CHARACTERIZING TEMPERATURE INDUCED STRENGTH DEGRADATION AND EXPLOSIVE SPALLING IN ULTRA HIGH PERFORMANCE CONCRETE By Mahmood A. Sarwar A THESIS Submitted to Michigan State University in partial fulfillment of the requirements for the degree of Civil Engineering―Master of Science 2017 ABSTRACT CHARACTERIZING TEMPERATURE INDUCED STRENGTH DEGRADATION AND EXPLOSIVE SPALLING IN ULTRA HIGH PERFORMANCE CONCRETE By Mahmood A. Sarwar Significant research and development in concrete technology have led to the evolution of ultra-high-performance concrete (UHPC). UHPC possesses excellent durability and ductility characteristics, and exemplary tensile and compressive strength properties. Therefore, owing to its superlative properties UHPC is being progressively used in infrastructure and must satisfy fire resistance requirements. Yet, evaluating fire resistance requires knowledge of elevated temperature mechanical properties, and unfortunately such properties are lacking. Furthermore, exploratory investigations reveal UHPC’s composition and construct precipitate the temperature engendered dilapidation of its strength, and it is highly susceptible to fire induced spalling. To fulfill this integral gap, a comprehensive experimental study was undertaken to develop temperature induced degradation in compressive strength, along with the fire induced spalling behavior of UHPC. Variables were introduced to the testing program through varying the content and type of fibers, and varying the application of heating rate. Furthermore, UHPC’s results were compared to four conventional concretes tested, and recommendations as prescribed in ASCE (1992) and Eurocode 2 (2004). Results from the experimental testing reveal the compressive strength and stress-strain behavior of UHPC deviates from conventional concretes, and there is a vast disconnect amongst the experimental results and recommendations prescribed in codes. Moreover, successful testing of UHPC at and above 300°C, was only possible through drastically reducing the heating rate to less than 0.75°C/min. Otherwise, employing higher heating rates induces explosive spalling at temperatures as low as 190°C. Copyright by MAHMOOD A. SARWAR 2017 To my Beevee, our three babies, Baby Girl, Iman and Afreen, and to all the children who have suffered through war and tragedy. iv ACKNOWLEDGEMENTS Sincere thanks go in particular to my supervisor Prof. Venkatesh Kodur for his valuable guidance and constructive suggestions he provided in undertaking this research and in preparation of this thesis. Also, special thanks to the distinguished faculty members who served on my committee: Professors: Parviz Soroushian and Weiyi Lu. Thank you to all my committee members for their support, patience, encouragement, useful suggestions and guidance. Most importantly, I thank God who brought my wife and I together. Her continuous love, care and patience is what keeps me on my feet. Also, I would like to thank the whole of our research group, especially Mohannad Naser, Ankit Agrawal, Xu Dong, Saleh Alogla, Puneet Kumar, Roya Solhmirzaei and Esam Aziz. Thanks to the faculty and staff in the CEE department, Veterans Certification Team and Student Veteran Resource Center for their support and help, especially the manager of the Civil Infrastructure Laboratory Mr. Siavosh “Sia” Ravanbakhsh for his mentorship and everlasting patience. Without his guidance, I would not have been able to complete my experimental testing. Additionally, I would like to extend my thanks to Mrs. Laura Taylor, Mrs. Margaret Conner and Mrs. Laura Post for all their help. Lastly, thank you to all my family for their love and continuing prayers. v TABLE OF CONTENTS LIST OF TABLES ..................................................................................................................... ix LIST OF FIGURES ..................................................................................................................... x CHAPTER ONE ......................................................................................................................... 1 1. INTRODUCTION ................................................................................................................... 1 1.1 General............................................................................................................................... 1 1.2 Fire resistance properties of concrete ................................................................................ 4 1.3 Mechanical properties of concrete at elevated temperature .............................................. 5 1.4 Objectives of this research ................................................................................................. 6 CHAPTER TWO......................................................................................................................... 9 2. STATE OF THE ART REVIEW ............................................................................................ 9 2.1 General............................................................................................................................... 9 2.2 Thermal properties of concrete ........................................................................................ 10 2.2.1 General .................................................................................................................. 10 2.2.2 Test methods for high temperature thermal properties .......................................... 10 2.2.3 Previous studies on thermal properties .................................................................. 12 2.2.4 Effect of temperature on thermal properties of conventional concretes................ 12 2.2.5 Effect of temperature on thermal properties of UHPC .......................................... 13 2.3 Mechanical properties of concrete ................................................................................... 13 2.3.1 General .................................................................................................................. 13 2.3.2 Testing methods for high temperature mechanical properties .............................. 15 2.3.3 Previous studies on mechanical properties ............................................................ 16 2.3.4 Compressive strength ............................................................................................ 17 2.3.4.1 Effect of temperature on compressive strength of conventional concretes . 17 2.3.4.2 Effect of temperature on compressive strength of UHPC ........................... 18 2.3.5 Tensile strength ..................................................................................................... 19 2.3.5.1 Effect of temperature on tensile strength of conventional concretes .......... 19 2.3.5.2 Effect of temperature on tensile strength of UHPC .................................... 20 2.3.6 Stress-strain relationship and elastic modulus ....................................................... 21 2.3.6.1 Effect of temperature on stress-strain relationship and elastic modulus of conventional concretes ............................................................................................ 21 2.3.6.2 Effect of temperature on stress-strain relationship and elastic modulus of UHPC ...................................................................................................................... 22 2.4 Fire induced spalling ....................................................................................................... 23 2.4.1 General .................................................................................................................. 23 2.4.2 Causes of spalling .................................................................................................. 23 2.4.2.1 Rate of heat and thermal stresses induced by thermal gradient .................. 24 2.4.2.2 Pore pressure build-up ................................................................................. 24 2.4.3 Previous studies on fire induced spalling .............................................................. 25 2.4.4 Methods for minimizing explosive spalling .......................................................... 26 vi 2.5 Research gaps .................................................................................................................. 28 CHAPTER THREE ................................................................................................................... 54 3. EXPERIMENTAL STUDIES ON COMPRESSIVE STRENGTH AND EXPLOSIVE SPALLING OF UHPC AT ELEVATED TEMPERATURES ................................................. 54 3.1 General............................................................................................................................. 54 3.2 Design of mechanical property experiments ................................................................... 54 3.3 Mechanical properties tests ............................................................................................. 55 3.3.1 Batch mix proportions ........................................................................................... 55 3.3.2 Test specimens....................................................................................................... 56 3.3.3 Test apparatus ........................................................................................................ 58 3.3.4 Test procedure ....................................................................................................... 58 3.3.4.1 General procedure ....................................................................................... 58 3.3.4.2 Compressive strength, stress-strain relationship, and elastic modulus ....... 60 3.4 Results and discussion ..................................................................................................... 61 3.4.1 Sectional temperatures........................................................................................... 61 3.4.2 Compressive strength, elastic modulus, and stress-strain relationship.................. 63 3.4.2.1 NSC ............................................................................................................. 64 3.4.2.2 HSC ............................................................................................................. 65 3.4.2.3 UHPC .......................................................................................................... 67 3.4.3 Fire-induced spalling behavior .............................................................................. 70 3.4.3.1 Spalling behavior in experiments ................................................................ 70 3.4.3.2 Temperature gradient and rate of heat analysis ........................................... 74 3.5 Summary........................................................................................................................ 110 CHAPTER FOUR ................................................................................................................... 111 4. COMPARISON OF PROPERTIES OF UHPC WITH CONVENTIONAL CONCRETE AND BUILDING CODES ...................................................................................................... 111 4.1 General........................................................................................................................... 111 4.2 Comparison of room temperature properties ................................................................. 111 4.3 Comparison of elevated temperature properties ............................................................ 112 4.3.1 Comparison of UHPC with conventional concretes tested ................................. 112 4.3.2 Comparison of UHPC with building codes ......................................................... 114 4.4 Comparison of spalling.................................................................................................. 114 4.4.1 Comparison of UHPC with conventional concretes tested ................................. 114 4.4.2 Comparison of UHPC with building codes ......................................................... 114 4.5 Summary........................................................................................................................ 123 CHAPTER FIVE ..................................................................................................................... 124 5. CONCLUSIONS AND RECOMMENDATIONS.............................................................. 124 5.1 General........................................................................................................................... 124 5.2 Key findings .................................................................................................................. 124 5.3 Recommendations for future research ........................................................................... 125 5.4 Research impact ............................................................................................................. 126 vii APPENDIX ............................................................................................................................. 127 REFERENCES ........................................................................................................................ 131 viii LIST OF TABLES Table 2.1: Temperature rise and effect on concrete, adapted from Klingsch (2014) ................... 29 Table 2.2: Survey of UHPC/RPC and UHPFRC studies conducted at ambient conditions ......... 30 Table 2.3: Survey of UHPC/RPC and UHPFRC studies conducted at elevated temperatures..... 33 Table 3.1: Testing regime conducted as part of this study ........................................................... 78 Table 3.2: Mix proportions for UHPC design mixes tested as part of study ................................ 78 Table 3.3: Mix proportions for conventional concretes tested as part of study ............................ 79 Table 3.4: Density and 28-day compressive strengths of concrete cylinders tested as part of study ....................................................................................................................................................... 79 Table 3.5: Details of compressive strength tests of UHPC A & B cylinders ............................... 80 Table 3.6: Details of compressive strength tests of UHPC D cylinders ....................................... 81 Table 3.7: Details of compressive strength tests of UHPC F cylinders ........................................ 82 Table 3.8: Details of compressive strength tests of NSC-SF and NSC cylinders......................... 83 Table 3.9: Details of compressive strength tests of HSC-PP and HSC cylinders......................... 84 Table 3.10: Details pertaining to UHPC tests conducted at, and above 300°C ............................ 85 Table 3.11: Key points from thermal gradient with respect to time graphs for UHPC tests conducted at, and above 300°C ..................................................................................................... 86 Table 3.12: Color legend for thermal gradient with respect to time graphs ................................. 87 Table A1: Additional notes pertaining to UHPC A & B specimen tests .................................... 128 Table A2: Additional notes pertaining to UHPC D specimen tests ............................................ 129 Table A3: Additional notes pertaining to UHPC F specimen tests ............................................ 130 ix LIST OF FIGURES Figure 1.1: Photos depicting explosive spalling in a NSC and HSC column under elevated temperatures (Khaliq, 2012) ........................................................................................................... 8 Figure 2.1: Relative compressive strength versus temperature as per literature from the past 3 years .............................................................................................................................................. 51 Figure 2.2 Relative tensile strength versus temperature as per literature ..................................... 51 Figure 2.3 Relative elastic modulus versus temperature as per literature from the past 2 years .. 53 Figure 3.1: Prepared concrete specimens...................................................................................... 88 Figure 3.2: Table saw utilized to cut and prepare the concrete cylinders ..................................... 89 Figure 3.3: Electrical furnace utilized in heating concrete cylinders............................................ 90 Figure 3.4: Forney load controlled strength testing machine to conduct compressive strength testing as part of this study............................................................................................................ 90 Figure 3.5: Compressometer with (2) LVDTs and (2) metal rods utilized to develop the stressstrain relationship as part of this study ......................................................................................... 91 Figure 3.6: Desired heating rates for high temperature compression tests ................................... 91 Figure 3.7: Temperature data acquisition device utilized as part of this study ............................. 93 Figure 3.8: Temperature versus time development for concrete cylinders tested at 600°C ......... 94 Figure 3.9: Compressive strength with respect to temperature of various concrete cylinders tested as part of research ......................................................................................................................... 95 Figure 3.10: Elastic modulus with respect to temperature of various concrete cylinders tested as part of research.............................................................................................................................. 96 Figure 3.11: NSC stress-strain relationships with respect to temperature .................................... 97 Figure 3.12: Failure modes of NSC at respective temperatures ................................................... 97 Figure 3.13: NSC-SF stress-strain relationships with respect to temperature .............................. 98 Figure 3.14: Failure modes of NSC–SF at respective temperatures ............................................. 98 x Figure 3.15: HSC stress-strain relationships with respect to temperature .................................... 99 Figure 3.16: Failure modes of HSC at respective temperatures ................................................... 99 Figure 3.17: HSC-PP stress-strain relationships with respect to temperature ............................ 100 Figure 3.18: Failure modes of HSC – PP at respective temperatures ......................................... 101 Figure 3.19: UHPC A & B stress-strain relationships with respect to temperature ................... 102 Figure 3.20: Failure modes of UHPC A & B at respective temperatures ................................... 102 Figure 3.21: UHPC D stress-strain relationships with respect to temperature ........................... 103 Figure 3.22: Failure modes of UHPC D at respective temperatures........................................... 103 Figure 3.23: UHPC F stress-strain relationships with respect to temperature ............................ 104 Figure 3.24: Failure modes of UHPC F at respective temperatures ........................................... 104 Figure 3.25: Damage to furnace due to explosive spalling......................................................... 105 Figure 3.26: UHPC specimens following experiencing explosive spalling in electrical furnace106 Figure 3.27: Specimen UHPC B5 displaying water escaping concrete following 300°C test ... 107 Figure 3.28: Relation between rate of heating with respect to either, (1) the spalling temperature, or (2) the maximum center temperature attained ........................................................................ 108 Figure 3.29: Thermal gradient with respect to time for UHPC A & B cylinders ....................... 108 Figure 3.30: Thermal gradient with respect to time for UHPC D cylinders ............................... 109 Figure 3.31: Thermal gradient with respect to time for UHPC F cylinders ............................... 109 Figure 4.1: Relative compressive strength with respect to temperature of various concrete cylinders tested as part of research, and Eurocode 2 (2004) and ASCE (1992) ......................... 115 Figure 4.2: Relative elastic modulus with respect to temperature of various concrete cylinders tested as part of research, and Eurocode 2 (2004) and ASCE (1992)......................................... 116 Figure 4.3: Relative stress-strain relationships for concrete cylinders tested ............................. 117 xi CHAPTER ONE 1. INTRODUCTION 1.1 General The use and implementation of concrete for construction can be traced as far back as over 3500 years (Hertz, 2003). Despite the extraordinary advancements in technology since then, the compulsion for builders to utilize concrete continues to endure the test of time. On both a domestic and global scale, the yearly manufacturing of concrete surpasses any other material, with 8 billion cubic meters globally, and 180 million cubic meters within the United States (Ulm, 2008; Kosmatka and Wilson, 2011). Whether dictated by consumer demand, or simply by availability of resources, the relentless global appetite for concrete continues to further research and development in its strength, durability, and sustainability properties. In the early twentieth-century Abrams (1919) determined that water content was the critical constituent that determines the resulting compressive strength of concrete. Approximately a decade later, researchers discovered concrete’s strength could be increased during placement through the application of pressure (Richard and Cheyrezy, 1995). Furthermore, it wasn’t until the 1970’s that concrete’s density was increased by the addition of silica fume, and/or water reducing admixtures, allowing the compressive strength to drastically increase in the range between 50-120 megapascal (MPa) (Hertz, 2003; Buchanan and Abu, 2017). Such a concrete is referred to as high strength concrete (HSC), and concrete with compressive strength less than 50 MPa is commonly denoted as normal strength concrete (NSC). Finally, in the mid-1990s researchers developed a concrete with a denser microstructure, named ultra-high-performance concrete (UHPC), otherwise known as reactive powder concrete (RPC). UHPC provides compressive strength beyond 150 MPa, tensile strength (post-cracking) higher than 5 MPa, elastic modulus in the range of 40-70 1 gigapascal (GPa), protection from detrimental compounds (chloride or alkali silica reaction), freeze-thaw resistance, blast resistance and increased ductility with the inclusion of steel fibers (Kosmatka and Wilson, 2011; Graybeal, 2015; Gu et al., 2015; Li et al., 2015). Such supreme mechanical properties enable UHPC to be a versatile and durable material. UHPC has a surfeit amount of applications including construction of infrastructure, strengthening and rehabilitation of structures, and within military, petroleum, marine, and nuclear facilities (Kosmatka and Wilson, 2011; Zheng et al., 2014a; Gu et al., 2015). In North America UHPC is predominantly utilized for the construction of bridges to exploit its excellent compressive and tensile strength properties (Graybeal, 2014). As of 2014, 55 bridges and overpasses were constructed employing UHPC (Russell and Graybeal, 2013). The Hosokawa River Tunnel in Japan is the first in its class to be retrofitted utilizing UHPC (Gu et al., 2015). However, UHPC’s implementation is limited to certain areas due to autogenous shrinkage during the early stages of curing, high cost and its poor fire resistance characteristics. Extreme cases of autogenous shrinkage occur in very thin applications of UHPC, but can be avoided with certain admixtures. The initial high cost is due to the volume and type of ingredients used (cement, silica fume, etc.), and availability of such materials (Soliman and Nehdi, 2011; Canbaz, 2014; Yazıcı et al., 2010; So et al., 2015). Nevertheless, implementing a stronger material as UHPC allows the structural engineer to choose a reduced cross section (Russell and Graybeal, 2013). Furthermore, the cost may be driven down by implementing industrial by-products within the UHPC design mix. Contents of silica fume and cement may be reduced by substituting with ground granulated blast furnace slag (GGBFS) or fly ash, while maintaining UHPC’s high mechanical properties (Gesoglu et al., 2015; Xiao et al., 2014; Yazıcı et al., 2009; Alkaysi, 2016; So et al., 2015). Whereas UHPC’s reduced cross section subsides the cost, with increasing temperatures it 2 exacerbates the strength degradation and chance of explosive spalling (Hertz, 2003; Kodur, 2014). The spalling (Figure 1.1) process occurs when concrete is hastily heated, and the vaporized water begins to increase and build up. If there is no clear avenue to release the built-up pore pressure (due to low permeability), it will eventually surpass the concrete’s tensile strength and experience explosive spalling (Khaliq, 2012; Buchanan and Abu, 2017). Depending on the type and size of fire, a structure exposed to such an extreme environment signifies one of the most dire circumstances (Kodur and Phan 2007; Zheng et al., 2012; Kodur, 2014). Given the predominant use of UHPC within North America is for transportation structures, detailed data pertaining to such structures affected by fire exposure is now presented. Transportation structures must endure higher temperatures since the source of fire is petroleum, and fire temperatures can reach 815°Celsius (°C) within the first three minutes (min), which is 66% greater than a standard temperature versus time fire curve such as ASTM E119 (Kodur and Phan, 2007). During the last 22 years, seven fires within tunnel structures have occurred. The Channel Tunnel, connecting Britain and France was the first to suffer such a disaster while employing HSC (Hertz, 2003; Ingason, 2004; Aydin and Baradan, 2012; Bei and Zhixiang, 2016). Due to HSC’s low permeability the Channel Tunnel, along with the Great Belt Tunnel in Denmark, suffered extreme damage in the form of spalling (Aydin and Baradan, 2012; Buchanan and Abu, 2017). The Channel and Great Belt Tunnels’ fire reached a maximum temperature of 1,100 and 800°C, respectively (Khoury, 2000). On the other hand, bridges experience greater damage due to fires. From 1989 to 2000, 16 U.S. bridges collapsed due to fire, and from 2002 to 2015, the number jumped to 27 (Naser and Kodur, 2015; Aziz, 2015). Furthermore, records from 2014 reveal, of the 200,000 fire occurrences via motor vehicles in the United States, nearly 90% occurred while traveling on the highway resulting in 345 deaths and $1.5 billion worth of damage (NFDC, 2017). 