FINAL = These specifications cover everything necessary to make a first class direct, indirect steam heating system. If at any -~ - , - , q . . - ~-. . . , : . . . > 2 . a ‘ , 3 . ae . . f ' . ’ set oa , é . 7 =e . 2 6 - \ ‘ . ’ . , 4 o- . \ 1‘ ° . t ’ . wa ‘ ‘ . . = -- . - —t - . ‘ \ , ‘ ° . . > \ ‘ . - @.* . ‘ ’ * 7 , x ‘ ' ' - ‘ - - . > ' . ‘ , 2 . « ' ' . - + ae 4 time that the contractor does not clearly understand the full meaning of the plans or specifications, he is expected to see the superintendent and get his interpretation of same. The plans of the heating system and of the building are to be used to: the best of advantage. All_final measurements are tobe taken from the building and not from the drawings. = BILL OF MATERIAL.= 561 ft. of 4" wrought irom pipe 75 "34" " 565 v? La ia 7 ? 1868 we ” on e a] re 360 v "ian vf " L 305 " "12" " Ss ] te 50 " " 1" a] ef Cs] 21" Fairbanks Thermostatic Radiator Valves. 45 1: 65 13" ve | # o 6 e | , en . § w 118 Allen's automatic air valves. ‘ 92 4" Gate valves. aT ate Cast irom pipe flanges for brick wall. 7 3" te w | | ve | 6 4" Pie sufports in basement. 54 3" " = RADIATORS = No. Radiating Surface(Sq. Ft.) Sections Height Length. 30 78 19 38" 474" 2 92 23 38" 57a" 4 52 13 38" 32a" 3 56 L4 38" 25" 9 48. 12 38" 30* 5 36 9: 38" 224" 2 24 9 26" 225" 3 157 28: 38" 70" 6 72 “ 1& 38" 45" 1 80: 15 ge" 3t4" L 16 4 26" 10* 1 20 5 26" 123" 1 40 10 38" 25* 8 60 15 38" 37%" Ll 64 16 38" 40" ' - . « ' - ‘ ‘ . - t . + . . nf nd . . 1 ' , . . . + . . . ‘ 14 . . . . _ e —- ae . \ ‘ ® *. oe at ea 1 re ' e oe . ? . Gs ae ‘ ar . aa e? oe oo +; 9 ‘ oe . so te oe + ve ! i +o o t° - . ‘ q o¢ ‘ ' re : « . - : + ey . . ‘ u ' 1 . - - ro. ?t ie ve . . x. " ts yee " ‘ we ' 4 . ‘ , . e . . oo . . . . et . .- > e . 3 me es ‘ wee . : . : : . , ‘ ‘ ees a ey e t '! ! vt ' . : os - 7s ‘ se " my . \ . ees spt ae . ' ’ se. a . ‘ - et ‘ 9 ey ry st ‘ e ~ . me , ~- ‘ . : , . Py t . ‘ - - a ‘ . - e- ' 4 . ‘ "Woe * a? 5 4 - s C ? . to. ' ¢* 4 , . . . : - we we * e ‘ eae . No Radiating Surface(Sq.Ft.) 10 4 13 4 68 32 44 28 Sections 17 8 Ll 7 Height 38" 38" 38" 38" Length. 422" 20 OTe" 174" ome ee (Mn me ee iy HEATING PLAN @G BLOG 7A.C. ‘ER Y Co/L CASING E ELEVATION. ———— el a ATING PLAN BLDG MAC. Y COIL CASING ELEVAT/OYW. + = i | zm a be PERFEL i “ “ a rie « cis en: Pe aes een SG = i} 5 Ps ans , er Loe ' ‘te yeaa ° .eE bow ecg yee f f > me aor = 7 ms) Zi " Wat: : : 7 ; . : ; | ‘ nw a iF > * x “a ‘ ; s ~ . ’ . _ ; — ails a MICHIGAN STATE UNIV. LIBRARIES iii 1293017488754