3 Considering the increased desire for engineers to select UHPC as a building material, the fire behavior of UHPC must be investigated, and as per local structural provisions these structures must adhere to the fire resistance requirements. However, no requirements regarding fire resistance currently exist for bridges further increasing the consternation, and proving to be quite contrary to fire safety’s main objectives (Naser and Kodur, 2015; Buchanan, and Abu, 2017). 1.2 Fire resistance properties of concrete The fire resistance of a structural member is its ability to withstand elevated temperatures without compromising its structural integrity, stability, and the transmission of heat (Kodur, 2014). Different criteria may be utilized, but fire resistance is typically measured in time. Moreover, depending on the type of structure, it must maintain the previously mentioned conditions for a given specified duration as prescribed in local codes. Thus, for infrastructure applications, fire resistance is imperative. In addition, concrete as a material possesses excellent resistance properties because of its non-combustible nature, coupled with its low thermal conductivity, and high specific heat (Behloul et al., 2002; Kosmatka and Wilson, 2012; Kodur, 2014; Buchanan and Abu, 2017). The combination of such qualities enable concrete to experience a gradual progression of heat across the section and minimize the spread of fire throughout the structure (Kosmatka and Wilson, 2011). However, with the inclusion of silica fume and reduction of water content to achieve denser concrete, the fire resistance is inversely proportional to its strength, and explosive spalling further thwarts its resisting ability. As opposed to NSC and HSC, UHPC’s rudiments are attributed to its granular elements allowing reduction of the cross section, precipitating the diminution of its fire resistance. Therefore, prior to implementing a novel material such as UHPC, understanding the potential of its material behavior with increasing temperature is preeminent. Exploiting the ambient condition mechanical properties of concrete allow the development of 4 varying structural arrangements. However, considering the inherent hazard a fire disaster poses and to ensure the structure meets its fire resistance requirements, the mechanical properties of concrete at elevated temperatures must be understood. The following section will discuss the constituents of concrete influencing the principle mechanical properties, and the risk of temperature induced strength dilapidation. 1.3 Mechanical properties of concrete at elevated temperature Mechanical properties of materials experience a degradation with increasing temperatures. Nevertheless, the composition and construct of concrete can serve as a catalyst to the rate of reduction. The cement paste undergoes several decompositions and dehydration of chemically bound water, resulting in strength loss at each respective temperature. Moreover, the amount of cement can further exaggerate the decrease in strength (Klingsch, 2014). The type and size of aggregate can influence the fire resistance as well. With the former, limestone’s specific heat is much greater than quartz, therefore providing a greater resistance to fire exposure (Kodur and Phan, 2007). Additionally, quartz’s dramatic expansion in volume at temperatures above 500°C, results in further loss of strength (Schrefler et al., 2002; Jang et al., 2016). The latter, dictates the permeability of the concrete, thereby influencing the strength. Utilization of silica fume or the use of finer aggregates jointly with silica fume, will deliver a progressively increasing dilapidation of the concrete’s mechanical properties and allow the concrete to be more vulnerable to explosive spalling (Kodur, 2014). Including polymer fibers to denser concretes may alleviate the explosive spalling but will decrease its strength. As compared to conventional concretes, UHPC is designed on the premise to increase the fineness of its elements to capitalize on its packing density (Kosmatka and Wilson, 2011; Ju et al., 2013; Zdeb, 2013; Richard and Cheyrezy, 1995; Canbaz, 2014). The optimization of the packing 5 density of UHPC is achieved through minimizing the porosity of the UHPC, and exploiting any available space within the concrete’s matrix (Magureanu et al., 2012; Zdeb, 2013). The dense microstructure is achieved through a combination of, (1) low water-to-cement (w/c) ratio of 0.20 or lower, (2) addition of superplasticizers, silica fume, and steel fibers, (3) employing quartz sand vice coarse aggregate (grain size is reduced by a factor of 50), and/or (4) through additional treatments, such as thermal, and/or applied pressure (Hager et al., 2013; Zdeb, 2013; Wang et al., 2015; Wang and Gao, 2016). Thereby, the mechanical properties will suffer a rapid degradation, as opposed to the conventional concretes. Additionally, though UHPC has tremendous compressive and tensile strength, the dense matrix causes it to be tremendously vulnerable to explosive spalling and the data associated to UHPC at high temperature conditions is limited. UHPC’s strongest attributes conversely serve as its paramount imperfection at elevated temperatures. 1.4 Objectives of this research The foremost aims of this research are to illustrate the variation of temperature-dependent compressive strength of different UHPC types as compared to other conventional types of concretes, and to highlight the details pertaining to explosive spalling within UHPC through an inclusive experimental study. To successfully complete these goals, the research objectives listed below were accomplished: ▪ Conduct a detailed state of the art literature review on the thermal and mechanical responses of concrete at elevated temperatures. Also, to enumerate the pertinent research gaps, specifically with respect to UHPC properties at elevated temperatures. The thorough literature review will incorporate experimental and analytical studies. 6 ▪ Evaluate compressive strengths of three design mixes of UHPC at various temperatures (20, 100, 200, 300, 400, 600 and 700°C), immediately following exposure to elevated temperatures. Also, undertake compressive strength tests with differing design mixes of NSC and HSC for comparison. ▪ Trace the explosive spalling behavior of the UHPC specimens at the elevated temperatures stated previously. ▪ Compare the temperature dependent compressive strength and explosive spalling behavior of UHPC with other concrete types, ASCE (1992) and Eurocode 2 (2004). 7 Figure 1.1: Photos depicting explosive spalling in a NSC and HSC column under elevated temperatures (Khaliq, 2012) 8 CHAPTER TWO 2. STATE OF THE ART REVIEW 2.1 General UHPC’s paragon properties allow the employment of such a material in diverse functions. However, with increasing temperatures, UHPC will result in a disparate degradation and associated properties given its granular microstructure; Thus posing a hindrance in reaching the required fire resistance. Therefore, for evaluating fire resistance of structural members, properties at elevated temperatures are required. Moreover, understanding the temperature induced physiochemical changes provides further insight regarding concrete’s deterioration. Klingsch (2014) presents a consolidated table that is consistent with other research conducted, providing the rising temperature with the effect on concrete (Table 2.1). The most notable points will be presented and the data is from the following research, Felicetti et al. (2000), Schrefler et al. (2002), Dehn (2004), Klingsch (2014), Way and Wille (2015), Zheng et al. (2015) and Bei and Zhixiang (2016). At temperatures above 105°C, the physical water is completely evaporated causing an increase in porosity and mechanical properties to decrease. Whereas in higher strength concretes the free water can still produce disastrous results in the form of explosive spalling. The likelihood of explosive spalling is increased at temperatures of 100-300°C upon the evaporation of the chemically bound water within the cement paste. The decomposition of the binder at the above-mentioned temperature range triggers strength loss as well. Further strength loss is attributed to the following, (1) the formation of lime (CaO), from calcium hydroxide, Ca(OH)2, and the magnitude of strength loss is contingent upon the calcium-oxide (CaO) to silica-dioxide (SiO2) (C/S) ratio of the concrete mixture, (2) concrete with siliceous 9 aggregate will cause apparent expansions and result in microcracking due to the α-quartz transforming to β-quartz around 573ºC, (3) temperatures above 700°C the decarbonation of CaCO3 produces additional CaO, along with carbon dioxide (CO2), and from 800-1000°C all chemically bound water within the cement matrix evaporates. Upon cooling of the concrete, CaO rehydrates from the air and CaCO3 reforms, resulting in drastic widening of the cracks (up to 40% increase). Lastly, within siliceous aggregate concrete, the β-quartz retransforms to α-quartz at 573ºC followed with a steep contraction (Khoury, 2000; Schrefler, 2002; Hertz, 2005). Though research pertaining to traditional concrete’s fire behavior is ongoing, owing to UHPC’s composition and construct, grasping its full depth is in its embryonic stage. The following sections will present research pertaining to concrete’s thermal and mechanical properties, and the occurrence of fire induced spalling. 2.2 Thermal properties of concrete 2.2.1 General Concrete is an inert material possessing low thermal conductivity and high specific heat. Such qualities enable it to prevent the spread of fire because it diminishes the progress of heat. However, due to the concrete undergoing physiochemical changes with increasing temperatures, the thermal properties do not remain constant, thereby inflicting change upon the mechanical behavior of concrete with increasing temperatures. Therefore, understanding the behavior of a material exposed to high temperatures, enable the designer to fully exercise the material’s full potential. 2.2.2 Test methods for high temperature thermal properties There are two methods to determine the thermal conductivity of a material. First is the hot wire method and second is the guarded heat flow meter method. The guidelines associated with 10 the former are presented in ASTM C1113/C1113M (2013), and for the latter in ASTM E1530-11 (2016). The hot wire method may be utilized to evaluate the thermal conductivity up to 1500°C, and utilizes an electrical current passing through a wire that is between two blocks of the material to be tested. Depending upon how fast the heat flows to the material block determines the thermal conductivity value. The second method, guarded heat flow meter method, can accurately provide the thermal conductivity up to 325°C. At temperatures beyond 325°C, it is dependent upon the calibration of the equipment. In this method, the material to be tested, along with a heat flux transducer (HFT), are placed between two controlled temperature plates. Therefore, dependent upon the heat transfer from one plate to the other determines the thermal conductivity for the material. To determine the specific heat capacity, the guidelines prescribed in ASTM E1269-11 (2011) recommend using differential scanning calorimetry method. The test is accurate at temperatures between 100-600°C, and beyond it is dependent upon the equipment utilized. The test can be performed very quickly and is simple to conduct. Essentially, select a benchmark and measure the change in heat flow between another selected point and the benchmark. To evaluate the linear thermal expansion of a solid material, one method is to employ a thermomechanical analysis as recommended in ASTM E831-14 (2014). The test is effective up to 900°C, and beyond it is dependent upon the equipment utilized. The specimen is exposed to a consistent heating rate and the expansion of the material is recorded with respect to temperature. Lastly, to determine the mass loss of a material, ASTM E1868-10 (2015) recommends utilizing the thermogravimetry method. The test is valid up to 1000C and applicable to a wide range of materials. The specimen is subjected to a consistent temperature and the mass is measured for 11 either a specified time or once the loss attains a specified value. Following the heating process, the percent of mass loss is calculated by dividing the mass loss divided by the original mass. 2.2.3 Previous studies on thermal properties Investigations pertaining to conventional concrete’s thermal properties have been ongoing for over 4 decades. Moreover, ASCE (1992), Eurocode 2 (2004) and several researchers formulated constitutive relationships pertaining to both NSC and HSC’s thermal properties with increasing temperatures. As compared to conventional concretes, UHPC’s thermal properties have scarcely been researched in the last 2 decades. Furthermore, no current codes dictate the constitutive relationship of UHPC either. The following two sections will impart the notable points from literature pertaining to the effect of elevated temperatures on the thermal properties of conventional concretes and UHPC. 2.2.4 Effect of temperature on thermal properties of conventional concretes As compared to carbonate aggregate, siliceous aggregate contributes negatively with respect to fire resistance, and except for the thermal expansion at temperatures above 700°C, NSC and HSC’s thermal properties are very similar (Lie and Kodur, 1996; Kalifa et al., 2000; Sultan and Kodur, 2003). Concrete with siliceous aggregate’s specific heat remains steady and only experiences a bump around 450ºC, which is attributed to the formation of CaO and H2O from Ca(OH)2. Moreover, the coefficient of thermal expansion (CTE), of siliceous aggregate concrete will abruptly rise around 550°C, due to the quartz transformation. While, the disjoining of CaCO3 will cause two occurrences to transpire in carbonate aggregate concrete. At 700°C, the specific heat undergoes a drastic spike, and at 800°C the CTE deviates from a steady linear rise (So et al., 2014). The thermal conductivity experiences a steady decrease, with the siliceous concrete having 12 the higher values and, the mass loss progressively rises linearly but drastically reduces beyond 700°C due to all the chemically bound water evaporating. 2.2.5 Effect of temperature on thermal properties of UHPC Aside from the thermal diffusivity, RPC’s thermal conductivity, specific heat capacity and mass loss are lower than HSC. Additionally, if compared at temperature levels, the CTE is about the same (Ju et al., 2011). The thermal conductivity and thermal diffusivity decrease with increasing temperatures, while the specific heat capacity and CTE continuously rise (Behloul et al., 2002; Zheng et al., 2014b). Ju et al. (2011) examined the effects of steel fiber content and discovered altering the content of steel fiber only influences specific heat capacity and thermal diffusivity. Behloul et al. (2002) and Wang et al. (2013) studies reported very similar results pertaining to the CTE. Both experienced a linear progression (roughly 12e -6/°C) to about 500°C and both encounter a slight bump between 300-400°C. The bump between 300-400°C is attributed to the decomposition of Ca(OH)2. Beyond 500°C, the CTE experiences a dramatic increase due to the αquartz transforming to β-quartz, followed by a decline after 700°C. Finally, Zheng et al. (2014b) exposed RPC to temperatures of 20 to 800°C and found a smooth and steady mass loss with increasing temperatures. 2.3 Mechanical properties of concrete 2.3.1 General The major proponents of concrete’s mechanical properties are compressive and tensile strength, ductility, stress-strain relationship, and elastic modulus. The preceding properties degradation dictates whether the fire resistance design is acceptable. Prior to presenting the data from literature pertaining to concrete’s behavior to increased temperatures, a synopsis regarding 13 concrete’s mechanical behavior under ambient conditions is discussed, and research investigating UHPC/RPC and ultra-high performance fiber reinforced concrete (UHPFRC) under service conditions is presented. At room temperature, the w/c ratio coupled with the percentage of contact amid the binder with the coarse aggregate, called interface transition zones, play a crucial role regarding the concrete’s strength (Kodur, 2014; So et al., 2014; Kamen et al., 2007). In very dense concretes, the strength is directly contributed by the w/c ratio, integrated with granular constituents and silica fume (Xiao et al., 2014). Specifically, superfluous amounts of silica fume (20-25% the weight of cement) make up UHPC’s binder, and as cement (C3S) mixes with water, (H2O) the chemical reaction results in calcium silicate hydrate, C-S-H and Ca(OH)2. Therefore, in addition to minimizing the voids within UHPC’s matrix, silica fume contributes further by decreasing the C/S ratio, resulting in less production of Ca(OH)2, and increase the production of C-S-H (Khoury, 2000; Schrefler et al., 2002; Kosmatka and Wilson, 2011; Zdeb, 2013). The C-S-H’s role in dense concretes is quite significant as it serves as the chief binder directly contributing to its mechanical properties and houses majority of the chemically bound water (Burke, 2011; Jagannathan, 2013; Klingsch, 2014). Considering UHPC’s very dense microstructure, it enables UHPC to have superior mechanical properties as compared to NSC and HSC at ambient conditions. The current literature pertaining to UHPC/RPC or UHPFRC at ambient conditions predominantly explores different methods to increase the mechanical properties utilizing various treatments or with altering the main ingredients. On the contrary, research pertaining to exploring environmentally friendly and/or sustainable UHPC is quite limited. Yazıcı et al. (2010), Aydin and Baradan (2013), Gesoglu et al. (2015) and Peng et al. (2016) conducted research to develop a UHPC that maintains its mechanical properties while being environmentally conscience, 14 sustainable or economical. Table 2.2 provides a summation of tests regarding UHPC/RPC and UHPFRC, conducted in ambient conditions. Unless compressive strengths greater than 300 MPa are required, developing the appropriate design mix (with no treatment) will result in compressive strengths as high as 200 MPa, (Wille et al., 2011; Zdeb, 2013; Voit and Kirnbauer, 2014). 2.3.2 Testing methods for high temperature mechanical properties Extensive research studies at ambient conditions for NSC, HSC and UHPC conducted by Elwell and Fu (1995) and Graybeal and Davis (2008) provide guidance on choosing the specimens’ shape and state that choosing a cylinder or cube specimen is purely preference and does not alter the strengths. Furthermore, no ASTM standard exists to evaluate mechanical properties of concrete at elevated temperatures. Therefore, RILEM Standard (RILEM Technical Committee 200-HTC, 2007) is utilized to standardize the heating process and dimension requirements, while the respective ASTM standard is implemented for each different mechanical property test. Consolidated recommendations from the RILEM standard pertaining to the high temperature mechanical property tests are presented. RILEM standard recommends three different steady state tests to evaluate mechanical properties at elevated temperatures, (1) unstressed, (2) stressed, and (3) residual state. The unstressed condition demands once the specimen attains its testing temperature, to remain in the furnace for a specified duration to reach complete saturation across the specimen. If a load is to be applied during the heating process, referred to as a stressed test, it must remain constant and must be a certain percentage of the at room temperature compressive strength until complete saturation is attained. Upon saturation of the specimen, the load is increased until failure of the specimen. For the residual-state, the specimen must completely cool down to the ambient condition prior to testing. The compressive strength, stress-strain behavior, and elastic modulus may be evaluated 15 using either of the three methods. While the tensile strength is recommended only for unstressed or residual state. 2.3.3 Previous studies on mechanical properties Just as each element serves a purpose to contribute to concrete’s facets, the constituent(s) can undesirably affect the structural member’s performance with increasing temperatures. There is significant ongoing research evaluating the mechanical properties of conventional concretes. Owing to HSC’s differing microstructure, literature indicates HSC’s mechanical properties decrease faster as opposed to NSC (Zheng et al., 2012; Kodur, 2014). Furthermore, HSC is prone to explosive spalling and mitigation techniques must be utilized. Further discussion pertaining to fire induced spalling will be presented in section 2.4. Discordant with conventional concretes, the bulk of UHPC’s studies have been conducted in the last 5 years. Attributed to UHPC’s granulated elements, and superior strength, its fire performance is dissimilar as compared to the conventional concretes. UHPC’s assets touted by its advocates prove to be its downfall when exposed to elevated temperatures. With increasing temperature, the multitude of physiochemical changes, dilapidation, and the inconsistency of properties between the binder and aggregate undergo, heavily contribute to UHPC’s mechanical property degradation (Khoury, 2000; Zheng et al., 2015; Li and Liu, 2016). Unless proper measures are taken (for instance the addition of fibers or employ pozzolanic resources), UHPC will not be able to endure the elevated temperatures for long (Khoury, 2000; Ye et al., 2012). Table 2.3 provides a summation of studies regarding UHPC/RPC and UHPFRC conducted at elevated temperatures, identifying the strengths, and disadvantages for each investigation. Summarizing Table 2.3 the current research pertaining to UHPC’s mechanical properties exposed to increasing temperatures is dominated by residual state testing of customary UHPC design mixes. 16 Less than one-third explore the behavior with varying fiber type and content. Only three studies evaluate UHPC with a treatment and an additional three investigate the fire behavior of more economical and environmental design mixes of UHPC. In addition, most studies evaluate the compressive and tensile strength and only a handful cover the stress-strain relationship along with the elastic modulus. Finally, there are very few investigations proposing models to predict the explosive spalling behavior of UHPC. The following sections will impart the notable points from literature pertaining to the effect of high temperatures on the mechanical properties of conventional concretes and UHPC. 2.3.4 Compressive strength 2.3.4.1 Effect of temperature on compressive strength of conventional concretes Investigations pertaining to conventional concretes display compressive strength decreasing with rising temperatures and HSC experiencing a steeper degradation (Arioz, 2007; Sarhat and Sherwood, 2013). However, due to the removal of free water and consolidation of concrete, the denser HSC design mixes underwent an increase in strength between 200-300ºC (Ghandehari et al., 2010). Furthermore, the 300 to 600ºC range is crucial for denser concretes, with great strength loss by 600ºC (Demirel and Keleştemur, 2010; Ghandehari et al., 2010). A handful of researchers utilized either recycled or locally available aggregate for NSC or HSC, and discovered the results are comparable to typical aggregates, and quartz dominant concrete will provide a poorer performance with increasing temperatures (Sarhat and Sherwood, 2013; Hager et al., 2016). Yet, if a pozzalanic material blend is implemented to reduce the amount of cement, the concrete’s strength underwent a more rapid deterioration (Demirel and Keleştemur, 2010; Li et al., 2014). In addition, employing higher contents of cement will provide greater strengths under ambient conditions, while suffering a quicker decline with the temperature rise (Ergün et al., 2013). 17 A higher content of w/c ratio does not greatly affect the relative strengths, but will allow a more rapid decrease in strength (Arioz, 2007; Al-Jabri et al., 2016). 2.3.4.2 Effect of temperature on compressive strength of UHPC UHPC is contrived to deliver high compressive strengths at ambient conditions. However, unless the proper mixture is formulated, UHPC will experience sudden degradation and/or explosive spalling. UHPC’s compressive strength at elevated temperatures is dependent upon the design and Figure 2.1 illustrates the sporadic results amongst the literature for UHPC/RPC studies from the last three years (Kodur, 2014). Behloul et al. (2002), Ye et al. (2012) and Zheng et al. (2015) were the only studies evaluating the hot-state compressive strength and two of those, Behloul et al. (2002) and Ye et al. (2012) were stressed while being heated. The non-cured UHPC mix studied by Behloul et al. (2002) performed exceptionally well, attaining 120% of its room temperature strength at 500°C. The unstressed test degraded the fastest to 50% at only 500°C (Zheng et al., 2015). The remainder of tests evaluated the residual compressive strengths. For the most part the tests conducted attain 115-160% of their respective original strength between 100-400°C, soon followed by a steady decline. Aydin and Baradan (2012) and Bashandy (2013) studies experienced explosive spalling beyond 300°C. Aydin and Baradan (2012) design contained high volume of silica fume and cement, while Bashandy (2013) utilized locally available steel fiber and cement to produce an economic RPC. So et al. (2015), Way and Wille (2015) and Jang et al. (2016) achieved the greatest residual compressive strengths of 145, 160 and 140% at 400, 300 and 400°C, respectively. Zheng et al. (2014a) and Zheng et al. (2014b) investigated UHPC with polypropylene and steel fiber alongside UHPC with polypropylene fiber, nearly lost 40% of the compressive strength at 100°C and only increased to 80% between 500-600°C. 18 Aydin and Baradan (2012), So et al. (2015) and Jang et al., 2016 studied the residual compressive strength behavior of UHPC with a ternary pozzalanic material blend. All three studies conducted tests at and beyond 800°C without experiencing explosive spalling and with comparable, if not improved fire behavior than their respective typical UHPC formula. Sanchayan and Foster (2016) tested RPC with a combination of steel fiber and polyvinyl alcohol (PVA) fibers. The RPC mix with high PVA and low steel fiber content behavior was similar, save the strengths attained at 300 and 400°C. Additionally, the high PVA fiber content RPC underwent explosive spalling beyond 500°C. Approximately 15 of the studies evaluated the effects of varying the fiber content of the UHPC. Two researchers concluded the steel and polypropylene fibers contribute positively and 0.9% polypropylene fiber content is recommended (Tai et al., 2011; Abdul-Hussain, 2013). However, Hager et al. (2013) study revealed the content of polypropylene fibers do not provide an impact to UHPC’s compressive strength. Canbaz (2014), Way and Wille (2015) and Xiong and Liew (2015) investigated the effects of various curing treatments. Canbaz (2014) evaluated RPC pressure treated and cured in water at 90°C and Way and Wille (2015) oven dried the UHPFRC and both achieved improvements with respect to the compressive strength. The RPC in Canbaz (2014) study experienced an increase up to 400°C, followed by a decline. However, Xiong and Liew (2015) research did not provide any substantial effect with respect to varying curing techniques. 2.3.5 Tensile strength 2.3.5.1 Effect of temperature on tensile strength of conventional concretes The tensile strength of conventional concretes is influenced by the following at elevated temperatures, (1) enhancement through the addition of steel or hybrid fibers, (2) undergo 19 dilapidation with increasing temperatures, (3) experience a dramatic decrease beyond 300°C, and (4) HSC’s tensile strength sustains a greater decrease as opposed to its compressive strength (Ghandehari et al., 2010, Khaliq and Kodur, 2011). Furthermore, the alteration of the cement content alone does not pose much of a difference with respect to the relative tensile strength, but employing a ternary pozzolanic blend will result in a drastic reduction to 20% of its original tensile strength at 500°C (Li et al., 2014). As expected, the quartz aggregate concrete displayed greater reduction as opposed to limestone aggregate, and increasing the w/c ratio will decrease the tensile strength as well (Al-Jabri et al., 2016; Hager et al., 2016). Finally, similar to the compressive strength, very dense HSC’s tensile strength will increase from 100 to 200ºC, followed by a decline (Ghandehari et al., 2010). 2.3.5.2 Effect of temperature on tensile strength of UHPC Only two studies evaluated both the hot-state and residual-state tensile (direct) strength of UHPC, Felicetti et al. (2000) and Behloul et al. (2002). While Felicetti et al. (2000) results displayed very little difference between the test types, Behloul et al. (2002) study demonstrated the hot-state tensile strength was slightly higher. The remainder of the residual direct tensile tests behave very similarly with increasing temperatures and achieve 50% of original strength between 450-550 (Zheng et al., 2014a; Zheng et al., 2014b; Li and Liu, 2016). Four separate investigations tested the residual splitting tensile strength and Peng et al. (2012), Abdul-Hussain (2013) and So et al. (2015) results are very similar. Their original strengths reduce to 50% at about 600°C. While Bashandy (2013) presented drastic degradation, 50% at 300°C, may be attributed to utilizing cheaper steel and cement. Finally, five research studies tested the residual flexural strength and Aydin and Baradan (2012) and Ali et al. (2016) tested typical RPC mixture containing silica fume could not withstand temperatures above 300 and 400°C, 20 respectively. Additionally, Aydin and Baradan (2012), So et al. (2015) and Ali et al. (2016) found the RPC formulation implementing ternary pozzalanic materials performed quite well at and beyond 600°C. With So et al. (2015) results were exceptionally well, attaining near 150% of original strength at 400°C, reducing to 50% around 700°C and 22% at 1000°C. Aside from Aydin and Baradan (2012) ternary pozzalanic RPC mixture, the remaining RPC’s tested up to and beyond 600°C, reached 50% of their respective original strength. Khoury (2000) claims employing the splitting tensile and flexural strength tests do not provide an accurate representation and concludes the direct tensile strength tests is supreme. However, the literature is evenly distributed amongst the 3 types of tensile strength tests. Finally, increasing the steel fiber content directly contributes to tensile strength (Abdul-Hussain, 2013; Li and Liu, 2016). Figure 2.2 depicts the tensile strengths (direct tensile, splitting tensile and flexural strengths) at elevated temperatures from literature. 2.3.6 Stress-strain relationship and elastic modulus 2.3.6.1 Effect of temperature on stress-strain relationship and elastic modulus of conventional concretes With increasing temperatures conventional concretes’ peak strain increases, the ascension portion is near linear, the descent portion becomes progressively recumbent at temperatures of 500ºC and above, and the compressive strength and elastic modulus lessen (Chang et al., 2006; Zheng et al., 2012). Additionally, the elastic modulus degrades the fastest with rising temperatures amongst the mechanical properties. Finally, the elastic modulus is further reduced utilizing a ternary pozzolanic mixture to reduce the cement content. A study conducted by Li et al. (2014) discovered the addition of high contents of GGBFS hastily declines the elastic modulus at 500°C to nearly a tenth of its original elastic modulus. 21 2.3.6.2 Effect of temperature on stress-strain relationship and elastic modulus of UHPC Only 3 of the studies evaluated the stress-strain relationship, of which two were residual. Zheng et al. (2012) demonstrated residual stress-strain curve attains the peak strain at 600°C, minimal change is seen up to 300°C and beyond 300°C, the curve becomes more flattened. While Tai et al. (2011) found the residual stress-strain curve’s slope steadily decreases with progressing temperature. Greater steel fiber content improved the peak strain between 200-800°C for Tai et al. (2011) but only up to 600°C for Zheng et al. (2015) study. Moreover, Zheng et al. (2015) determined 2% steel fiber content to be most optimum for increasing ductility. Three tests evaluated the hot-state elastic modulus, Behloul et al. (2002) research indicated UHPC decreasing to 50% of its original stiffness beyond 600°C, while Zheng et al. (2015) experienced a sudden degradation at 200°C. Behloul et al. (2002) conducted residual elastic modulus tests as well and found the residual elastic modulus to perform exceptionally well. The UHPC studied maintained within its original stiffness up to 600°C, only to reduce to 80% at 700°C. Hager et al. (2013) was the only other study to reach 50% decline around 800°C. Aside from Behloul et al. (2002) and Hager et al. (2013), the bulk of the remainder elastic modulus results, declined to 50% of its stiffness between 350-500°C. Xiong and Liew (2015) test consisted of various curing methods and heating rates. Their findings displayed the curing techniques did not influence the stiffness and the UHPC exposed to higher heating rates degraded much sooner. Hager et al. (2013) tested various polypropylene fiber content and concluded the addition of polypropylene fiber does not contribute to RPC’s stiffness. Figure 2.3 depicts the elastic modulus at elevated temperatures from literature for UHPC/RPC studies from the last two years. 22 2.4 Fire induced spalling 2.4.1 General Hertz (1984) encountered explosive spalling and hypothesized ultra-high strength concretes developed utilizing silica fume, to densify the concrete’s matrix, have a greater risk to experience explosive spalling. The explosive spalling was attributed to the obstruction of the vaporized water attempting to evacuate the heated specimen. Following further research, Hertz (2003) concluded the increased strength does not necessarily correlate to explosive spalling as much as the exorbitant dense medium attained with silica fume. Although HSC is more susceptible to explosive spalling than NSC, HSC tested with no silica fume proved to be tolerable of increasing temperatures and did not explode (Phan, 1996; Hertz, 2003; Kodur, 2014). Additionally, a comprehensive study conducted by Klingsch (2014) determined UHPC lacking silica fume exposed to extreme heating rates to survive without exploding either. Silica fume maintains a stout link with explosive spalling but there are other crucial factors as well. The following sections will present data from literature pertaining to the foremost causes of spalling and methods to minimize the occurrence. 2.4.2 Causes of spalling Minimal permeability, temperature gradients, migration of moisture and pore pressure build-up, and thermal dilation contribute to explosive spalling (Zheng et al., 2013; Kodur, 2014; Xiong and Liew, 2015; Jang et al., 2016). Additionally, the threat is further augmented by the type of aggregate, specimen dimensions, low tensile strength, type of fire exposure and contents of silica fume, cement (w/c ratio) and limestone filler (Hertz, 2003; Zheng et al., 2013; Klingsch, 2014; Kodur, 2014). Consequently denser concretes experience explosive spalling mainly due to the development of temperature gradients and pore pressure build-up. Furthermore, UHPC is 23 formulated implementing granular constituents and may not adhere to the same mechanisms of explosive spalling as HSC, and regrettably UHPC’s design foundation is concocted upon most of the risks previously listed (Ju et al., 2015; Ali et al., 2016). Therefore, UHPC will experience explosive spalling at a lower temperature and shorter time period (or much sooner) than HSC (Phan, 1996). According to literature, several researchers determined explosive spalling can occur at temperatures of 250°C and above (Khoury, 2000; Burke, 2011; Zheng et al., 2013). 2.4.2.1 Rate of heat and thermal stresses induced by thermal gradient Attributed to concrete’s low thermal conductivity, fire exposure causes thermal gradients to develop resulting in a fluctuation of physiochemical variations across the cross section and thermal stresses (Hertz, 1984). The result is further compounded with applications of excessive heating rates (type of fire). Hertz (1984) research determined the critical rate of heat to avoid explosive spalling with immensely dense concretes is as low as 1ºC/min. Klingsch and Frangi (2011) precursory investigation determined the same value (1ºC/min) for UHPC. However, decreasing the heating rate does not necessarily correspond to mitigation of explosive spalling, because it only minimizes the thermal gradients (Felicetti et al., 2000; Klingsch, 2014). Thermal gradients vastly impact the development of pore pressure and will be discussed further in the next section (Phan, 2008; Khaliq, 2012). 2.4.2.2 Pore pressure build-up Current literature correlates the built-up pore pressure within concrete to be the pivotal cause leading to explosive spalling (Klingsch, 2014; Sanchayan and Foster, 2016). The complication is further exacerbated with low permeability and extreme heating rates (Burke, 2011). In addition, various studies conducted found chemically bound water alone can cause explosive spalling (Hertz, 1984; Hertz, 2003; Sanchayan and Foster, 2016). Therefore, it is no 24 question due to UHPC’s exceptionally dense matrix coupled with high amount of cement, explosive spalling occurs. With increasing temperatures, thermal gradients within the concrete’s cross section will develop and covert the moisture into a vapor. Since concrete maintains a certain amount of permeability, the water nearest to the surface will evaporate, however some of the moisture will follow the pressure gradient and travel inwards and condensate due to encountering cooler temperatures (Ju et al., 2013; Klingsch, 2014). Eventually a saturated barrier will form resulting in increasing pore pressure and soon followed by explosive spalling (Burke, 2011; Klingsch, 2014; Kodur, 2014). To withstand such a pressure increase, it is paramount for low permeability concrete to have great tensile strength (Klingsch, 2014; Kodur, 2014). The process is referred to as moisture clog and is well documented within the literature (Kalifa et al., 2000; Phan, 2008; Dwaikat and Kodur, 2009; Felicetti and Lo Monte, 2013). Explosive spalling can be predicted because the point of explosion will have a much higher pressure than amongst the remaining specimen (Ju et al., 2013). In addition, the moisture clog will occur at a greater temperature with decreasing permeability. However, inclusion of polypropylene fibers within a UHPC design mix reduces the temperature corresponding to the melting point of the fibers, 170°C (Klingsch, 2014; Ju et al., 2015). 2.4.3 Previous studies on fire induced spalling Previous studies by researchers resulted in various measures for evaluating the explosive spalling within HSC and UHPC. The investigations implemented preventive measures such as the use of organic fibers, diminish the contents of cement and/or silica fume, and numerical models. Existing research overwhelmingly utilizes organic fibers, such as polypropylene fiber to alleviate explosive spalling, with only a handful utilizing pozzolanic constituents to reduce the silica fume 25 and cement contents, or the use of locally available material. Moreover, Klingsch (2014) and Ju et al. (2015) developed numerical models to predict the explosive spalling behavior of UHPC with compressive strengths greater than 150 MPa. Though, numerical models require sufficient facets and validation, they provide an immense capability to efficiently determine whether explosive spalling may occur (Dwaikat and Kodur, 2009; Klingsch and Frangi, 2011). 2.4.4 Methods for minimizing explosive spalling A simple and cost-effective method to mitigate the occurrence of fire induced spalling is with the inclusion of polypropylene fibers (Behloul et al., 2002; Bei and Zhixiang, 2016). Polypropylene fibers melt at a temperature between 150-170°C creating pathways to release the built-up pore pressure, and alleviate the rise of thermal gradients (Klingsch and Frangi, 2011; Ju et al., 2015; Xiong and Liew, 2015). Moreover, various studies utilized mercury intrusion porosimetry (MIP) and scanning electron microscopy (SEM) to confirm pathways created by the melting of the polypropylene fibers and the total pore volume increasing between 2-7 times following heating up to 600°C (Hager et al., 2013; Zheng et al., 2014b; Bei and Zhixiang, 2016). The amount of polypropylene fibers required to avoid explosive spalling is dependent upon the entire UHPC design mix and literature displayed values as low as 0.9 kg/m 3 to greater than 2.0 kg/m3 (So et al., 2014; Zheng et al., 2014a). Research conducted by Klingsch (2014) and Bei and Zhixiang (2016) went further to assert the individual polypropylene fibers’ dimension is paramount. The length must be of appropriate size to allow a continuous path for the vapor pressure to follow and the diameter must be kept minimal. Lastly, polypropylene fibers diminish the workability and strength of UHPC and must be implemented proficiently, and researchers advise their use may prove to be ineffective for encapsulated structures (Behloul et al., 2002; Hertz, 2003; Klingsch and Frangi, 2011; Aydin and Baradan, 2012). 26 An alternate method alleviate explosive spalling is to increase the tensile strength of the concrete with the incorporation of steel fibers. Though studies have displayed the effectiveness of steel fibers with HSC, the literature is not in total agreement with their use in UHPC (Klingsch, 2014; Kodur, 2014; Xiong and Liew, 2015; Bei and Zhixiang, 2016). Furthermore, implementing a hybrid fiber (steel and polypropylene fibers) UHPC design mix displayed an improved performance regarding the mitigation of the explosive spalling. Although polypropylene and steel fibers serve an elementary method to reduce the explosive spalling hazard, researchers are evaluating other lucrative techniques as well. To utilize RPC in marine applications to avoid corrosion, while satisfying a tolerance to elevated temperatures, Sanchayan and Foster (2016) conducted a study to determine if PVA fibers can be utilized as an effective substitute for steel. By varying the different fiber contents, the research developed a RPC design mix mitigating the explosive spalling risk through combining PVA fibers along with a small amount of steel fibers, and oven drying the specimens. Although inclusion of PVA fibers reduces the compressive strength, the stiffness comparatively remains the same. Finally, Aydin and Baradan (2012), So et al. (2015) and Jang et al. (2016) successfully utilized ternary pozzolanic materials consisting of GGBFS, fly ash and silica fume to avoid explosive spalling. 27 2.5 Research gaps As per the state of the art literature review, only few studies evaluating the residual-state mechanical properties of UHPC have been conducted in the past five years. Furthermore, data supporting the thermal properties of UHPC with increasing temperatures are severely sparse. Although the residual-state mechanical properties are important, it is quite evident the high temperature properties are lacking. To facilitate evacuation of occupants and allow the first responders an opportunity to fight the fire, the structure must remain standing for the duration it was designed for. Thus, the high temperature mechanical properties are imperative and the following research gaps remain: ▪ No standard exists to evaluate the properties of a cementitious composite such as UHPC/RPC or UHPFRC, at elevated temperatures. ▪ Thermal properties of UHPC with increasing temperature are deficient. ▪ Higher temperature mechanical properties of UHPC are gravely scarce. ▪ Detailed data and modelling of the fire induced spalling nature of UHPC is lacking. ▪ Impact to UHPC’s high temperature mechanical properties with varying steel fiber content. ▪ Impact to UHPC’s high temperature mechanical properties with a hybrid (steel and polypropylene) fiber content. ▪ Impact to sustainable and lucrative design mixes of UHPC’s high temperature and residualstate properties. 28 Table 2.1: Temperature rise and effect on concrete, adapted from Klingsch (2014) Temperature, °C 20-100 105 120-150 150 270 >300 374 400-600 535 573 >700 710-720 >800 1200 Resulting change to concrete Concrete loses free and physical water (begins to dry) Start of hydrothermal reaction C-S-H phase decomposes C-S-H’s first peak C-S-H’s second peak Porosity and micro cracking drastically intensify Complete evaporation of free and physically bound H2O (critical point) Detachment of calcium hydroxide, Ca(OH)2  CaO + H2O Decomposition of Ca(OH)2 maximum point α-quartz transforms to β-quartz (reversible), leading to pronounced expansion Within cement paste and limestone decarbonation of calcium carbonate; CaCO3  CaO + CO2 C-S-H’s decomposition, third peak Full evaporation of all water chemically bound Melting of concrete ensues 29 Table 2.2: Survey of UHPC/RPC and UHPFRC studies conducted at ambient conditions Study/Investigation Richard and Cheyrezy (1995) Reda et al. (1999) Rahman, Molyneaux, and Patnaikuni (2005) Kamen et al. (2007) Graybeal and Davis (2008) Yang et al. (2009) Mechanical Property Tested Type of Treatment Strengths Recorded Compressive strength of RPC Pressure and thermal curing Compressive strength 275 MPa Compressive strength of UHPC Hot water bath (HW), ovencured (OV), and pressure applied to fresh concrete Compressive strength – 240 MPa (OV with pressure of 80 MPa), 140 MPa (HW) None – various mixtures Compressive strength 155 MPa Compressive strength of UHPC Compressive and bending strength, and modulus of elasticity of UHPFRC Compressive strength of UHPFRC Compressive and flexural strength of UHPFRC Varying curing temperature Temperature and RH Cured in water, 20 and 90°C Yazıcı et al. (2009) Compressive strength of RPC Steam and autoclave curing Yazıcı et al. (2010) Compressive and flexural strength, and fracture energy of RPC Standard, autoclave, and steam curing, and pressure treatment Soliman and Nehdi (2011) Compressive strength of UHPC Wille et al. (2011) Compressive strength of UHPC Varying curing conditions – RH, and Temperature, and mixtures to mitigate shrinkage None – adjust the content of cement, silica fume and highrange water reducer to maximize its strength 30 Compressive strength 290 MPa Bending strength 2 MPa Modulus of elasticity 48 GPa 240 MPa Compressive strength 160-180 MPa Flexural strength 24 MPa Compressive strength – 234 and 250 MPa Compressive strength 403 MPa Flexural strength 33 MPa Fracture energy 7200 J/m2 Compressive strength 160 MPa Plain UHPC – 190 MPa UHPC with steel fiber – 200 MPa Table 2.2 (cont’d) Aydin and Baradan (2013) Compressive, flexural, and splitting tensile strength, modulus of elasticity, and fracture energy of RPC and alkali-activated cement (CRPC) Steam cured Hassan et al. (2012) Compressive, direct tensile strength and modulus of elasticity of UHPFRC None Magureanu et al. (2012) Compressive, flexural, and splitting tensile strength, and modulus of elasticity of UHPC Temperature and RH Prem et al. (2012) Compressive, flexural, and splitting tensile strength, and modulus of elasticity of UHPC Water and hot air curing Zdeb (2013) Compressive and flexural strength, and modulus of elasticity of UHPC Steam, and water curing, autoclave Graybeal (2014) Compressive, and direct tensile strength, and modulus of elasticity of UHPC Temperature and steam curing Voit and Kirnbauer (2014) Compressive, and splitting tensile strength and fracture energy of UHPC Pressure, and thermal 31 Compressive strength – 215 MPa, Flexural strength – RPC 42 MPa, ARPC 35 MPa Splitting tensile strength – 19 MPa Modulus of Elasticity – RPC 114 GPa, ARPC 84 GPa Fracture energy – RPC 14 kJ/m2, ARPC 16 kJ/m2 Compressive strength – 151 MPa Direct tensile strength – 9 MPa Modulus of Elasticity – 46 GPa Compressive strength – 180 MPa Flexural strength – 34 MPa Splitting tensile strength – 13 MPa Modulus of Elasticity – 52 GPa Compressive strength – 180 MPa Flexural strength – 44 MPa Splitting tensile strength – 24 MPa Modulus of Elasticity – 40 GPa Compressive strength – 315 MPa Flexural strength – 27 MPa Modulus of Elasticity – 50 GPa Compressive strength – 182 MPa Direct tensile strength – 9 MPa Splitting tensile strength – MPa Modulus of Elasticity – 53 GPa Compressive strength – 345 MPa, Splitting tensile strength – 24 MPa Fracture energy – 2500 J/m2 Table 2.2 (cont’d) Xiao et al. (2014) Compressive, and flexural strength of UHPC Steam cured at 90°C, and with special mixtures Gesoglu et al. (2015) Compressive strength of UHPFRC Ghafari et al. (2015) Compressive strength of UHPC Water or steam cured, with varying mixtures None – adjust the mixture contents to develop an ecoefficient UHPC while maximizing its strength Graybeal (2015) Kusumawardaningsih et al. (2015) Alkaysi (2016) Peng et al. (2016) Wang and Gao (2016) Zdeb (2017) Compressive strength of UHPC Tensile strength of UHPC and UHPFRC Compressive and direct tensile strength of UHPC Compressive strength, splitting tensile strength and fracture energy of UHPC (standard, and recycled steel fiber) Compressive and flexural strength of UHPC Compressive, and flexural strength of RPC Compressive strength UHPC 1.4% superplasticizer – 151 MPa UHPC high w/c – 100 MPa Flexural strength UHPC 4% steel fiber – 32 MPa UHPC 1% steel fiber – 16 MPa Compressive strength 150 MPa 170 MPa Steam curing 200 MPa Varying treatment UHPC 4 MPa, UHPFRC 7 MPa None – only utilized varying types of silica fume and powder, and cement Compressive strength 186 MPa Direct tensile strength 9 MPa None – only utilized varying types and content of steel fiber Steam curing at 90°C Steam and autoclave curing 32 Average – (1) compressive strength 141 MPa, (2) splitting tensile strength 9 MPa, and (3) fracture energy 5440 J/m2 Compressive strength 110-230 MPa Flexural Strength 20-45 MPa Compressive strength 200 MPa Flexural strength 19 MPa Table 2.3: Survey of UHPC/RPC and UHPFRC studies conducted at elevated temperatures Study/Investigation Hertz (1984) Study Objectives/Detail Explosive spalling of ultra high strength concretes Features and Methodology ▪ Observation of explosive spalling with high dense concretes ▪ Heating rate as low as 1ºC/min Felicetti et al. (2000) Mechanical properties of HPC and UHPC (hot and residual) are investigated ▪ Residual and hotstate direct tension, Young’s modulus and fracture energy ▪ 20-600°C, with a rate of (1) residual, 1ºC/min, and (2) hotstate, 2ºC/min Khoury (2000) Mechanical properties of HSC, UHPC are investigated at elevated temperatures ▪ Residual compressive strength ▪ 20-700°C, with rate of 2ºC/min 33 Observations/Conclusions ▪ At room temperature compressive strength 170 MPa ▪ Explosive spalling occurred with lower moisture content and rate of heating as compared to conventional concretes ▪ UHPC at room temperature compressive strength 160 MPa, tensile strength 10-11 MPa ▪ The hot-state and residual strengths are very similar ▪ At room temperature compressive strength 115-170 MPa Strengths/Drawbacks ▪ Explosive spalling is solely due to the low permeability, i.e. high density, achieved through addition of silica fume ▪ Further research will be conducted to better understand behavior ▪ The Young’s modulus is lower with respect to the hot-state tests ▪ The fracture energy of UHPC experiences a dramatic increase up to 250300°C ▪ The test method exhibits an important role ▪ Mechanical properties fire performance are dependent upon the design mix ▪ Be mindful of the ratio consisting of CaO/SiO2 Table 2.3 (cont’d) Behloul et al. (2002) Mechanical and thermal properties of UHPC (stressed hot-state and residual) are investigated at elevated temperatures ▪ Compressive, and direct tensile strengths, elastic modulus, thermal conductivity, specific heat, and coefficient of thermal expansion (CTE) ▪ 20-750°C, with rate of 2ºC/min Schrefler et al. (2002) Investigate the overall behavior of UHPC and conventional concretes at elevated temperatures with respect to developing a model ▪ Model encompasses the thermal, hydral and mechanical behavior ▪ 20-1000°C, with a rate of 2ºC/min 34 ▪ At room temperature compressive strength 140-200 MPa, and tensile strength 8-12 MPa, elastic modulus 45-50 GPa ▪ Thermal conductivity and specific heat steadily decline with increasing temperatures, however experience a sudden increase at 200°C ▪ CTE increases linearly up to ~550°C, then a sudden spike closer to 575 C, followed by a decline, and then an increase around 800°C ▪ UHPC at room temperature compressive strength 118 MPa (input data for model) ▪ Mechanical and chemical (microstructure) behavior inputted via experimental testing ▪ Residual compressive strength, and elastic modulus mechanical properties outperformed the hot-state values ▪ Hot-state direct tensile strengths produced slightly higher values than their residual counterparts ▪ Based off the formulation of UHPC, no spalling was observed ▪ Two examples are provided within the report to display the validity of said model Table 2.3 (cont’d) Hertz (2003) Explosive spalling limits of concrete at elevated temperatures ▪ Consolidation of information and recommendations pertaining to explosive spalling phenomenon based off author’s experience and knowledge ▪ Concrete will have a lesser chance of spalling if silica fume is not used, coupled with if the moisture content is 3-4% Heinz et al. (2004) Explosive spalling behavior of UHPC of varying content of steel and PP fibers, at elevated temperatures Mechanical properties of RPC are investigated and compared to with HPC and NSC ▪ Cylindrical specimens ▪ 20-1050°C, standardized ETK curve (DIN 4102-2) ▪ All specimens without PP fiber, exploded ▪ Residual compressive strength tests ▪ Thermogravimetric analysis ▪ Fire exposure (500°C) durations were altered (0-120 min, 30 min increments) ▪ RPC at room temperature compressive strength 75 MPa ▪ The RPC’s fire endurance is greater versus conventional concretes ▪ The RPC’s displayed a larger residual compressive strength Liu and Huang (2009) 35 ▪ Explosive spalling is correlated to 374 C, approximately the pertinent temperature of steam ▪ Explosive spalling can be alleviated via either thermal cracks, and/or PP fiber, if and only if there is no immediate external deterrent ▪ Steel (3.5%) and PP (0.66%) fiber by volume produce the best results for fire resistance ▪ RPC displays greater resistance when affected by increasing temperature ▪ RPC experienced explosive spalling at 790°C Table 2.3 (cont’d) Burke (2011) The compressive strength of UHPC is studied with varying PP fiber content ▪ Conducted compressive cylinder and cube specimen tests ▪ 20 to 600°C, with rate of 5ºC/min ▪ At room temperature compressive strength, (1) cylinder – 137-152 MPa, and (2) cube – 140-180 MPa ▪ PP fibers alleviated explosive spalling Ju et al. (2011) The thermophysical properties of RPC are evaluated at elevated temperatures ▪ Thermophysical properties, thermal conductivity, thermal diffusivity, specific heat capacity and linear thermal expansion with four varying steel fiber volume ▪ 20 to 250°C (in 50°C increments), with rate of 5ºC/min Tai et al. (2011) Study the compressive stress-strain relationship of RPC with varying steel fiber content at elevated temperatures ▪ Residual compressive strength, and stressstrain relationship ▪ 20-800°C, with rate of 2ºC/min ▪ Minimal mass loss at 250°C ▪ Only specific heat capacity increases with higher temperatures ▪ The steel fiber content effects the specific heat capacity and thermal diffusivity values ▪ RPC’s thermal conductivity, and specific heat capacity are lower than HSC ▪ The compressive strength increases slightly up to 300°C, soon followed by a decrease with increasing temperatures ▪ The peak strain increases with higher temperatures 36 ▪ UHPC’s residual compressive strength with respect to increasing temperature is like other concretes ▪ The exposure duration of the heat affected the cube specimens, but not the cylinder specimens ▪ Due to the differing microstructure, RPC’s thermophysical properties vary as compared to HSC ▪ RPC with 1% steel fiber content behave differently than with 2 and 3% steel fiber content ▪ The slope decreases of the stress-strain curve with increasing temperatures Table 2.3 (cont’d) Aydin and Baradan (2012) The mechanical properties of RPC with a Portland cement replacement at elevated temperatures is investigated ▪ Cement is replaced with alkali-activatedslag (ARPC), and results are compared with cement based RPC (CRPC) ▪ Residual flexural, compressive strength and toughness ▪ 20-800°C, with rate of 10°C/min Peng et al. (2012) The residual mechanical properties of RPC with varying content of steel and PP fibers and the explosive spalling behavior were studied ▪ Residual compressive, splitting tensile strength and fracture energy ▪ 20-600°C, with rate of 10°C/min 37 ▪ The CRPC strength changes very little up to 300°C and undergoes explosive spalling beyond 300°C ▪ The ARPC’s strength steadily decreases with decreasing temperature ▪ ARPC can withstand temperatures up to 800°C ▪ At room temperature compressive strength 70-100 MPa, splitting tensile strength 13-16 MPa, and fracture energy 12,000-15000 J/m2 ▪ The compressive strength increases up to 400°C, while the splitting tensile strength and fracture energy only up to 200°C ▪ CRPC’s increasing temperature resistance is greater than ARPC up to 300°C ▪ Beyond 300°C, ARPC is better ▪ ARPC with 20% silica fume did not experience explosive spalling ▪ The use of PP fiber is a method to avoid explosive spalling ▪ RPC with water-cement ratio from 0.16-0.20 has a higher chance to experience explosive spalling ▪ Increase of mechanical properties between 200400°C may be attributed to hydration of the cementitious materials, but further research is required Table 2.3 (cont’d) Study the compressive strength of UHPC with varying PP fiber, and with and without steel bar reinforcement at elevated temperatures Zheng et al. (2012) Study the compressive stress-strain relationship of RPC with varying steel fiber content at elevated temperatures ▪ Stressed at 30% of the ultimate strength, hot-state compressive strength ▪ 20-400°C ▪ Many cracks were observed with increasing temperature up to 300°C ▪ Specimen heated to 400°C experienced explosive spalling ▪ Adding PP fiber, 2 kg/m3, alleviated the cracks and spalling ▪ Residual compressive strength, stress-strain relationship and elastic modulus ▪ 20-900°C, with rate of 4ºC/min ▪ Specimens are heat treated ▪ Minimum compressive strength reached at 700°C ▪ Very little changes with respect to the stress strain relationship up to 300°C; following 300°C, the curves begin to flatten Abdul-Hussain (2013) ▪ Residual compressive, flexural and splitting tensile strength on cubes, cylinders and prisms ▪ 20-600°C, with slow heating rate ▪ The compressive strength increase with initial temperature increase, however begin to decrease soon after ▪ The peak strain increases with higher temperatures ▪ At room temperature (with increasing PP fiber content) compressive strength 97-122 MPa, flexural strength 6-23 MPa, and splitting tensile strength 5-15 MPa Ye et al. (2012) Various mechanical properties of fiber RPC, and explosive spalling were studied 38 ▪ All mechanical properties tested decrease at temperatures above 400°C ▪ Tensile strengths suffered the most following exposure of 600°C Table 2.3 (cont’d) Jagannathan (2013) To study and understand the CS-H in concrete at elevated temperatures Zheng et al. (2013) Various mechanical properties of steel fiber RPC were studied ▪ Utilizing experimental data, compare the C-S-H in UHPC versus conventional concretes ▪ Residual compressive and tensile strength tests ▪ 20-800°C, with rate of 5ºC/min 39 ▪ At the micro-level, the drastic difference in stiffness between the C-S-H phase and steel fiber, cause the packing density of the C-S-H to lessen, and capillary porosity within the matrix is formed ▪ The critical temperatures for explosive spalling are from 260-520°C, and the risk rises with larger dimensions ▪ The compressive strength decreases at 100°C, rises up to 500°C, and followed by a decline ▪ The tensile strength decreases at 200°C, rises only up to 300°C, and followed by a decline ▪ UHPC’s C-S-H phase is quite durable up to 400°C, and dramatically firmer than conventional concretes ▪ 2% steel fibers can prevent RPC to undergo explosive spalling ▪ Based off study implementation of codes for RPC design is conservative for temperatures between 400-800°C, and not recommended for temperatures under 400°C Table 2.3 (cont’d) Bashandy (2013) Various mechanical properties of fiber RPC, with varying cement and steel fiber content, and differing fire exposure times Hager et al. (2013) The compressive strength and modulus of elasticity of RPC are studied with varying PP fiber content ▪ Residual compressive (cube specimens of 100 x 100 x 100 mm) and splitting tensile strength (cylinder specimens of 200 mm length and 100 mm diameter) ▪ 20-500°C, with a rate of 10°C/min ▪ Heating durations of 2 and 4 hours ▪ Residual compressive strength tests on prism specimens 40 x 40 x 80 mm ▪ 20 to 1000°C, with rate of 0.5ºC/min ▪ Spalling tests to 600°C, with rates of 0.5, 1, 2, 4 and 8ºC/min ▪ 40 ▪ At room temperature compressive strength 85-150 MPa, splitting tensile strength 7-11 MPa ▪ ▪ Increasing the heating duration, decreases the residual strengths ▪ Increase in cement improves only the at room temperature strengths ▪ Steel fibers enhance the strengths only up to 150°C At room temperature compressive strength 180220 MPa, and elastic modulus 48 GPa ▪ 2.0 kg/m3 PP fibers prevented explosive spalling ▪ PP fibers do not drastically alter the relative compressive strength as a function of temperature ▪ Modulus of elasticity is not affected by the addition of PP fibers ▪ Porosity increases from 0.02 to 0.14 cm3/cm3, when temperature is heated to 600°C Table 2.3 (cont’d) Ju et al. (2013) Wang et al. (2013) In order to better understand the spalling behavior of RPC, the microstructure along with the pore pressure were studied at elevated temperatures The study investigated the thermomechanical (TMA) analysis of UHPC with varying dimensions and content of steel fiber ▪ Plain RPC specimens ▪ The pore ▪ 20-350°C characteristics ▪ Mercury intrusion increase with higher porosimetry (MIP), temperatures and scanning electron A model proposed to help microscopy (SEM) analyze the pore pressure were utilized and explosive spalling ▪ Explosive spalling is mainly attributed to the lack of pathways to allow release of vapor pressure ▪ Coefficient of thermal expansion (CTE), ▪ 20-800°C, with rate of ±3ºC/min ▪ Both UHPC types tested, (1) extended almost linearly up to 570°C, (2) severely contracted above 700°C, and (3) ▪ Copious amount of cracks exposed via SEM, in vicinity of phase interfaces due to thermal stresses caused by differences in CTE 41 ▪ α-β quartz transformation – 570°C, reversible phase transformation ▪ Dihydroxylation transition of C-S-H – above 700°C, irreversible phase transformation Table 2.3 (cont’d) Canbaz (2014) Investigate the compressive strength of pressurized and accelerated curing RPC with varying PP fiber content, at elevated temperature ▪ Residual compressive strength and UPV tests ▪ 20-900°C, with rate of 10°C/min Klingsch (2014) Investigate the explosive spalling behavior of UHPC at elevated temperatures ▪ Vary the silica fume content and employ different heating rates So et al. (2014) ▪ Residual compressive and flexural strength ▪ 20-1095 C, with rate of 30°C/min (KSF 2257-1, Korean standard) Mechanical properties and thermogravimetricdifferential thermal analysis (TG-DTA) of RPC with varying cement, silica fume and PP fiber at elevated temperatures 42 ▪ At room temperature compressive strength, 200 MPa (0% PP), and 165 MPa (1% PP) ▪ RPC with no PP fiber relatively well up to 400°C, however poor performance at high temperatures up to 900°C ▪ Addition of PP fiber improved the RPC’s performance up to high temperatures ▪ At room temperature compressive strength 150 MPa ▪ Hydrothermal model is presented, which is validated via experimental testing ▪ At room temperature compressive strength 106150 MPa, and flexural strength 17-27 MPa ▪ The relative residual compressive and flexural strength at 1095 C was between 0.15-0.29 and 0.20-0.33, respectively ▪ 1% of PP fibers is suggested to avoid explosive spalling and to maintain its strength at elevated temperatures up to 900°C ▪ RPC with no PP fiber was not able to withstand temperatures higher than 900°C ▪ Explosive spalling will occur if the pore pressure exceeds the concrete’s tensile strength ▪ Employing a low rate of heating can still contribute to explosive spalling, due to UHPC’s dense matrix ▪ RPC is more at risk of explosive spalling with (1) increasing cement content and silica fumecement ratio, (2) value of the pore-volume proportion, and (3) PP fiber content of at least 2.0 kg/m3 Table 2.3 (cont’d) Zheng et al. (2014a) Study the mechanical properties of RPC with steel and PP fiber at elevated temperatures and varying fire exposure durations ▪ Residual compressive and tensile strength ▪ 20-800°C, with rate of 5ºC/min 43 ▪ At room temperature compressive strength, 135-163 MPa, tensile strength, 5.5-7.5 MPa ▪ Compressive strength (PP and steel fiber) decrease at 100°C, and increases up to 500°C; followed by a decrease at 600°C and above ▪ Compressive strength increases up to 400°C with prolonged fire exposure ▪ Tensile strength (PP and steel fiber) decrease at 200°C, and increase at 300°C; followed by a decrease with higher temperatures ▪ The compressive and tensile strengths attain an initial increase, soon followed by a degradation of strength ▪ PP fibers provide avenues for the vapor pressure to release, and avoid explosive spalling Table 2.3 (cont’d) Zheng et al. (2014b) Various mechanical properties of fiber RPC, the microstructure and explosive spalling were studied Objective: ▪ Evaluate the effects of differing PP fiber content ▪ Measure porosity, thermal conductivity ▪ Compressive strength tests, 70 x 70 x 70 mm cubes and 70 x 70 x 220 mm prismatic specimens ▪ Tensile strength tests, dog-bone shaped ▪ 20 to 800°C, with rate of 5ºC/min 44 ▪ Room temperature compressive strength, (1) cube 107-137 MPa, and (2) 92-138 MPa, (3) tensile strength 4.5-5.75 MPa ▪ ▪ 2.73 kg/m3 PP fibers prevented explosive spalling ▪ Cube compressive strength performed the best ▪ Compressive and tensile strength fluctuated, decreased at 100 and 200°C, respectively, increased from 200 to 600°C, and 200 to 300°C, respectively, and decreased above 600°C, and 400°C, respectively ▪ Thermal conductivity sharply decreased up to 400°C, and slowly beyond 400°C Table 2.3 (cont’d) Ju et al. (2015) The residual mechanical properties and the spalling behavior of RPC were investigated Objective: To vary the PP fiber content (by volume) So et al. (2015) ▪ Study the mechanical properties of a more economical mixture of RPC at elevated temperatures ▪ Compressive strength, split tensile strength, and flexural strength (up to 350°C), with rate of 3ºC/min ▪ The spalling performance and details up to 600°C, with rate of 4.8ºC/min ▪ The contents of silica fume and cement are drastically reduced ▪ In return, developed a mixture that contains silica fume, blast furnace slag and fly ash ▪ Residual strength tests at 20-1000°C with a rate of 10°C/min 45 ▪ Room temperature compressive strength 135-160 MPa ▪ Thermomechanical properties increase up to 300°C, and decrease following 300°C ▪ 0.9% PP fiber is critical dosage for ideal residual strengths ▪ Mass loss variation with respect to temperature range ▪ At 280-290°C, moisture begins to migrate towards the outside ▪ Room temperature compressive strength 140-190 MPa, tensile strength 15-22 MPa, and flexural strength 35-42 MPa ▪ Modified RPC residual compressive, flexural, and splitting tensile strengths were 36%, 22%, and 29% of the ambient strength, following exposure to 1000°C ▪ 0.9% PP fiber dosage is optimum for residual mechanical properties ▪ Above 150°C, mass loss (evaporation of water) increases very rapidly ▪ Moisture migration occurs around 280-290°C ▪ The modified RPC outperformed the more traditional RPC mixture ▪ 30% fly ash, 10% blast furnace slag, and with the lowest silica fume content proved to be the best combination ▪ Substantial strength loss experienced from 400800°C Table 2.3 (cont’d) Way and Wille (2015) Xiong and Liew (2015) ▪ Investigate the effect of chemical degradation (DSC/TGA) of the mechanical properties of UHPFRC ▪ Residual compressive strength and stressstrain relationship ▪ 20-900°C with a rate of 0.1ºC/min ▪ At room temperature 206-233 MPa (with thermal treatment ▪ Oven drying the specimens provided an increase in compressive strength and elastic modulus over the control (90°C) Investigate mechanical properties of UHPC with varying fiber type, dosage, heating rate and curing condition at elevated temperatures ▪ Residual compressive strength and elastic modulus ▪ 20-800°C, with rates of 5 and 30°C/min ▪ At room compressive strength 160-185 MPa ▪ Steel fibers are not effective to avoid explosive spalling ▪ Compressive strength experiences an increase at 200°C – attributed to water removal; not seen with elastic modulus 46 ▪ UHPFRC experienced a rise in strength at 135 and 200°C, followed by a decrease ▪ The elastic modulus decreased following 300°C and above ▪ The peak strain increased with increasing temperature ▪ The thermomechanical analysis provided reasoning to decrease in strength at respective temperatures ▪ PP fiber with dosages of 0.1% is effective to avoid explosive spalling ▪ The compressive strength and elastic modulus reduce more rapidly with higher heating rates ▪ Curing conditions do not effect the compressive strength and elastic modulus Table 2.3 (cont’d) Zheng et al. (2015) Mechanical properties at hotstate of RPC with steel fiber at elevated temperatures ▪ Hot-state compressive strength, stress-strain relationship, elastic modulus and energy absorption ▪ 20-800°C, with rate of 5ºC/min Ali et al. (2016) Investigate the use of waste glass powder to enhance the mechanical properties at elevated temperature of HSC and compare to RPC ▪ Residual compressive, and flexural strengths, modulus of elasticity and stress strain relationship ▪ 20-800°C with rate of 13ºC/min Bei and Zhixiang (2016) Investigate the explosive spalling behavior of UHPC (with varying fiber mix and content) at elevated temperatures ▪ Place UHPC specimen in a preheated furnace (1000°C) for a short duration, followed by sudden exposure to a 25 C environment 47 ▪ At room temperature compressive strength 142-165 MPa ▪ With increasing temperatures, (1) the thermal expansion, peak strain, and energy absorption (up to 400°C) escalate, (2) compressive strength, and Gismodine progressively decreases ▪ RPC (HSC with waste glass powder, no silica fume, HSC-GP) at room temperature compressive strength 142 MPa (81 MPa), modulus of elasticity 52.8 GPa (40.4 GPa) and flexural strength 6.7 MPa (5.9 MPa) ▪ At room temperature, compressive strength 168-198 MPa ▪ Steel fiber merely postpones the time to spall ▪ Increasing the steel fiber content will not improve the compressive strength, however will intensity the ductility ▪ Following temperatures up to 800C C-S-H decomposes (pores and cracks appear), and C2S and C3S formulate ▪ The mechanical properties dilapidation is due to the pores and microcracks ▪ RPC experiences a sudden decline in compressive and flexural strengths with increasing temperature, while HSC-GP experiences a steady decline ▪ RPC (HSC-GP) experienced partial spalling at 400°C (500°C) and full spalling at and above 500°C (800°C) ▪ PP fiber content greater than 0.20%, and length of 12 and 19 mm prevent explosive spalling Table 2.3 (cont’d) Li and Liu (2016) Investigates the tensile properties of RPC with steel and PP fibers at elevated temperatures ▪ Residual flexural and direct tensile strength ▪ 20-900°C, with rate of 4ºC/min Jang et al., 2016 The residual mechanical properties and the spalling behavior of RPC were investigated ▪ Compressive, flexural and splitting tensile strength ▪ 20 to 1000°C, with a rate of 10°C/min ▪ Thermogravimetric and microstructure analysis Objective: ▪ To vary the fiber content (by volume) ▪ Alter the admixture with a combination of ternary pozzolanic materials 48 ▪ At room temperature, flexural strength 22-31 MPa, and direct tensile strength is between 68 MPa ▪ The flexural and direct tensile strength experience a steady decline with increasing temperature ▪ Room temperature compressive strength 150 MPa, and flexural strength 25-32 MPa, ▪ Modified RPC contained only 765 kg/m3 of cement, and an increase in compressive and flexural strength as a function of temperature ▪ Compressive strength increased up to 400°C, and then decreased ▪ Flexural strength increased up to 200°C, and then decreased ▪ Only the steel fibers can increase the tensile strength and the tensile strength increases with higher steel fiber content ▪ A decrease in table flow as the fiber content was increased ▪ PP fiber is effective to inhibit explosive spalling, so long as the volume is 0.2% of the binder content ▪ Table 2.3 (cont’d) Peng et al. (2016) Study the explosive spalling behavior and ambient condition mechanical properties of UHPC with varying types of steel fiber at elevated temperature ▪ Utilize standard steel fiber and sustainable (recycled) steel fiber to reinforce UHPC ▪ 20-800°C, rate of 10°C/min (for explosive spalling tests only) Sanchayan and Foster (2016) The residual and hot state mechanical properties and the spalling behavior of RPC (6 different mixes) were investigated ▪ Residual compressive strength, and elastic modulus, with a rate of 5ºC/min ▪ Hot state elastic modulus, free thermal strain and transitional thermal creep, with a rate of 5ºC/min Objective: If PVA fibers would alleviate the explosive spalling behavior 49 ▪ At room temperature compressive strength 130-154 MPa, splitting tensile strength 7-12 MPa, and fracture energy 260-13,828 J/m2 ▪ The recycled steel fiber compressive strength ranged from the lowest to about the average of compressive strengths ▪ While the splitting tensile strength, and the fracture energy of the recycled steel fiber proved to be the most favorable ▪ Room temperature compressive strength 134-170 MPa ▪ Utilizing PVA fibers alone reduced the compressive strength, elastic modulus remained constant ▪ Elastic modulus and ultrasonic pulse velocity drop following exposure to 300°C ▪ Transitional thermal creep very high above 250°C ▪ Surfeit amount of mass loss for tests conducted to 300, and 400°C ▪ The steel fiber with the least diameter proved to be the most effective to avoid explosive spalling ▪ Additionally, the recycled steel fiber UHPC provided explosive spalling relief as well ▪ 1% of steel and PVA fibers design mix provided the best results ▪ Increase of compressive strength up to 300°C, followed by a drop ▪ Hot state elastic modulus of RPC 1% steel and PVA fibers decreased almost linearly Table 2.3 (cont’d) Nazri et al. (2017) The residual mechanical properties and the spalling behavior of UHPFRC were investigated ▪ Residual compressive strength on cube specimens of 40 x 40 x 50 mm ▪ 20-600°C with a rate of 15ºC/min 50 ▪ At room temperature compressive strength 157-161 MPa ▪ UHPFRC experienced explosive spalling at temperatures above 400°C ▪ Did not contain any PP fiber ▪ Due to undergoing explosive spalling only conducted compressive strength up to 200°C with very little reduction in strength ▪ Fire Propagation Index of 0.0, under BS476 Part 6, Class 1 fire rating under Part 7 Figure 2.1: Relative compressive strength versus temperature as per literature from the past 3 years (a) Relative direct tensile strength Figure 2.2 Relative tensile strength versus temperature as per literature 51 Figure 2.2 (cont’d) (b) Relative splitting tensile strength (c) Relative flexural strength 52 Figure 2.3 Relative elastic modulus versus temperature as per literature from the past 2 years 53 CHAPTER THREE 3. EXPERIMENTAL STUDIES ON COMPRESSIVE STRENGTH AND EXPLOSIVE SPALLING OF UHPC AT ELEVATED TEMPERATURES 3.1 General Data pertaining to the mechanical properties of UHPC at elevated temperatures are needed to evaluate concrete structural members’ fire response. Thus, grasping the degradation of compressive strength, stress-strain relationship, and elastic modulus with increasing temperatures, enable designers to achieve the fire resistance requirements dictated by code provisions. As presented in the previous chapter, it is apparent data on high temperature mechanical properties and temperature induced explosive spalling behavior of UHPC are lacking. To fulfill this integral gap, a comprehensive experimental study was undertaken to investigate UHPC’s compressive strength, stress-strain relationship, and elastic modulus with increasing temperatures. From the collected data, an empirical relation was formulated showing the variation of the 3 mechanical properties of UHPC with respect to temperature (20-700ºC), and highlights pertaining to explosive spalling. The following sections will impart the experimental design and details, procedures followed, and the findings will be discussed. 3.2 Design of mechanical property experiments The experimental study evaluated the unstressed mechanical properties of 3 different design mixes of UHPC. Each UHPC design mix incorporated a varying mixture of fiber(s), to investigate their influence on the respective mechanical properties, and effect of mitigating the explosive spalling occurrence. Specifically, two mixes of UHPC with varying content of steel fibers and one UHPC mix with a combination of steel and polypropylene fibers (hybrid) were 54 tested. The cylinders were tested under compressive loads at various temperatures (20, 100, 200, 300, 400, 600 and 700°C) in a elevated temperature state as opposed to testing under conventional residual-state regime. For comparative purposes, in addition to the UHPC 4 other conventional types of concretes, NSC, NSC with steel fiber (NSC-SF), HSC, and HSC with polypropylene fibers (HSC-PP) were also tested (at similar temperature ranges). Additionally, in the absence of an ASTM standard dictating guidelines for material properties at elevated temperatures, to regulate the testing procedure a combination of published standards was followed. The mechanical property tests were carried out as outlined in each respective ASTM standard, coupled with the heating regiment delineated in RILEM Standard (RILEM Technical Committee 200-HTC, 2007) were applied. 3.3 Mechanical properties tests The mechanical properties investigated as part of this study were compressive strength, stress-strain relationship, and elastic modulus. Table 3.1 displays the type and number of tests conducted for each respective type of concrete. 3.3.1 Batch mix proportions Four batches of UHPC were cast to prepare needed test specimens for evaluating the mechanical properties. Batch mix proportions for the UHPC mixes have been developed by Metna Co. Furthermore, 4 conventional concrete design mixes were cast as well, NSC, NSC-SF, HSC, and HSC-PP. All concrete types evaluated contained Portland cement, Type I, but with varying quantities. The conventional concrete mixes incorporated 9.5-millimeter (mm) limestone-coarse aggregate, and natural sand. The HSC mixes contained nearly 2.5 times the cement as the NSC mixes, and silica fume. All 3 UHPC design mixes contained 2.38 mm limestone-coarse aggregate, silica and natural sand, over 5 times the silica fume as compared to the HSC mixes, limestone 55 powder, and a superplasticizer, Chryso. The two UHPC design mixes with steel fibers are UHPC A, B, and D. UHPC A and B (A & B) are the same mixture proportions, however due to logistical constraints at the time of casting, two concrete batches were made. UHPC D has the same components but in lesser quantity, as compared to UHPC A & B. Namely, there is less steel fiber content in UHPC D, vice UHPC A & B. UHPC F is the hybrid design mix with steel and polypropylene fibers, and the other components are very similar as to design mix UHPC D. Furthermore, UHPC D and F were casted in Metna Co. laboratory, and therefore in a more controlled environment. The mix proportions in each type of UHPC design mix, and conventional concretes tested are given in Table 3.2, and Table 3.3, respectively. Additionally, the conventional concretes 28-day compressive strength range from 29-110 MPa, while UHPC’s from 132-182 MPa. The 28-day compressive strengths, along with the densities of all concretes tested, are provided in Table 3.4. 3.3.2 Test specimens The test specimens comprised of 75 mm in diameter by 150 mm in length cylinders as shown in Figure 3.1 and were cast using paper molds. Paper molds were used for casting UHPC cylinders to facilitate the placement of type K thermocouples in the cylinder for temperature measurement. Prior to casting, each paper mold is drilled from the side at mid-height and thermocouples are inserted from the side exactly at the center (75 mm from the side) of the cylinder. However, center thermocouples were not employed with the conventional concretes, thereby allowing the use of reusable plastic molds. When each respective concrete mixture was ready, the molds were filled with concrete and placed on a shaking table at high frequency for about 2 min. 56 The casted specimens are covered with plastic sheets to minimize moisture loss and left to set slowly for 24 hours. After 24 hours, the hardened UHPC specimens are demolded and immediately placed in a steam chamber for curing at 90°C for 48 hours. After steam curing, the specimens are air dried in Michigan State University Civil Infrastructure Laboratory (MSU CIL) for at least 90 days before conducting high-temperature tests. Since the cylinder’s top and bottom surfaces are originally rough from casting, a table saw (Figure 3.2) is utilized to create a smooth and leveled finish on both end surfaces (Figure 3.1). This smooth finished surface was performed for high-temperature testing since the available capping material melt at low temperatures of less than 127ºC. However, if an excellent level finish is not attained using the electrical saw, the results for compressive strength will not be accurate and this can be observed from the failure mode of the specimen as described in ASTM-C39/C39M (ASTM C39/C39M, 2016). The smooth leveled surface is achieved through slowly cutting the specimen, and repeatedly smoothing the surface until it achieves a leveled finish. The finished surface is finally checked utilizing a magnetic level. For each heated UHPC specimen in the furnace, three thermocouples are utilized to monitor temperature rise. Figure 3.1(a) depicts the thermocouple locations when the specimen is placed within the electrical furnace. Thermocouple (1) monitors the furnace temperature, nearest to the specimen, (2) the specimen’s surface temperature and (3) specimen’s core temperature. In addition, the electrical furnace has its own temperature gauges which are compared with the thermocouple readings. Contrary to UHPC specimens, the four conventional concretes did not have a center thermocouple, and the surface thermocouple is utilized to monitor the temperature rise. The arrangement of thermocouples for the conventional concretes is shown in Figure 3.1(b). 57 3.3.3 Test apparatus The test apparatus for compressive strength tests at various temperatures is composed of an electrical furnace to heat the specimens to the target temperature, loading machine to conduct the compressive strength test, and compressometer equipped with two high accuracy linear variable displacement transducers (LVDT), to track the deformations. The electric furnace shown in Figure 3.3 is specially designed for simulating high-temperature conditions and can produce maximum temperatures up to 925°C. It is equipped with internal heating electric elements, a ramp and a hold temperature controller that can generate different heating rates. Along with attaining the compressive strength, the 1800 kN load-controlled strength testing machine shown in Figure 3.4, combined with the compressometer shown in Figure 3.5, provide the stress-rate controlled stress-strain relationship by monitoring the load and deformation with respect to time. The elastic modulus can be extracted from the stress-strain relation utilizing equation 1, as prescribed in ASTM-C469/C469M (ASTM C469/C469M, 2014). 𝐸 = (𝑆2 − 𝑆1 )/(𝜀2 − 0.000050) (1) Where E, is the chord modulus of elasticity (GPa), S1, is the stress corresponding to a longitudinal strain, S2, is the stress corresponding to 40% of ultimate load (MPa), 𝜀1 , of 50 millionths, (MPa), and 𝜀2 , is the longitudinal strain produced by stress, S2, (mm/mm). The LVDTs are part of the compressometer, thus providing more local and accurate deformation measurements. 3.3.4 Test procedure 3.3.4.1 General procedure The specimen was evaluated at the elevated target temperature, and the applied load commenced following the heating of the specimen to the appropriate temperature. RILEM 58 standard considers such a procedure as an unstressed test. Furthermore, a steady-state method is adopted for determining the compressive strength utilizing the electric furnace (Figure 3.3). In the steady-state testing method, the specimen is heated to a predetermined target temperature, and then the specimen is immediately transferred to the strength testing machine for applying stress. Figure 3.6(a) depicts the desired regime of heating in this kind of test and Figure 3.6(b) summarizes the desired rate of heating for each type of concrete evaluated. The RILEM standard recommends a heating rate of 2ºC/min for specimens with a maximum diameter of 80 mm and a temperature recording interval of 4 min. For the testing conducted, a rate of heating of 2ºC/min was utilized for the four conventional types of concretes. Unfortunately, due to UHPC’s lower permeability as compared to conventional concretes, unless a lower heating regime was employed, tests at and above 300°C would result in explosive spalling. The spalling of this nature reduces the UHPC specimens into fragments and a compressive strength test cannot be conducted. Therefore, to improve the understanding of the explosive spalling behavior of UHPC, a heating rate ranging from 0.25 to 4ºC/min were employed. For all tests conducted, temperature recordings were taken every thirty seconds. Furthermore, due to the constraints of the electric furnace (Figure 3.3), coupled with the installation of the compressometer (Figure 3.5), the core temperature is taken 30°C beyond the target temperature. As seen in Figure 3.6(a), the increased temperature facilitates the additional time required to install the compressometer. Plus, as recommended by RILEM standard the additional 30°C permits the specimen to saturate for 30-45 min before removal from the furnace. Since the surface thermocouple is utilized to track the heating rate for the conventional concretes, the specimen is ready once the surface temperature reaches 60°C beyond the target temperature. The thermocouples are attached to a data acquisition device (Figure 3.7) that continuously monitor and records the temperature. 59 3.3.4.2 Compressive strength, stress-strain relationship, and elastic modulus Once concrete specimen attains the targeted temperature, it is removed from the furnace, Figure 3.6(b), and while the center thermocouple remains intact (UHPC specimens only), the surface thermocouple is removed prior to weighing the specimen. However, since the conventional concretes do not have a center thermocouple, the surface thermocouple remains in place to monitor the temperature while conducting the strength test. Preceding to place the specimen within the Forney strength machine (Figure 3.4), the compressometer (Figure 3.5) is installed upon the cylinder. As seen in Figure 3.5, there are two rods that hold the apparatus together, and once the compressometer is installed upon the concrete specimen, the rods are removed prior to commencing the compressive strength test. Tests conducted at 20ºC follow the steps outlined in this section, excluding the placement of thermocouples and heating within the furnace. When the specimen is set up within the Forney strength test machine, as per ASTM C39/C39M, a load rate of 0.25 ± 0.05 MPa/sec is applied and must be maintained for the duration of the test. Once the concrete specimen reaches its maximum load and depending on the temperature at which the test is being conducted and type of concrete, the specimen may fail in an explosive and brittle way, thus the test is concluded. Upon hearing the explosion, the test of specimens with steel fiber is continued briefly to ensure the specimen has in fact completely failed; Further discussion will be provided in section 3.4.2. The maximum load along with the load versus displacement data collected is used to develop the stress versus strain curves, along with the modulus of elasticity. Unless there was a poor failure as per ASTM-C39/C39M (ASTM C39/C39M, 2016), one conventional concrete specimen was evaluated at each respective temperature. While 3-4 repetition tests were conducted for UHPC A & B, and F up to 400°C, unfortunately, due to limited specimens cast and explosive spalling, only 1 specimen was tested for UHPC F above 400°C and 60 UHPC D. UHPC A & B and D’s compressive strengths were evaluated at 20, 100, 200, 300, and 400ºC, but for UHPC F, tests were conducted similarly as UHPC A & B and D, plus at 600 and 700°C. NSC tests were at 20, 400, 600, 700, and 750 ºC, NSC-SF at 20, 200, 400, 600, and 700ºC, HSC at 20. 200, 400, and 600ºC, and HSC-PP at 20, 200, 400, 600, 700, and 750ºC. 3.4 Results and discussion Results from the compressive strength tests are presented in this section. This section will discuss each type of concrete’s results individually. Chapter four will discuss the UHPC results as compared to the conventional concretes tested. 3.4.1 Sectional temperatures As illustrated in Figure 3.1, thermocouples are mounted in the electrical furnace and on the cylinders to record the temperature data with respect to time. The thermocouples ensured the appropriate rate of heat is being applied to the specimen while it is in the electric furnace and the proper temperature is reached. The temperature data acquisition device (Figure 3.7) records the temperatures via the thermocouples every 30 seconds. Following the completion of the test, the data is analyzed and the actual average rate of heat is calculated by plotting the temperature versus time (Figures 3.8), and enumerating the average slope developed during the heating of the concrete specimen. In each respective figure, the targeted rate of heat is shown via a dashed dark grey line as annotated by the legend. Additionally, the temperature versus time data, depicts the thermal gradients experienced by the UHPC specimen while being heated within the electric furnace. The thermal gradient is calculated utilizing equation (2). 𝑡ℎ𝑒𝑟𝑚𝑎𝑙 𝑔𝑟𝑎𝑑𝑖𝑒𝑛𝑡 = 61 𝑇𝑠 −𝑇𝑐 𝑟𝑠𝑝𝑒𝑐 (2) Where, 𝑇𝑠 , is the surface temperature (C), 𝑇𝑐 , is the center temperature (C), and 𝑟𝑠𝑝𝑒𝑐 , is the radius of the concrete cylinder, i.e. distance from the surface to the placement of the center thermocouple within the specimen (centimeter, cm). Therefore, employing equation (2) with the temperature rise data with respect to time, the thermal gradient is graphed with respect to time as well. The thermal gradient data is pertinent regarding UHPC’s explosive spalling behavior and will be discussed further in section 3.4.3.2. The desired heating rate utilized for the conventional concretes tests was 2ºC/min and to avoid explosive spalling, the rate of heat for UHPC testing depended upon the target temperature, Figure 3.6(b). Tests conducted at temperatures of 300ºC and above employed a heating rate of 0.50°C/min, while the remaining UHPC tests employed the same heating rate as the conventional concretes. Figure 3.8 illustrates the rise in temperature to 600°C for each type of concrete. Due to concrete’s low thermal conductivity and high specific heat, as expected the surface temperatures increase more rapidly as compared to the temperature within the core of the cylinder (Figure 3.8). Although the equipment is tested prior to each test, at times during a test, a thermocouple would begin providing erroneous data. While each thermocouple is essential, the surface and center thermocouples, Figure 3.1(a), are more critical for they provide vital data with respect to explosive spalling. If the surface thermocouple was reporting erroneous values, the average between the furnace, and center thermocouples was taken to be the surface values. Additionally, if the center thermocouple experienced damage, the recorded surface temperatures were utilized for the average rate of heat and the thermal gradient was not calculated. Furthermore, in case a similar test was performed previously, i.e. same UHPC type, and furnace input, the respective value from the preceding test were utilized. Table A1, A2, and A3 in Appendix A will provide further details associated with each UHPC design mix test. 62 The conventional concretes (Figure 3.8(a) and (b)) temperature rise to 600°C is very similar. However, due to the lower thermal conductivity of UHPC, as compared to the conventional concretes, the time required to reach 600°C is over three times greater. There was a smaller learning curve with the conventional concretes as opposed to UHPC, to calibrate the furnace to provide the desired rate of heating. Therefore, the same average rate of heat were not utilized for the conventional concretes depicted in Figure 3.8. However, regarding the tests conducted at the other temperatures, NSC-SF and HSC both required greater time to reach their target temperatures as opposed to NSC and HSC-PP, respectively. The additional time for NSCSF is due to the steel fibers and the lack of polypropylene fibers for HSC. Regarding Figure 3.8(c) the desired rate of heating to allow UHPC F9 to reach 600°C was 0.5ºC/min and as seen in the figure it took over 17 hours to do so. Furthermore, similar to HSC, the design mixes of UHPC containing no polypropylene fibers required a greater time versus design mix UHPC F. Moreover, due to explosive spalling, temperatures above 400°C were not attainable for UHPC A & B and D. Finally, as seen in Figure 3.8(c) no visible moisture induced plateau was seen in any UHPC F temperature versus time curve (Klingsch, 2014; Ju et al., 2015). The rate of heating for UHPC will be discussed in detail in section 3.4.3. 3.4.2 Compressive strength, elastic modulus, and stress-strain relationship The compressive strength, and modulus of elasticity with respect to temperature are presented in Figures 3.9 and 3.10, accordingly. All the tests were load-controlled and stopped as soon as the specimen experienced failure. The stress-strain relationship will be presented in the following subsequent sections for each respective type of concrete, along with the discussion of all three mechanical properties. Details pertaining to each UHPC test are given in Tables 3.5, 3.6 and 3.7; While the conventional concretes respective data are in Table 3.8 and 3.9. Chapter Four 63 will compare and discuss the 3 UHPC design mixes, with the 4 conventional concretes and ASCE (1992) and Eurocode 2 (2004). 3.4.2.1 NSC Figure 3.11 and 3.13 provide the stress-strain relationship for NSC and NSC-SF, respectively. Additionally Figure 3.12 and 3.14 display the type of failure modes for NSC and NSC-SF, following the compressive strength tests. Both types of concretes were evaluated from 20-750°C and the ambient temperature tests for both NSC and NSC-SF were conducted utilizing rubber caps. Due to the limited capability of the electrical furnace (Figure 3.3), 800°C tests could not be conducted. The maximum temperature attained were 750 and 700°C for NSC and NSC-SF, respectively. The NSC-SF specimens’ slightly lower temperature is attributed to the steel fiber content and the higher specific heat of the concrete at temperatures above 400°C (Kodur and Khaliq, 2011). The compressive strength tests conducted up to 400°C resulted in a thunderous explosion. However, the tests conducted at, and above 600°C did not produce any sound upon failure. The concrete’s hue (Figure 3.12 and 3.14) begins to change following exposure to 600°C, and above. The compressive strength (Figure 3.9) of NSC and NSC-SF reduces to about 50% at 600°C. Such a decrease may be attributed to the severance of calcium-hydroxide between 400 and 600°C (Schrefler et al., 2002; Klingsch, 2014). Furthermore, the relative compressive strength of NSC at 750°C drastically decreases below 25%. The calcium-carbonate decarbonating at temperatures greater than 700°C may be the cause of the sudden loss of strength. Moreover, due to the electrical furnaces’ capability, in an attempt to reach 800°C, the reduction may have been exacerbated further due to the prolonged exposure to the heat. Overall, up to 700°C, NSC’s compressive strength (Figure 3.9) degradation is much smoother as compared to NSC-SF. Although the NSC64 SF test conducted at 200°C suffered a diagonal fracture (Figure 3.14), it resulted in a lower compressive strength than the 400°C test. For the most part NSC and NSC-SF behave very similarly with respect to their stress-strain relationship (Figure 14, and 16). At ambient conditions, NSC-SF displayed 33% more ductility than NSC and with increasing temperatures NSC-SF remained more ductile. Although, steel fibers are predominantly utilized for tensile strength purposes, the additional ductility during the stressstrain curve is attributed to the fibers as well. As the specimens were exposed to elevated temperatures, the peak strain increased due to softening of the material. The elastic modulus for both, NSC, and NSC-SF regress faster as compared to their compressive strengths. NSC elastic modulus reaches down to 26% at 400°C, and NSC-SF even further to 16% as compared to their respective ambient condition stiffness. The decaying of the cement paste most likely caused the rapid stiffness decline (Kalifa et al., 2000). The addition of steel fiber to the concrete did not contribute towards its stiffness. 3.4.2.2 HSC Figure 3.15 and 3.17 provide the stress-strain relationship for HSC and HSC-PP, respectively. Additionally Figure 3.16 and 3.18 display the type of failure modes for HSC and HSC-PP, following the compressive strength tests. HSC was evaluated from 20-600°C, and HSCPP up to 750°C, and the ambient temperature tests for both HSC and HSC-PP were conducted utilizing rubber caps. Due to the limited capability of the electrical furnace (Figure 3.3), 800°C test for HSC-PP could not be conducted. The compressive strength tests sound upon failure for HSC and HSC-PP is equivalent to NSC and NSC-SF, and the concrete’s hue (Figure 3.16 and 3.18) begins to change following exposure to 400°C, and above. 65 Due to the denser microstructure achieved through the addition of silica fume and high content of cement, coupled with the reduction in w/c ratio, the compressive strength’s (Figure 3.9) reduction is much more drastic. The HSC and HSC-PP design mixes tested, employ over two times the amount of cement as compared to the NSC and NSC-SF. Therefore, at temperatures between 100-300°C, the decomposition of the hydration products of cement contribute greatly to the strength loss (Dehn, 2004; Klingsch, 2014). As seen in Figure 3.9, at 400°C the compressive strength is reduced to a third of its original strength. However, HSC and HSC-PP maintain around 30% of their original strength at 600°C. The minimal strength loss is attributed to the reduction of calcium-hydroxide formation accomplished with the addition of silica fume. Though it is only 7% of the cement, it is enough to relatively maintain its strength (Khoury, 2000; Zdeb, 2013). The decreasing strength of HSC-PP beyond 600°C is owed to the analogous factors that influenced NSC’s strength. Beyond 200°C, HSC-PP (Figure 3.17) displayed greater ductility as opposed to HSC (Figure 3.15), and excluding the HSC test at 600°C, the peak strain increased with elevated temperatures due to softening of the material. The HSC at 20°C and HSC-PP at 200°C, were repeated due to erroneous results and poor compressive failure mode of the cylinder. Furthermore, below temperatures of 600°C, the addition of polypropylene fibers improved the stiffness. While, HSC’s stiffness degraded below 50% at 200°C, it wasn’t until 400°C for HSC-PP. Finally, at 600°C, both concretes stiffness degraded to about 15% of its original elastic modulus. Therefore, the addition of polypropylene fibers with HSC assists its ductility and stiffness with increasing temperatures. 66 3.4.2.3 UHPC Figure 3.19, 3.21 and 3.23 provide the stress-strain relationship for design mixes UHPC A & B, D, and F, respectively. Additionally Figure 3.20, 3.22 and 3.24 display the type of failure modes for each UHPC design mix, following the compressive strength tests. Due to UHPC A & B and D undergoing explosive spalling, both design mixes’ mechanical properties were only evaluated up to 400°C; while the addition of polypropylene fibers granted UHPC F to be tested up to 700°C. Moreover, due to explosive spalling and limited resources, only design mixes UHPC A & B and F allowed repetition of tests (3-4), conducted at temperatures of 20-400°C and tests at and beyond 300°C could only be performed utilizing an heating rate of less than 1ºC/min. The data provided for the remaining UHPC tests, consisted of a singular test. There are 4 UHPC A & B tests in Table 3.5, conducted at 20, 100, 200 and 200°C, that did not adhere to the method according to ASTM-C469/C469M, but followed ASTM-C39/C39M. Therefore only their respective compressive strengths were attained, and their corresponding data is incorporated in Figure 3.9. The compressive strength tests sound upon failure and the concrete’s hue (Figure 3.20, 3.22 and 3.24) are similar to the design mixes of HSC. The ambient temperature data collected for UHPC A & B and F were conducted utilizing caps and with no cap. Unfortunately, due to the limited number of specimens of design mix UHPC D, no 20°C test could be conducted utilizing a cap. The cap removes any imperfections upon the horizontal surfaces and provides a higher value. Therefore, though UHPC D’s 28-day compressive strength is 10% greater than UHPC F, from Figure 3.9 UHPC D and F have the same compressive strength at ambient conditions. All the UHPC design mixes tested experienced a decrease in strength at 100°C, with UHPC A & B experiencing the greatest reduction of 18%. The degradation of strength is attributed to the 67 evaporation of the non-chemically bound water within the UHPC, causing increased permeability and loss of strength (Dehn, 2004; Klingsch, 2014). However, following exposure of 200°C, UHPC F was the only design mix that did not increase in strength. The increase in strength is owed to shrinkage of the concrete following the water evaporation (Xiong and Liew, 2015). UHPC F did not experience an intensification until 300°C. The delayed response of the surge of strength may be caused by the melting of polypropylene fibers around 150-170°C and further increasing the permeability (Klingsch and Frangi, 2011; Bei and Zhixiang, 2016). At 300 and 400°C, UHPC D and F maintain strengths close to their respective original strength, with UHPC D achieving strengths greater than the original at 110 and 104% at 300 and 400°C, respectively, while UHPC design mix A & B deviate from the group beyond 200°C. The nonconformity seems to be caused by either the specimen was not properly prepared, resulting in a poor break, or higher heating rates deteriorated the strength. The former was the cause for one test and the latter for the remaining four. The greatest compressive strengths attained for UHPC A & B at 300 and 400°C employed heating rates that were on average 30% lower than the lower compressive strengths, with on average 16% greater duration of heating. Moreover, the supreme strength attained from all UHPC design mixes, was by UHPC D8 tested at 300°C with an average heating rate of 0.25ºC/min and total heat exposure duration of 18 hours. Although nearly reducing the average rate of heating to 50%, UHPC F sustained a 16% increase in compressive strength at 200°C, dramatically increasing the duration in the furnace and employing extremely slow heating rates, at 300 and 400°C negatively effects UHPC design mix F. When employing a heating rate like UHPC D8 (0.25ºC/min), on average the duration within the furnace was increased and strength decreased, 2.5 times and 8%, accordingly. 68 UHPC F9 decays to 70% of its original strength at 600°C and experiences a drastic deterioration at 700°C (UHPC F13). The inordinate amount of silica fume as compared to the cement content in UHPC F provides a very low C/S ratio, thus resulting in minimal calciumhydroxide (Khoury, 2000; Zdeb, 2013). Therefore, the sudden decrease experienced by UHPC F9 and F13, is dominated by the α-quartz to β-quartz transformation occurring around 570°C coupled with the continual dilapidation of the cement paste (Dehn, 2004; Klingsch, 2014). At ambient conditions (Figure 3.19, 3.21 and 3.23), save the maximum compressive strengths attained, the three UHPC design mixes tested resulted in similar peak strains. At elevated temperatures, for the most part UHPC A & B, D, and F behave very similarly, with respect to their stress-strain relationship, with increasing temperatures the peak strain increases. However, as explained previously, some of the UHPC A & B tests conducted at 300 and 400°C differed slightly. The elastic modulus for UHPC behaved quite differently as compared to their respective compressive strengths. At ambient conditions the elastic modulus for all three UHPC tested is very similar. At temperatures of 100 and 200°C, UHPC F’s elastic modulus experiences the slowest degradation. However, all three UHPC tested reach half their elastic modulus around the same temperature (300°C). At 600 and 700°C design mix UHPC F elastic modulus sustained a rapid decrease to 10 and 7% from ambient conditions. The addition of polypropylene fibers along with steel fibers, UHPC F, does improve the fire performance with respect to compressive strength, elastic modulus below 400°C and reaching temperatures above 400°C. Finally, utilization of larger volume content of steel fiber (design mix UHPC A & B) does not necessarily increase the compressive strength. 69 3.4.3 Fire-induced spalling behavior The following two sections will emphasize the prominent results accumulated as part of this study corresponding to explosive spalling in UHPC. The data pertaining to the effects of rate of heating will be discussed first, followed by thermal gradients. 3.4.3.1 Spalling behavior in experiments The results from this study indicate that employing a low rate of heating does not necessarily correlate with the mitigation of explosive spalling. Though the rate of heat and development of thermal gradients are vital, their resultant, pore pressure, seems to be the predominant trigger (Felicetti et al., 2000). The effects of rate of heat upon the three UHPC design mixes will be discussed here and information pertaining to thermal gradients will be presented in detail in the following section. During this study, the electric furnace experienced fourteen fire induced spalling events; of those, thirteen were explosive in nature. As seen by Figure 3.25, such an explosion produces an exorbitant amount of energy, enough to expand the metal frame of the furnace. The numerous explosive spalling events experienced by the furnace caused a gap of at least 6.35 mm, for most of the height of the furnace door. Therefore, tie down straps were utilized to compensate for the gap. The explosion was usually accompanied with a very loud sound, and Figure 3.26 displays specimens from each design mix that underwent explosive spalling. Prior to utilization of the temperature acquisition data device (Figure 3.7), a handheld thermocouple reader was used, and the temperature was measured every 30 to 45 min. Therefore, the first three elevated temperature tests listed in Table 3.5, the rate of heats listed are estimates, and not exact values. Moreover, the initial goal was to maintain a rate of heat of 2ºC/min as recommended by RILEM standard. However, there was a bit of a learning curve due to testing a novel material. In the first three 70 elevated temperature tests as listed in Table 3.5, the actual heating rates were far below the desired 2ºC/min. Therefore, the electric furnace (Figure 3.3) was calibrated with UHPC A1, in desire to better understand the furnace behavior with UHPC, coupled with an attempt to complete a 600°C compressive test. Unfortunately, specimen UHPC A1 experienced explosive spalling with an average rate of 1.05ºC/min. To better comprehend the explosive spalling involved with UHPC a new testing regime was devised. In short, rate of heating ranging from 2 to 4ºC/min were to be used, with temperature ranging from 200 to 400°C with design mix UHPC A & B. The data associated with this testing, along with all UHPC data for tests conducted at, and above 300°C, is given in Table 3.10. To avoid presenting redundant data, thermal gradient results are presented in Table 3.10 as well, however as stated previously, thermal gradient results will be discussed further in the following section. Table A1, A2, and A3 in Appendix A will provide further details associated with each UHPC test conducted. As expected, the higher the rate of heat, the sooner the UHPC specimen will experience explosive spalling. UHPC B3 (Figure 3.26) experienced explosive spalling in the shortest period, 80 min, combined with the lowest center temperature, 191°C. Although specimen UHPC B8’s rate of heat was higher than UHPC B3, UHPC B8 exploded at 95 min and at a greater core temperature, 248°C. The conflicting results may be attributed to differing furnace input or variance in moisture within the specimen. As opposed to design mix UHPC A & B, UHPC F contains 2.00 kg/m 3 of polypropylene fibers as prescribed by Eurocode 2 (2004), and explosive spalling was not expected. However, UHPC F1 (Figure 3.26) sustained explosive spalling with a rate of heat less than 1.50°C/min. The test was repeated and UHPC F12 underwent explosive spalling around the same temperature, 295°C. Furthermore, UHPC B3’s test was repeated but with UHPC F14 and sustained 71 explosive spalling at the equivalent time, with an average rate of heat 2.50°C/min and core temperature slightly higher, 220°C. Item to mention, due to an experiment error, UHPC A7’s test was abruptly ended and sustained mere surface spalling. However, as the rate was shy of 2ºC/min it is highly expected if the furnace was not shut down too soon, it would have experienced explosive spalling. The nine specimens to explosively spall as part of the initial testing regiment, the average rate of heat was 2.70°C/min, with the least slightly higher than 1ºC/min and average core temperature of 250°C. Therefore, it was concluded to conduct a successful 300°C or higher compressive strength test, a rate of heat lower than 1ºC/min must be utilized. To further study the behavior of UHPC, all three design mixes were studied with a desired rate of heat of 0.50°C/min at temperatures of 300°C and above. To achieve such a rate, two different furnace inputs were utilized, a steady increase with a high target temperature (referred to as input 1) and rapid increase with a low target temperature (referred to as input 2). The former produced three (UHPC B1, B2 and D7) out of the nine tests to explode and surprisingly the latter only two (UHPC D5 and D6) out of fourteen. Employing either of these inputs, design mix UHPC F did not sustain any explosions. UHPC D4 (average rate of heating, 0.50°C/min) was the sole specimen from design mix UHPC D to avoid explosive spalling with input 2 and UHPC D5 and D6 experienced explosive spalling with a center temperature close to 270°C. Astonishingly, the average rate of heat for the two tests were very similar to the UHPC A & B tests that did not experience explosive spalling, of around 0.95ºC/min. Following the resulting two explosions, UHPC D7 and D8 were tested employing input 1 and desired average rate of heating of 0.25ºC/min, with 50% success. UHPC D7 (Figure 3.26) sustained an explosion following a slight increase to the furnace input with core temperature of 284°C and a time to spall of 850 min. UHPC D8 avoided an explosion with an 72 average rate of heating of 0.25ºC/min. Additionally, UHPC B5 was the sole test to avoid explosive spalling from design mix UHPC A & B with input 1 and the core temperature was taken to 329°C. Moreover, upon removal from the furnace, there was moisture visibly escaping the specimen in numerous locations (Figure 3.27). Design mix UHPC F overall average rate of heating to avoid explosive spalling was 0.75ºC/min. The last four UHPC F tests listed in Table 3.7 were not included as part of the previous average. The tests consisted of altering the average rate of heating drastically in an attempt to evaluate the compressive strength following prolonged exposure in the furnace. The average heating rate, core temperature and time to spall for the specimens to undergo explosive spalling for each separate design mix are: UHPC A & B, 1.75ºC/min, 250°C and 170 min, UHPC D, 0.75ºC/min, 275°C and 440 min, and UHPC F, 2.00°C/min, 270°C and 140 min. Overall amongst all UHPC to experience explosive spalling the averages are: 1.50°C/min, 265°C and 250 min. UHPC D’s time to spall is very high due to UHPC D7 undergoing the explosion at 850 min. If UHPC D7 is not included, UHPC D’s average time to spall is 232 min. Figure 3.28, displays the average rate of heating with respect to either, the maximum core temperature attained, or the core temperature for which the specimen experienced explosive spalling, for all the UHPC tests from Table 3.7. Each specimen is labeled in Figure 3.28 and all 14 specimens to experience explosive spalling are depicted with a red box along with their respective time to spall. It is abundantly clear, the rate of heating to avoid explosive spalling for design mixes UHPC A & B, and F is 0.75ºC/min (depicted by a pink dashed line in Figure 3.28) and design mix UHPC D is 0.25ºC/min (depicted by a red dashed line in Figure 3.28). From this experimental study, employing a higher average rate of heating, shows that UHPC can undergo explosive spalling quicker, with core temperatures and average rate of heating 73 as low as 191°C and 1.50°C/min, accordingly. UHPC A & B contains 10% more steel fiber and its critical rate of heating to avoid explosive spalling is 3 times versus UHPC D. In addition, steel fiber alone and the combination with 2.00 kg/m 3 of polypropylene fibers does not mitigate explosive spalling. Moreover, tests confirmed minimal average rate of heating alone do not mitigate the explosive spalling behavior of UHPC. As seen with UHPC B5 and D7, moisture is quite relevant at temperatures above 300°C. Therefore, at lower heating rates, development of thermal gradients coupled with the release of vapor pressure are more crucial. Effect of thermal gradients will be discussed further in the following section. 3.4.3.2 Temperature gradient and rate of heat analysis The thermal gradients development within UHPC directly affect the release of built-up pore pressure (Phan, 2008: Klingsch, 2014). Furthermore, since majority of the moisture content is chemically bound within the binder and does not completely evaporate until temperatures above 800°C, the risk of explosive spalling resulting from thermal gradients is continuously present (Klingsch, 2014). Therefore, results from this research give importance to not only high thermal gradients, but to minimal values as well (Ju et al., 2013). Table 3.11 displays the key points from the thermal gradient with respect to time graphs for each UHPC test listed in Table 3.10. Table 3.11 does not include the UHPC tests conducted employing an average heating rate less than 0.50°C/min. Furthermore, the thermal gradient with respect to time graph for each UHPC design mix (A & B, D, and F) tests, are given in Figure 3.29, 3.30 and 3.31, respectively. Table 3.12 is given to serve as a legend to Figure 3.29, 3.30 and 3.31. The legend describes the average rate of heating for each UHPC test. Referring to Table 3.10 and 3.11, the UHPC tests that underwent high average rate of heating, of at least 1.25ºC/min, the maximum thermal gradient ranged from 14.55 to 32.00°C/cm. 74 The maximum thermal gradients occurred on average within 82 min of heating duration and the center temperature of the specimen did not go beyond 240°C. Eight of these tests, UHPC A13, B8, B3, A4, F1, F12 and F14 (Figure 3.29 and 3.31), underwent explosive spalling, which happened to occur on average about 40 min following the peak thermal gradient. Only UHPC F14 experienced the maximum thermal gradient and explosive spalling at the same time and UHPC F1 with the longest of 86 min. UHPC A13, B8, F1 and F14 respective thermal gradients experienced a short-lived sudden decline following the apex, and then a rapid increase which was concluded abruptly by the occurrence of explosive spalling. UHPC F1’s test was not concluded following the explosive spalling, because the loud explosion was not heard. Thereby, the specimen was discovered to have exploded once opening of the furnace. UHPC B3 and F12 did not suddenly increase following the decline and underwent explosive spalling during their respective decline. Prior to the test prematurely ending, UHPC A7’s (Figure 3.29) thermal gradient was at the initial stages of decreasing. Based off the data attained by the three tests that did explode, if the test were to have continued it too would have experienced explosive spalling. The UHPC specimens that experienced explosive spalling with the slower rate of heating, of less than 1.25ºC/min, the maximum thermal gradients occurred at a much later time as compared to the higher average rate of heating. On average, the maximum thermal gradient occurred within 200 min for these five tests, and the time to spall occurred within 70 min thereafter. Three of the five tests (UHPC A1, B1 and B2) underwent explosive spalling utilizing input 1. Furthermore, the thermal gradient reached the maximum value during the latter part of the test; with each of the specimens experiencing an explosion within 20 min following the maximum thermal gradient. The remaining two tests (UHPC D5, and D6) that underwent explosive spalling, utilized input 2. The maximum thermal gradient was attained much faster (within 90 min), and the explosion occurred 75 144 min following the maximum thermal gradient. Specimen UHPC D6’s maximum thermal gradient (20°C/cm) was as high as the specimens that underwent the higher rate of heating (at least 1.25ºC/min). Surprisingly, specimen UHPC D5’s pinnacle value for its thermal gradient was under 5ºC/cm, yet it still underwent explosive spalling. On the other hand, there were thirteen specimens that did not explode implementing the lower rate of heating. As stated in the previous section UHPC B5 is the sole test not to explode with input 1. Its maximum thermal gradient was 6.9ºC/cm and occurred during the latter part of the test. Over 90% of the remaining twelve specimens, the maximum thermal gradient occurred early (within 90 min), ranging from 6.53 to 8.83ºC/min. UHPC F13 (700°C) is the sole test where the maximum thermal gradient occurred at the end of the heating duration. In an attempt to reach 700°C, the furnace input’s rate was increased towards the latter part of the heating process. Thus, if the input was not drastically increased, the maximum thermal gradient would have occurred within the first 100 min of heating. Based off this study, UHPC inflicted with higher average rate of heating, will develop greater thermal gradients within the specimen that will occur later in the heating process. Average rate of heating greater than 1.25ºC/min coupled with thermal gradients of at least 20°C/cm for design mix UHPC A & B and 5ºC/cm for design mix UHPC F, 100% of the specimens experienced explosive spalling. Plus, the maximum thermal gradient occurred within two-thirds of the heating duration. Additionally, it makes sense UHPC F would result in a lower thermal gradient because of the presence of polypropylene fibers (Phan, 2008). However, with lower average rate of heating of less than 1ºC/min, two different scenarios occurred, (1) if the maximum thermal gradient (at least 10°C/cm) was reached towards the latter portion of the heating process, 67% of the specimens underwent explosive spalling, and (2) if the maximum thermal gradient (at least 5ºC/cm) was 76 reached early during the heating process, 22% of the specimens experienced explosive spalling. The lower maximum thermal gradient corresponds with UHPC D5 and the higher to UHPC B1. Given the critical average rate of heating for design mix UHPC D is lower than UHPC A & B, the values do coincide. Monitoring the thermal gradient while the UHPC specimen is being heated, can provide an inclination whether the UHPC will in fact, experience explosive spalling. 77 Table 3.1: Testing regime conducted as part of this study Elevated temperatures Cylinder size 75x150 mm 24 7 17 6 3 5 4 Room temperature Number Concrete type 1 2 3 4 5 6 7 UHPC A & B UHPC D UHPC F HSC-PP HSC NSC-SF NSC 4 1 4 1 1 1 1 Table 3.2: Mix proportions for UHPC design mixes tested as part of study Components Limestone No. 8, kg/m3 Michigan Natural Sand, kg/m3 Silica Sand, kg/m3 Cement Type I, kg/m3 Silica Fume, kg/m3 Slag St. Lawrence, kg/m3 Limestone Powder, kg/m3 Steel Fiber, kg/m3 Polypropylene Fiber, kg/m3 Water, kg/m3 Water Cement Ratio (w/c) HWRA (28%) Chryso., kg/m3 UHPC A & B UHPC D UHPC F 526 553 304 519 228 104 187 130 153 0.14 43 487 513 282 481 212 96 173 118 114 0.14 46 488 514 283 482 212 96 173 118 2.00 115 0.14 46 78 Table 3.3: Mix proportions for conventional concretes tested as part of study Components HSC HSC-PP NSC NSC-SF Cement Type I, kg/m3 561 561 230 230 Fine aggregate, kg/m3 641 641 930 930 Course aggregate 3/8" Limestone, kg/m3 1089 1089 985 985 42 42 - - - - - 42 - 1.66 - - 151 151 157 154 0.30 0.30 0.50 0.50 - - 25 25 - - 77 77 Silica Fume, kg/m 3 Steel fiber, kg/m3 Polypropylene fibers, kg/m Water, kg/m 3 3 Water cement ratio (w/c) Superplastizer, kg/m 3 Fly Ash (Class C), kg/m3 Table 3.4: Density and 28-day compressive strengths of concrete cylinders tested as part of study Concrete type UHPC A & B UHPC D UHPC F HSC HSC-PP NSC NSC-SF * - Denotes an estimate 28-day compressive strength, MPa 132 182 165 111 100 29 29 79 Density, kg/m3 Density, g/cm3 2500 * 2456 2436 2297 2358 2256 2231 2.50 * 2.46 2.44 2.30 2.36 2.26 2.23 Table 3.5: Details of compressive strength tests of UHPC A & B cylinders T Average rate of heat f c' E Tmax(core) Tmax(furnace) ºC ºC/min MPa GPa ºC ºC UHPC B9 20 N/A 135 X N/A N/A UHPC A12 20 N/A 139 39 N/A N/A UHPC A2 20 N/A 134 42 N/A N/A UHPC A7 20 N/A 138 38 N/A N/A UHPC A 100 0.60 * 121 X X X UHPC A 100 0.40 109 30 X X UHPC B14 100 1.37 119 35 133 237 UHPC A3 100 0.30* 112 31 105 129 UHPC A9 100 1.00* 103 38 132 174 UHPC A14 100 2.00* 108 35 116 162 UHPC A & B 200 0.70* 118 X X X UHPC A6 200 0.54 138 25 218 262 UHPC A & B 200 0.75* 135 X X X UHPC B12 300 0.70 114 18 354 353 UHPC B19 300 0.65 120 11 X 443 UHPC A12 300 0.42 135 18 301 330 UHPC B4 400 0.60* 100 11 X X UHPC A2 400 0.69 117 14 434 339 UHPC A13 400 0.50 134 13 401 425 UHPC B11 400 * – Denotes an estimate 0.60 124 13 X 443 Specimen X – Denotes data not collected 80 Table 3.6: Details of compressive strength tests of UHPC D cylinders T Average rate of heat f c' E Tmax(core) Tmax(furnace) ºC ºC/min MPa GPa ºC ºC UHPC D-1 20 N/A 148 36 N/A N/A UHPC D-2 100 1.60 134 27 161 244 UHPC D-3 200 1.13 142 19 237 X UHPC D-8 300 0.27 163 15 330 347 0.53 153 10 455 463 Specimen UHPC D-4 400 * – Denotes an estimate X – Denotes data not collected 81 Table 3.7: Details of compressive strength tests of UHPC F cylinders T Average rate of heat f c' E Tmax(core) Tmax(furnace) ºC ºC/min MPa GPa ºC ºC UHPC F-4 20 N/A 128 38 N/A N/A UHPC F-11 20 N/A 170 39 N/A N/A UHPC F-19 20 N/A 153 X N/A N/A UHPC F-21 20 N/A 140 X N/A N/A UHPC F-2 100 1.64 120 36 169 229 UHPC F-6 100 2.66 125 X X 304 UHPC F-20 100 1.65 131 X 170 317 UHPC F-3 200 1.89 115 40 230 330 UHPC F-7 200 1.76 127 24 234 300 UHPC F-10 200 0.91 133 X 238 231 UHPC F-5 300 0.75 150 16 330 360 UHPC F-15 300 0.21 136 13 319 346 UHPC F-17 300 0.25 143 10 329 344 UHPC F-8 400 0.74 151 11 433 X UHPC F-16 400 0.23 142 13 421 433 UHPC F-18 400 0.24 132 10 421 436 UHPC F-9 600 0.74 100 4 632 629 0.69 38 3 731 768 Specimen UHPC F-13 700 * – Denotes an estimate X – Denotes data not collected 82 Table 3.8: Details of compressive strength tests of NSC-SF and NSC cylinders T Average rate of heat f c' E Tmax(core) Tmax(furnace) °C °C/min MPa GPa °C °C NSC-SF 20 N/A 42 21 N/A N/A NSC-SF 200 2.36 26 10 N/A 364 NSC-SF 400 2.11 25 3 N/A 482 NSC-SF 400 3.66 30 5 N/A 526 NSC-SF 600 2.29 19 2 N/A 692 NSC-SF 700 1.48 11 2 N/A X NSC 20 N/A 46 24 N/A N/A NSC 400 1.93 30 6 N/A 482 NSC 600 2.15 26 2 N/A 691 NSC 700 1.82 24 3 N/A 742 1.49 11 3 N/A 777 Specimen NSC 750 * – Denotes an estimate X – Denotes data not collected 83 Table 3.9: Details of compressive strength tests of HSC-PP and HSC cylinders T Average rate of heat f c' E Tmax(core) Tmax(furnace) °C °C/min MPa GPa °C °C HSC-PP 20 N/A 112 32 N/A N/A HSC-PP 200 1.04 82 31 N/A 277 HSC-PP 200 2.31 73 13 N/A 401 HSC-PP 400 2.29 41 10 N/A 483 HSC-PP 600 1.94 32 4 N/A 696 HSC-PP 700 1.62 24 3 N/A 741 HSC-PP 750 1.86 16 1 N/A 784 HSC 20 N/A 68 27 N/A N/A HSC 20 N/A 120 31 N/A N/A HSC 200 2.96 72 14 N/A 432 HSC 400 1.90 41 5 N/A 507 2.40 39 6 N/A 664 Specimen HSC 600 * – Denotes an estimate X – Denotes data not collected 84 Table 3.10: Details pertaining to UHPC tests conducted at, and above 300°C ºC/cm 24 Time for maximum thermal gradient min 245 Heating rate at time of spalling ºC/min 2.80 248 32 83 3.42 95 248 29 72 3.43 1.87 99 185 21 96 3.89 200 2.60 80 191 24 67 5.41 A4 300 2.00 102 227 X X 2.70 A&B 300 0.42 No spalling 301 X X N/A A&B 400 0.50 No spalling 401 X X N/A B5 300 0.80 No spalling 329 7 290 N/A B1 400 0.77 281 273 10 279 1.60 B2 300 0.70 290 277 14 293 1.97 B12 300 0.70 No spalling 354 9 76 N/A B4 * 400 0.60 No spalling 430 X X N/A A2 400 0.69 No spalling 434 8 81 N/A B19 300 0.65 No spalling 340 7 83 N/A B11 * 400 0.60 No spalling 430 X X N/A D4 400 0.53 No spalling 455 7 84 N/A D5 * 600 0.88 228 267 4 87 0.48 D6 300 0.98 236 275 20 90 0.63 D7 D8 F1 F5 F8 F9 F12 F13 300 300 600 300 400 600 600 700 0.39 0.27 1.42 0.75 0.74 0.74 1.99 0.69 849 No spalling 177 No spalling No spalling No spalling 159 No spalling 284 330 295 330 433 632 296 731 5 X 15 7 8 8 5 10 849 X 91 90 87 85 83 1104 0.48 N/A 1.51 N/A N/A N/A 1.63 N/A T Average rate of heat Time to spall Tcore Maximum thermal gradient A1 ºC 600 ºC/min 1.05 min 293 ºC 350 A13 300 2.20 125 B8 * 300 2.83 A7 * 400 B3 Specimen 85 Table 3.10 (cont’d) Specimen T Average rate of heat C ºC/min F14 300 2.45 F15 300 0.21 F16 400 0.23 F17 300 0.25 F18 400 0.24 * – Denotes an estimate Time to spall Tcore Maximum thermal gradient min 81 No spalling No spalling No spalling No spalling ºC 220 319 421 329 421 ºC/cm 13 2 X 1 3 Time for maximum thermal gradient min 81 661 X 680 714 Heating rate at time of spalling ºC/min 5.83 N/A N/A N/A N/A X – Denotes data not collected Table 3.11: Key points from thermal gradient with respect to time graphs for UHPC tests conducted at, and above 300°C Average rate of heat, ºC/min Average rate of heat, ºC/min Maximum average thermal gradient, ºC/cm Average time for maximum average thermal gradient, min r ≥ 1.25 2.17 20 82 32 100 115 239 r < 1.25 0.71 10 212 24 27 266 389 0.65 8 220 10 N/A N/A 431 0.88 14 199 24 100 266 288 r < 1.25 (No spalling) r < 1.25 (Spalling) r – Denotes average rate of heat 86 Maximum thermal gradient, ºC/cm % of tests to spall Average Tavg.(core), time to ºC spall, min Table 3.12: Color legend for thermal gradient with respect to time graphs Average rate of heat, ºC/min Color designator r ≤ 0.70 Any shade of blue 0.70 < r ≤ 1.25 Any shade of green 1.25 < r ≤ 1.75 Any shade of violet 1.75 < r ≤ 2.25 Any shade of orange 2.25 < r ≤ 2.75 Any shade of red r > 2.75 Any shade of dark red r – Denotes average rate of heat 87 (a) UHPC specimens’ thermocouple placement (b) HSC and NSC specimens’ thermocouple placement Figure 3.1: Prepared concrete specimens 88 Figure 3.1 (cont’d) (c) Dimensions of tested cylinders Figure 3.2: Table saw utilized to cut and prepare the concrete cylinders 89 Figure 3.3: Electrical furnace utilized in heating concrete cylinders Figure 3.4: Forney load controlled strength testing machine to conduct compressive strength testing as part of this study 90 Figure 3.5: Compressometer with (2) LVDTs and (2) metal rods utilized to develop the stress-strain relationship as part of this study (a) Desired heating regime; Adapted from Khaliq (2012) Figure 3.6: Desired heating rates for high temperature compression tests 91 Figure 3.6 (cont’d) (b) Desired rate of heat by type of concrete (c) Desired loading regime; adapted from Khaliq (2012) 92 Figure 3.7: Temperature data acquisition device utilized as part of this study 93 800 700 Temperature, ºC 600 500 400 300 200 100 0 0 50 100 150 200 250 300 350 400 Time, min NSC Surface NSC Furnace NSC-SF Surface NSC-SF Furnace 2 C/min (a) NSC and NSC-SF concrete cylinders tested at 600ºC 800 700 Temperature, ºC 600 500 400 300 200 100 0 0 50 100 150 200 250 300 350 400 Time, min HSC Surface HSC Furnace HSC-PP Surface HSC-PP Furnace 2 C/min (b) HSC and HSC-PP concrete cylinders tested at 600ºC Figure 3.8: Temperature versus time development for concrete cylinders tested at 600°C 94 Figure 3.8 (cont’d) 700 Temperature, ºC 600 500 400 300 200 100 0 0 100 200 300 400 500 600 700 800 900 1000 1100 Time, min F9 Surface F9 Furnace F9 Center 0.5 C/min (c) UHPC F9 concrete cylinder tested at 600ºC 180 UHPC A & B UHPC D 160 UHPC F Compressive Strength, MPa 140 HSC-PP HSC 120 NSC-SF 100 NSC 80 60 40 20 0 0 100 200 300 400 500 Temperature, ºC 600 700 800 Figure 3.9: Compressive strength with respect to temperature of various concrete cylinders tested as part of research 95 40 UHPC A & B 35 UHPC D UHPC F Elastic Modulus, GPa 30 HSC-PP HSC 25 NSC-SF NSC 20 15 10 5 0 0 100 200 300 400 500 Temperature, ºC 600 700 800 Figure 3.10: Elastic modulus with respect to temperature of various concrete cylinders tested as part of research 96 50 20°C 45 400°C 40 600°C 35 Stress, MPa 700°C 30 750°C 25 20 15 10 5 0 0.00000 0.00500 0.01000 0.01500 0.02000 0.02500 0.03000 Strain, mm/mm Figure 3.11: NSC stress-strain relationships with respect to temperature Figure 3.12: Failure modes of NSC at respective temperatures 97 45 20°C 40 200°C 35 400°C - 1 30 Stress, MPa 400°C - 2 25 600°C 20 700°C 15 10 5 0 0.00000 0.00500 0.01000 0.01500 0.02000 0.02500 0.03000 Strain, mm/mm Figure 3.13: NSC-SF stress-strain relationships with respect to temperature Figure 3.14: Failure modes of NSC–SF at respective temperatures 98 140 120 Stress, MPa 100 80 60 40 20 0 0.0000 0.0010 0.0020 0.0030 0.0040 0.0050 0.0060 0.0070 Strain, mm/mm 20°C 20°C - 2 200°C 400°C 600°C Figure 3.15: HSC stress-strain relationships with respect to temperature Figure 3.16: Failure modes of HSC at respective temperatures 99 120 100 20°C 200°C - 1 200°C - 2 400°C - 1 400°C - 2 600°C 700°C 750°C Stress, MPa 80 60 40 20 0 0.00000 0.00500 0.01000 0.01500 0.02000 Strain, mm/mm Figure 3.17: HSC-PP stress-strain relationships with respect to temperature 100 Figure 3.18: Failure modes of HSC – PP at respective temperatures 101 160 140 Stress, MPa 120 100 80 60 40 20 0 0 0.002 0.004 0.006 0.008 0.01 0.012 Strain, mm/mm A12 20°C A2 20°C A7 20°C A 100°C A14 100°C A3 100°C A9 100°C B14 100°C A4 200°C B12 300°C B19 300°C A12 300°C B4 400°C A2 400°C B11 400°C A13 400°C Figure 3.19: UHPC A & B stress-strain relationships with respect to temperature Figure 3.20: Failure modes of UHPC A & B at respective temperatures 102 180 160 140 Stress, MPa 120 D1 20°C 100 D2 100°C 80 D3 200°C 60 D8 300°C 40 D4 400°C 20 0 0.00000 0.00200 0.00400 0.00600 0.00800 0.01000 0.01200 0.01400 Strain, mm/mm Figure 3.21: UHPC D stress-strain relationships with respect to temperature Figure 3.22: Failure modes of UHPC D at respective temperatures 103 180 160 140 Stress, MPa 120 100 80 60 40 20 0 0.000 0.002 0.004 0.006 0.008 0.010 0.012 0.014 0.016 0.018 Strain, mm/mm F4 20°C F11 20°C F21 20°C F2 100°C F6 100°C F20 100°C F3 200°C F7 200°C F10 200°C F5 300°C F15 300°C F17 300°C F8 400°C F16 400°C F18 400°C F9 600°C F13 700°C Figure 3.23: UHPC F stress-strain relationships with respect to temperature Figure 3.24: Failure modes of UHPC F at respective temperatures 104 Figure 3.25: Damage to furnace due to explosive spalling 105 Figure 3.26: UHPC specimens following experiencing explosive spalling in electrical furnace 106 Figure 3.27: Specimen UHPC B5 displaying water escaping concrete following 300°C test 107 Figure 3.28: Relation between rate of heating with respect to either, (1) the spalling temperature, or (2) the maximum center temperature attained Thermal Gradient, ºC/cm 45 40 A 100 C B14 100 C 35 B3 200 C A13 300 C 30 B8 300 C B5 300 C 25 B2 300 C B12 300 C 20 B19 300 C A7 400 C 15 B1 400 C A2 400 C A1 600 C B11 400 C 10 5 0 -5 0 100 200 300 400 500 600 700 800 Time, min Figure 3.29: Thermal gradient with respect to time for UHPC A & B cylinders 108 900 D2 100 C 20 Thermal Gradient, ºC/cm D4 400 C D5 600 C 15 D6 300 C D7 300 C D8 300 C 10 5 0 0 100 200 300 400 -5 500 600 700 800 900 1000 Time, min Figure 3.30: Thermal gradient with respect to time for UHPC D cylinders 20 F2 100 C F20 100 C F3 200 C F7 200 C F10 200 C F5 300 C F15 300 C F14 300 C F8 400 C F18 400 C F1 600 C F9 600 C F12 600 C F13 700 C 18 Thermal Gradient, ºC/cm 16 14 12 10 8 6 4 2 0 -2 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 Time, min Figure 3.31: Thermal gradient with respect to time for UHPC F cylinders 109 3.5 Summary Material tests were conducted to characterize the compressive strength, stiffness, and stress-strain relationship with increasing temperatures. All concretes evaluated underwent mechanical degradation with increasing temperatures, and to conduct successful tests of UHPC above 200°C, lower heating rates were utilized. Variables incorporated within the design mixes included, (1) addition of fibers (steel or polypropylene), (2) no fiber content, (3) varying the steel fiber content, and (4) a hybrid fiber mix (steel and polypropylene). The inclusion of fibers does not increase the strength. However, addition of steel fibers increases the ductility, and addition of polypropylene fibers influences the stiffness. Finally, all design mixes of UHPC experienced fire induced spalling, while none for conventional concretes. UHPC can sustain explosive spalling at temperatures less than 200°C, and minimizing the heating rate does not correspond to complete mitigation of explosive spalling. 110 CHAPTER FOUR 4. COMPARISON OF PROPERTIES OF UHPC WITH CONVENTIONAL CONCRETE AND BUILDING CODES 4.1 General UHPC’s design premise allows for excellent interfacial transition zones because it is developed upon minimal use of water, fine aggregate (limestone and silica sand), and profuse amount of silica fume and cement. These developmental qualities allow UHPC to have ambient condition mechanical properties superior to HSC and NSC. While at elevated temperatures, the rate of degradation of concrete is proportional to its strength or density. Consequently, the low permeability of UHPC, hailed for its mechanical properties and durability prowess, produces calamitous results with increasing temperatures. The compressive strength, stress-strain behavior, and elastic modulus of the three different design mixes of UHPC, A & B, D, and F, will be compared to the conventional concretes along with constitutive relationships provided as per ASCE (1992) and Eurocode 2 (2004). Initially the data will be compared at ambient conditions, followed by a comparison at elevated temperatures. 4.2 Comparison of room temperature properties As compared to UHPC, the NSC evaluated as part of this study contains over 3.5 times the w/c ratio, coarse aggregate and contains no silica fume. While HSC’s w/c ratio is 2 times more, it utilizes coarse aggregate and has 20% of the silica fume of UHPC. NSC and NSC-SF have the least compressive strength and elastic modulus due to their high w/c ratio. The two design mixes of NSC are on average only 30% and 60% of UHPC’s compressive strength and stiffness, respectively. Concurrently, due to the higher w/c ratio and small amount of silica fume combined with coarse aggregate, HSC and HSC-PP possess mechanical properties less than the UHPC tested. 111 The two design mixes of HSC are on average 81% of UHPC. Moreover, the peak strain achieved for all concretes are within a 0.0035 to 0.0050 mm/mm range, with UHPC F displaying the greatest ductility, closely followed by NSC-SF and HSC. Similar to UHPC F, conventional concretes with fibers produce the superior ductility. Lastly, regarding stiffness UHPC A & B with the higher amount of steel fiber achieved the greatest value, and the inclusion of polypropylene fibers with HSC-PP and UHPC F proved to increase the stiffness as well. 4.3 Comparison of elevated temperature properties 4.3.1 Comparison of UHPC with conventional concretes tested As seen in Figure 4.1, owing to each type of concrete’s unique design, the rate of degradation is not consistent. Due to UHPC’s maximized packing density, its compressive strength with increasing temperatures is quite different versus the conventional concretes tested. Moreover, due to implementing a heating rate that deviated from RILEM standard’s recommendation, directly comparing UHPC’s mechanical properties with the conventional concretes at and above temperatures of 200°C is abstruse. The comparison is further complicated by only UHPC F having successful tests conducted at 600 and 700°C. Given the above variables, the comparisons are as follows. Regarding the relative compressive strength (Figure 4.1), tests conducted through 400°C, all UHPC design mixes remain relatively close to their respective original strengths. The expected strength loss from calcium-hydroxide at temperatures of 400°C is immensely reduced due to high contents of silica fume in each UHPC design mix. While the conventional concretes experience a steady degradation, HSC design mixes suffer a steeper decline. Beyond 500°C the quartz within UHPC will further exacerbate the degradation, and at temperatures greater than 700°C UHPC will encounter strength loss due to the decomposition of the cement paste. The conventional concretes’ 112 strength suffers similarly to with the latter, however, UHPC’s will be much higher due to the higher contents of cement. Another similarity seen in Figure 4.1 is that the inclusion or increasing the contents of steel fiber does not correlate to greater compressive strength. Lastly, as seen by UHPC F and HSC-PP, the addition of polypropylene fibers slightly compromises the compressive strength. Contrary to the differences between the compressive strength, the relative modulus of elasticity (Figure 4.2) for all concretes tested, degrade in a similar fashion with increasing temperatures. Each type of concrete’s elastic modulus drops to 50%, ranging from 200 to 250°C. Moreover, with respect to the concretes tested up to 300°C, the addition of steel fibers did not contribute to NSC’s stiffness, while the inclusion of steel (UHPC A & B and D), polypropylene (HSC-PP), or polypropylene and steel fibers (UHPC F) did assist the modulus of elasticity. Although the relative elastic modulus for the various concrete degraded similarly, the relative stress-strain relationships (Figure 4.3) demonstrated differences. At temperatures up to 400°C, the ductility of the tested conventional concretes was comparable to the UHPC design mixes (twice the ambient condition peak strain). UHPC D4 (400°C) withstood the greatest ductility amongst all design mixes of UHPC with 3.25 times its original peak strain. The addition of steel or polypropylene fibers with the UHPC and conventional concretes improved the ductility with increasing temperatures. Though UHPC F9 (600°C) displayed greater peak strain as compared to the conventional concretes, it was 20% less than UHPC D4. Furthermore, UHPC F13’s (700°C) relative peak strain was 30% less than the tested conventional concretes. The drastic reduction in peak strain of UHPC F at 600 and 700°C may be attributed to the lengthy duration of fire exposure involved to reach the targeted temperatures. 113 4.3.2 Comparison of UHPC with building codes Through 400°C, the relative compressive strengths (Figure 4.1) of the code conventional concretes display minimal degradation and behave comparably as the tested UHPC. Furthermore, UHPC F’s relative strengths at 600 and 700°C are analogous to the constitutive relationships dictated by the codes as well. Along with the strengths, the elastic modulus (Figure 4.2), with increasing temperatures, displays minimal variation between the UHPC and code conventional concretes. However, the relative peak strain recommended by the codes is nearly 4.5 times the tested UHPC cylinders at a temperature range of 400 to 700°C. 4.4 Comparison of spalling 4.4.1 Comparison of UHPC with conventional concretes tested Though the HSC investigated as part of this study contains 7% silica fume, as compared to cement weight, and no polypropylene fibers, it did not result in explosive spalling. In fact, no conventional concrete evaluated encountered fire induced spalling. Whereas all UHPC design mixes considered as part of this research experienced explosive spalling with heating rates as low as 0.40°C/min. The occurrence of explosive spalling at such minimal heating rates implies the principle cause is the pore pressure build-up due to the dense microstructure of UHPC. 4.4.2 Comparison of UHPC with building codes Design mix UHPC F contains nearly 45% silica fume to cement weight ratio and as prescribed by Eurocode 2 (2004) for HSC, 2 kg/m3 of polypropylene fiber were incorporated to mitigate fire induced spalling. However, three UHPC F cylinders suffered an explosion with heating rates as low as 1.40°C/min. Though the high content of silica fume lowered the C/S ratio, it gravely reduced the permeability and increased the main binder for UHPC, C-S-H. 114 1.25 UHPC A & B UHPC D UHPC F 1.00 HSC-PP Relative Compressive Strength HSC NSC-SF NSC 0.75 ASCE EC-Siliceous EC Carbonate 0.50 0.25 0.00 0 100 200 300 400 500 Temperature, ºC 600 700 800 900 Figure 4.1: Relative compressive strength with respect to temperature of various concrete cylinders tested as part of research, and Eurocode 2 (2004) and ASCE (1992) 115 1.00 UHPC A & B UHPC D UHPC F HSC-PP 0.75 Relative Elastic Modulus HSC NSC-SF NSC ASCE 0.50 EC-Siliceous EC-Carbonate 0.25 0.00 0 100 200 300 400 500 Temperature, ºC 600 700 800 900 Figure 4.2: Relative elastic modulus with respect to temperature of various concrete cylinders tested as part of research, and Eurocode 2 (2004) and ASCE (1992) 116 1.25 NSC 20°C NSC 400°C NSC 600°C NSC 700°C 1.00 NSC 750°C Relative Stress, fc',T/fc' NSC-SF 20°C NSC-SF 200°C 0.75 NSC-SF 400°C NSC-SF 600°C NSC-SF 700°C 0.50 0.25 0.00 0 1 2 3 4 5 Relative Strain, εT/ε 6 7 8 (a) Relative stress-strain relationship for NSC and NSC-SF concrete cylinders tested Figure 4.3: Relative stress-strain relationships for concrete cylinders tested 117 Figure 4.3 (cont’d) 1.25 HSC 20°C HSC 200°C HSC 400°C 1.00 HSC 600°C HSC-PP 20°C Relative Stress, fc',T/fc' HSC-PP 200°C HSC-PP 400°C 0.75 HSC-PP 600°C HSC-PP 700°C HSC-PP 750°C 0.50 0.25 0.00 0 1 2 3 4 5 Relative Strain, εT/ε 6 7 8 (b) Relative stress-strain relationship for HSC and HSC-PP concrete cylinders tested 118 Figure 4.3 (cont’d) 1.25 Relative Stress, fc',T/fc' 1.00 0.75 0.50 0.25 0.00 0 1 2 3 4 5 Relative Strain, εT/ε 6 UHPC A & B 20°C UHPC B14 100°C UHPC A4 200°C UHPC A12 300°C UHPC A13 400°C UHPC D1 20°C UHPC D2 100°C UHPC D3 200°C UHPC D8 300°C 7 8 UHPC D4 400°C (c) Relative stress-strain relationship for UHPC A & B and D concrete cylinders tested 119 Figure 4.3 (cont’d) 1.25 UHPC F4 20 C UHPC F11 20°C UHPC F2 100°C 1.00 UHPC F3 200°C Relative Stress, fc',T/fc' UHPC F5 300°C UHPC F8 400°C 0.75 UHPC F9 600°C UHPC F13 700°C 0.50 0.25 0.00 0 1 2 3 4 5 Relative Strain, εT/ε 6 7 (d) Relative stress-strain relationship for UHPC F concrete cylinders tested 120 8 Figure 4.3 (cont’d) 1.25 Relative Stress, fc',T/fc' 1.00 0.75 0.50 0.25 0.00 0 1 2 3 4 5 6 7 8 9 10 11 Relative Strain, εT/ε 20°C ASCE - NSC 100°C ASCE - NSC 200°C ASCE - NSC 300°C ASCE - NSC 400°C ASCE - NSC 500°C ASCE - NSC 600°C ASCE - NSC 700°C ASCE - NSC 800°C ASCE - NSC (e) Relative stress-strain relationship for NSC from ASCE (1992) 121 12 13 Figure 4.3 (cont’d) 1.25 Relative Stress, fc',T/fc' 1.00 0.75 0.50 0.25 0.00 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Relative Strain, εT/ε 20°C EC 100°C EC 200°C EC 300°C EC 400°C EC - Sil. 400°C EC - Calc. 500°C EC - Sil. 500°C EC - Calc. 600°C EC - Sil. 600°C EC - Calc. 700°C EC - Sil. 700°C EC - Calc. 800°C EC - Sil. 800°C EC - Calc. (e) Relative stress-strain relationship for siliceous and carbonate concrete from Eurocode 2 (2004) 122 4.5 Summary Comparisons were presented from the experimental testing of UHPC and conventional concretes, and UHPC with the constitutive relationships recommended by ASCE (1992) and Eurocode 2 (2004). As expected due to UHPC’s contrasting composition, there are differences regarding the properties of UHPC and conventional concretes. Furthermore, UHPC’s strength degradation was comparable to the conventional concretes as prescribed by the codes. However, there is a vast variation of the peak strains between UHPC and code conventional concretes. Lastly, following the recommendations as prescribed by Eurocode 2 (2004) to mitigate fire induced spalling was not successful. 123 CHAPTER FIVE 5. CONCLUSIONS AND RECOMMENDATIONS 5.1 General The experimental investigation conducted as part of this thesis provides data pertaining to the high temperature behavior of UHPC. Thereby providing the necessary data to evaluate the fire response of UHPC structural members. The mechanical properties tested from 20-700°C were compressive strength, stress-strain relationship, and elastic modulus of three different design mixes of UHPC consisting of varying fiber type and content, and four different conventional types of concrete were tested for comparative purposes. Furthermore, differing heating rates were employed to study the explosive spalling nature of UHPC. Empirical relations depicting the mechanical behavior with respect to temperature, and prominent data of fire induced spalling are presented. 5.2 Key findings Based on the experimental research accumulated as part of this thesis, the following conclusions can be derived: 1. To conduct successful testing above 200°C of all UHPC design mixes heating rates less than 1°C/min were utilized, otherwise explosive spalling occurred. Furthermore, UHPC F sustained three explosive spalling occurrences, deeming 2.00 kg/m 3 of polypropylene fibers not sufficient to mitigate the abovementioned. 2. Fire induced spalling occurred with heating rates less than 0.50°C/min, implying the root cause of explosive spalling is the built-up pore pressure owing to UHPC’s dense medium. 124 3. UHPC’s compressive strength varies closely to its original strength up to 400°C, thereby degrading differently with temperature as compared to conventional concretes. 4. The steel fiber content does not influence the compressive strength of UHPC, but it does improve the ductility. Additionally, the combination of steel and polypropylene fibers (UHPC F) improves the stiffness up to 200°C 5. There is a vast disconnect for experimental data and recommendations prescribed in codes. Specifically, mechanical properties such as compressive strength and stress-strain behavior, displayed poorer fire performance as compared to their respective codes counterpart. 5.3 Recommendations for future research Although all three design mixes of UHPC suffered explosive spalling, the literature contains various studies that prove contrary. Investigations have employed heating rates of 10°C/min and evaluated UHPC specimens up to 1000°C. Furthermore, UHPC mechanical properties considered at the respective elevated temperatures, as opposed to the residual-state, is quite scarce. Therefore, refinement of the design mix to be tested at the elevated temperature state is of the utmost importance. Below are the author’s recommendations for future research: ▪ Formulate a design mix that would utilize a combination of silica fume, cement, and fly ash or GGBFS and evaluate the mechanical properties at elevated temperatures with varying heating rates ▪ Evaluate the mechanical properties at elevated temperatures with varying heating rates, utilizing a design mix with the above mentioned basic formula and vary the fiber content as follows: i. Steel fiber 125 ▪ ii. Steel and polypropylene fibers iii. Steel and polypropylene fibers and vary the polypropylene fibers dimension Evaluate the thermal properties at elevated temperatures utilizing a design mix with the above mentioned basic formula ▪ Further investigation of fire induced spalling at differing heating rates 5.4 Research impact It is evident that the data generated as part of this study is vital, and will provoke a swift impression upon the implementation of UHPC for infrastructure applications. By virtue of UHPC’s microstructure, it possesses consummate mechanical and durability properties. However, the preceding properties cause UHPC to be susceptible to fire induced spalling, and such an occurrence can inhibit a structure reaching its fire resistance requirement. Through the course of testing, this limiting facet could not be minimized by additional steel fiber or inclusion of polypropylene fiber as recommended in codes, and results as such emphasize the continual evaluation of UHPC’s properties at time of fire exposure. Therefore, to avoid further loss, supplementary research must be conducted evaluating high temperature properties of UHPC. 126 APPENDIX 127 Appendix High temperature properties of UHPC Table A1: Additional notes pertaining to UHPC A & B specimen tests T Specimen Average rate of heating Comments °C °C/min UHPC B9 20 N/A None UHPC A12 20 N/A None UHPC A2 20 N/A None UHPC A7 20 N/A None UHPC A 100 0.60 * UHPC A 100 0.40 None UHPC B14 100 1.37 None UHPC A3 100 0.30* None UHPC A9 100 1.00* None UHPC A14 100 2.00* None UHPC A & B 200 0.70* No data acquisition utilized. Average rate of heat is an estimation based off time UHPC A6 200 0.54 None UHPC A & B 200 0.75* UHPC B12 300 0.70 UHPC B19 300 0.65 None UHPC A12 300 0.42 None UHPC B4 400 0.60* Data acquisition turned off; average rate of heat is an estimate based off a similar test UHPC A2 400 0.69 None UHPC A13 400 0.50 None UHPC B11 400 0.60 Center thermocouple was not working No data acquisition utilized. Average rate of heat is an estimation based off time No data acquisition utilized. Average rate of heat is an estimation based off time Surface thermocouple readings were lower than center thermocouple; therefore for therm grad, utilized the average of the center and furnace for the surface temp * – Denotes an estimate 128 Table A2: Additional notes pertaining to UHPC D specimen tests T Specimen Average rate of heating Comments °C °C/min UHPC D-1 20 N/A None UHPC D-2 100 1.60 None UHPC D-3 200 1.13 Surface and furnace thermocouples providing erroneous values UHPC D-8 300 0.27 None UHPC D-4 400 0.53 None * – Denotes an estimate 129 Table A3: Additional notes pertaining to UHPC F specimen tests T Specimen Average rate of heating Comments °C °C/min UHPC F-4 20 N/A None UHPC F-11 20 N/A None UHPC F-19 20 N/A None UHPC F-21 20 N/A None UHPC F-2 100 1.64 UHPC F-6 100 2.66 UHPC F-20 100 1.65 UHPC F-3 200 1.89 UHPC F-7 200 1.76 None Center thermocouple values were void; data is regarding the surface thermocouple None Surface thermocouple readings were lower than expected; therefore, for thermal grad, utilized the average of the center and furnace for the surface temp None UHPC F-10 200 0.91 None UHPC F-5 300 0.75 UHPC F-15 300 0.21 UHPC F-17 300 0.25 UHPC F-8 400 0.74 UHPC F-16 400 0.23 UHPC F-18 400 0.24 UHPC F-9 600 0.74 None Testing the compressive strength with reduced rate of heating Testing the compressive strength with reduced rate of heating None Testing the compressive strength with reduced rate of heating Testing the compressive strength with reduced rate of heating Surface thermocouple readings were lower than expected; therefore, for thermal grad, utilized the average of the center and furnace for the surface temp None UHPC F-13 700 * – Denotes an estimate 0.69 130 REFERENCES 131 REFERENCES 1. Abdul-Hussain, S.T. (2013). "Effect of Elevated Temperatures on Compressive and Tensile Strengths of Reactive Powder Concrete." Journal of Engineering and Development, vol. 17.4: pp. 259-278. 2. Abrams, D.A. (1919). “Design of concrete mixtures.” Structural Materials Research Laboratory, Lewis Institute. 3. Al-Jabri, K.S., Waris, M.B., Al-Saidy, A.H. (2016). "Effect of aggregate and water to cement ratio on concrete properties at elevated temperature: Effect of Aggregate and Water to Cement Ratio on Concrete Properties." Fire and Materials, vol. 40(7): pp. 913-925. 4. Ali, M.H., Dinkha, Y.Z., Haido J.H. (2016). "Mechanical properties and spalling at elevated temperature of high performance concrete made with reactive and waste inert powders." Engineering Science and Technology, an International Journal, vol. 2: pp. 536-541. 5. Alkaysi, M. (2016). “Strength and Durability of Ultra-High Performance Concrete Materials and Structures.” Doctoral dissertation, University of Michigan. 6. Arioz, O. (2007). "Effects of elevated temperatures on properties of concrete." Fire Safety Journal, vol. 42(8): pp. 516-522. 7. ASCE (1992). “Structural fire protection.” American Society of Civil Engineers Manuals and Reports on Engineering Practice, 78, New York. 8. Aslani, F., Bastami, M. (2011). "Constitutive Relationships for Normal- and High-Strength Concrete at Elevated Temperatures." ACI Materials Journal, vol. 108(4): pp, 355. 9. ASTM C39/C39M (2016). “Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens.” American Society for Testing and Materials, West Conshohocken, PA. 10. ASTM C293/C293M (2016). “Standard Test Method for Flexural Strength of Concrete (Using Simple Beam with Center-point Loading.” American Society for Testing and Materials, West Conshohocken, PA. 11. ASTM C469/C469M (2014). “Standard Test Method for Static Modulus of Elasticity and Poisson’s Ratio of Concrete in Compression.” American Society for Testing and Materials, West Conshohocken, PA. 132 12. ASTM C496/C496M (2011). “Standard Test Method for Splitting Tensile Strength of Cylindrical Concrete Specimens.” American Society for Testing and Materials, West Conshohocken, PA. 13. ASTM C1113/C1113M (2013). “Standard Test Method for Thermal Conductivity of Refractories by Hot Wire (Platinum Resistance Thermometer Technique).” American Society for Testing and Materials, West Conshohocken, PA. 14. ASTM E119a (2008). “Standard Methods of Fire Test of Building Construction and Materials. ” American Society for Testing and Materials, West Conshohocken, PA. 15. ASTM E831 (2014). “Standard Test Method for Linear Thermal Expansion of Solid Materials by Thermomechanical Analysis.” American Society for Testing and Materials, West Conshohocken, PA. 16. ASTM E1269 (2011). “Standard Test for Determining Specific Heat Capacity by Differential Scanning Calorimetry.” American Society for Testing and Materials, West Conshohocken, PA. 17. ASTM E1530 (2016). “Standard Test Method for Evaluating the Resistance to Thermal Transmission of Materials by the Guarded Heat Flow Meter Technique.” American Society for Testing and Materials, West Conshohocken, PA. 18. ASTM E1868 (2015). “Standard Test Methods for Loss-On-Drying by Thermogravimetry.” American Society for Testing and Materials, West Conshohocken, PA. 19. Aydin, S., Baradan, B. (2013). “Engineering Properties of Reactive Powder Concrete without Portland Cement." ACI Materials Journal, vol. 110(6): pp. 619-627. 20. Aydin, S., Baradan, B. (2012). "High Temperature Resistance of Alkali-Activated Slag- and Portland Cement Based Reactive Powder Concrete." ACI Materials Journal, vol. 109(4): pp. 463-470. 21. Aziz, E.M. (2015). “Response of fire exposed steel bridge girders.” Doctoral dissertation, Michigan State University. 22. Bashandy, A.A. (2013). "Influence of elevated temperatures on the behavior of economical reactive powder concrete." Journal of Civil Engineering Research, vol. 3.3: pp. 89-97. 23. Behloul, M., Chanvillard, G., Casanova, P., Orange, G., France F.F. (2002). "Fire resistance of Ductal® ultra high performance concrete." 1st fib Congress, vol. 1: pp. 421-430. 133 24. Bei, S., Zhixiang, L. (2016). "Investigation on spalling resistance of ultra-high-strength concrete under rapid heating and rapid cooling." Case Studies in Construction Materials, vol. 4: pp. 146-153. 25. Buchanan, A.H., Abu, A.K. (2017). “Structural Design for Fire Safety.” John Wiley & Sons, Chichester, West Sussex, United Kingdom. 26. Burke, B.T. (2011). "Residual Strength of Ultra-High Performance Concrete After Exposure to Elevated Temperatures." Master thesis, University of Connecticut. 27. Canbaz, M. (2014). "The Effect of High Temperature on Reactive Powder Concrete." Construction and Building Materials, vol. 70: pp. 508-513. 28. Chang, Y.F., Chen, Y.H., Sheu, M.S., Yao, G.C. (2006). "Residual stress–strain relationship for concrete after exposure to high temperatures." Cement and Concrete Research, vol. 36(10): pp. 1999-2005. 29. Chen, G.M., Yang, H., Lin, C.J., Chen, J.F., He, Y.H., Zhang, H.Z. (2016). "Fracture behaviour of steel fibre reinforced recycled aggregate concrete after exposure to elevated temperatures." Construction and Building Materials, vol. 128: pp. 272-286. 30. Chen, X., Chen, W., Rougelot, T., Davy, C.A., Agostini, F., Skoczylas, F., Bourbon, X. (2009). "Experimental Evidence of a Moisture Clog Effect in Cement-Based Materials Under Temperature." Cement and Concrete Research, vol. 39(12): pp. 1139-1148. 31. Demirel, B., Keleştemur, O. (2010). "Effect of elevated temperature on the mechanical properties of concrete produced with finely ground pumice and silica fume." Fire Safety Journal, vol. 45(6): pp. 385-391. 32. Dehn, F. (2004). “Fire Resistance of Ultra High Performance Concrete (UHPC) – Testing of Laboratory Samples and Columns under Load.” International Symposium on Ultra High Performance Concrete, Kassel, Germany, September 13-15. 33. Dwaikat, M. B., Kodur, V.K.R. (2009). "Hydrothermal Model for Predicting Fire-Induced Spalling in Concrete Structural Systems." Fire Safety Journal, vol. 44(3): pp. 425-434. 34. Elwell, D.J., Fu, G. (1995). “Compression testing of concrete: cylinders vs. cubes”. No. FHWA/NY/SR-95/119.Albany, New York, NY, USA: Transportation Research and Development Bureau, New York State Department of Transportation. 35. Ergün, A., Kürklü, G., Serhat, M.B., Mansour, M.Y. (2013). "The effect of cement dosage on mechanical properties of concrete exposed to high temperatures." Fire Safety Journal, vol. 55: pp. 160-167. 134 36. EC2. (2004). “EN 1992-1-2: Design of concrete structures, Part 1-2: General Rules-Structural Fire Design.” European Committee for Standardization, Brussels, Belgium. 37. Felicetti R., Gambarova, P.G., Sora, M.N., Khoury, G.A. (2000). "Mechanical behaviour of HPC and UHPC in direct tension at high temperature and after cooling." Fifth RILEM symposium on fibre-reinforced concretes, vol. N: pp. 749-758. 38. Felicetti, R., Lo Monte, F. (2013). "Concrete Spalling: Interaction between Tensile Behaviour and Pore Pressure during Heating." MATEC Web of Conferences, vol. 6: pp. 3001. 39. Gesoglu, M., Güneyisi, E., Nahhab, A.H., Yazıcı, H. (2015). "Properties of Ultra-High Performance Fiber Reinforced Cementitious Composites made with Gypsum-Contaminated Aggregates and Cured at Normal and Elevated Temperatures." Construction and Building Materials, vol. 93: pp. 427-438. 40. Ghafari, E., Costa, H. and Júlio, E. (2015). "Statistical mixture design approach for ecoefficient UHPC." Cement and Concrete Composites, vol. 55: pp. 17-25. 41. Ghandehari, M., Behnood, A., Khanzadi, M. (2010). "Residual Mechanical Properties of HighStrength Concretes after Exposure to Elevated Temperatures." Journal of Materials in Civil Engineering, vol. 22(1): pp. 59-64. 42. Graybeal, B.A. (2015). "Compression Testing of Ultra-High-Performance Concrete." Advances in Civil Engineering Materials, vol. 4.2: pp. 102-112. 43. Graybeal, B.A. (2014). "Tensile Mechanical Response of Ultra-High-Performance Concrete." Advances in Civil Engineering Materials, vol. 4.2: pp. 62-74. 44. Graybeal, B., Davis, M. (2008). "Cylinder Or Cube: Strength Testing of 80 to 200 MPa (11.6 to 29 Ksi) Ultra-High-Performance Fiber-Reinforced Concrete." ACI Materials Journal, vol. 105(6): pp. 603-609. 45. Gu, C.P., Ye, G., Sun, W. (2015). "Ultrahigh Performance Concrete-Properties, Applications and Perspectives." Science China Technological Sciences, vol. 58(4): pp. 587-599. 46. Hager, I., Tracz, T., Śliwiński, J., Krzemień, K. (2016). "The influence of aggregate type on the physical and mechanical properties of high-performance concrete subjected to high temperature: Influence of aggregate type on HPC subjected to high temperature." Fire and Materials, vol. 40(5): pp. 668-682. 47. Hager, I., Zdeb, T., Krzemień, K. (2013). "The Impact of the Amount of Polypropylene Fibres on Spalling Behaviour and Residual Mechanical Properties of Reactive Powder Concretes." MATEC Web of Conferences, vol. 6: pp. 2003. 135 48. Hassan, A.M.T., Jones, S.W., Mahmud, G.H. (2012). "Experimental test methods to determine the uniaxial tensile and compressive behaviour of ultra high performance fibre reinforced concrete (UHPFRC).” Construction and Building Materials, vol. 37: pp. 874-882. 49. Heinz, D., Dehn, F., Urbonas, L. (2004). “Fire Resistance of Ultra High Performance Concrete (UHPC) – Testing of Laboratory Samples and Columns under Load.” International Symposium on Ultra High Performance Concrete, Kassel, Germany, September 13-15. 50. Hertz, K.D. (2005). "Concrete Strength for Fire Safety Design." Magazine of Concrete Research, vol. 57(8): pp. 445-453. 51. Hertz, K.D. (2003). "Limits of Spalling of Fire-Exposed Concrete." Fire Safety Journal, vol. 38(2): pp. 103-116. 52. Hertz, K.D., Sørensen, L.S. (2005). "Test Method for Spalling of Fire Exposed Concrete." Fire Safety Journal, vol. 40(5): pp. 466-476. 53. Hertz, K. (1984). “Explosion of silica-fume concrete.” Fire Safety Journal, vol. 8(1): pp. 77. 54. Ingason, H. (2004) "Fire development in catastrophic tunnel fires (CTF)." SP RAPPORTSTATENS PROVNINGSANSTALT, International Symposium on Catastrophic Tunnel Fires (CTF), Boras, Sweden, November 20-21, 2003: pp. 31-48. 55. Jagannathan, D. (2013). “Calcium-Silicate-Hydrate in cementitious systems: chemomechanical correlations, extreme temperature behavior, and kinetics and morphology of in-situ formation.” Doctoral dissertation, Massachusetts Institute of Technology. 56. Jang, H., So, H., So, S. (2016). The properties of reactive powder concrete using PP fiber and pozzolanic materials at elevated temperature.” Journal of Building Engineering, vol. 8: pp. 225-230. 57. Ju, Y., Wang, L., Liu, H., Tian, K. (2015). "An Experimental Investigation of the Thermal Spalling of Polypropylene-Fibered Reactive Powder Concrete Exposed to Elevated Temperatures." Science China Technological Sciences, vol. 23: pp. 2022-2053. 58. Ju, Y. Liu, H., Liu, J., Tian, K., Wei, S., Hao, S. (2011). "Investigation on Thermophysical Properties of Reactive Powder Concrete." Science China Technological Sciences, vol. 54(12): pp. 3382-3403. 59. Ju, Y., Liu, H., Tian, K., Wang, L., Ge, Z. (2013). "An Investigation on Micro Pore Structures and the Vapor Pressure Mechanism of Explosive Spalling of RPC Exposed to High Temperature." Science China Technological Sciences, vol. 56(2): pp. 458-470. 136 60. Kalifa, P., Menneteau, F.D., Quenard, D. (2000). "Spalling and Pore Pressure in HPC at High Temperatures." Cement and Concrete Research, vol. 30(12): pp. 1915-1927. 61. Kamen, A., Denarié, E., Brühwiler, E. (2007). "Thermal Effects on Physico-Mechanical Properties of Ultra-High-Performance Fiber-Reinforced Concrete." ACI Materials Journal, vol. 104(4): pp. 415-423. 62. Khaliq, W. (2012). “Performance characterization of high performance concretes under fire conditions.” Doctoral dissertation, Michigan State University. 63. Khoury, G.A. (2000). "Effect of fire on concrete and concrete structures." Progress in Structural Engineering and Materials, vol. 2.4: pp. 429-447. 64. Kim, Y., Kim, G., Lee, T. (2009). "Mechanical properties of high-strength concrete subjected to high temperature by stressed test." Transactions of Nonferrous Metals Society of China, vol. 19: pp. s128-s133. 65. Klingsch, E. (2014). "Explosive spalling of concrete in fire." Doctoral dissertation, ETH Zurich. 66. Klingsch, E., Frangi, F. (2011). "Experimental analysis on changes of the porosity of ultrahigh performance concrete at elevated temperatures." 2nd International RILEM Workshop on Concrete Spalling due to Fire Exposure. RILEM Publications SARL. 67. Ko, J., Ryu, D., Noguchi, T. (2011). "The Spalling Mechanism of High-Strength Concrete Under Fire." Magazine of Concrete Research, vol. 63(5): pp. 357-370. 68. Kodur, V. (2014). “Properties of Concrete at Elevated Temperatures.” ISRN Civ. Eng. pp. 115. 69. Kodur, V.K.R., Phan, L. (2007). "Critical Factors Governing the Fire Performance of High Strength Concrete Systems." Fire Safety Journal, vol. 42(6): pp. 482-488. 70. Khaliq, W., Kodur, V.K.R. (2011). "Effect of High Temperature on Tensile Strength of Different Types of High-Strength Concrete." ACI Materials Journal, vol. 108(4): pp. 394. 71. Kodur, V., Khaliq, W. (2011). "Effect of Temperature on Thermal Properties of Different Types of High-Strength Concrete." Journal of Materials in Civil Engineering, vol. 23(6): pp. 793-801. 72. Kosmatka, S.H. Wilson, M.L. (2011). “Design and Control of Concrete Mixtures.” EB001, 15th edition, Portland Cement Association, Skokie, Illinois, USA, 460 pages. 137 73. Kusumawardaningsih, Y., Fehling, E., Ismail, M., Aboubakr, A.A.M. (2015). Tensile strength behavior of UHPC and UHPFRC. Procedia Engineering, vol. 125: pp. 1081-1086. 74. Li, H., Liu, G. (2016). "Tensile Properties of Hybrid Fiber-Reinforced Reactive Powder Concrete After Exposure to Elevated Temperatures." International Journal of Concrete Structures and Materials, vol. 10(1): pp. 29-37. 75. Li, Q., Yuan, G., Xu, Z., Dou, T. (2014). "Effect of elevated temperature on the mechanical properties of high-volume GGBS concrete." Magazine of Concrete Research, vol. 66(24): pp. 1277-1285. 76. Li, Z., Venkata, H.K., Rangaraju, P.R. (2015). "Influence of Silica flour–silica Fume Combination on the Properties of High Performance Cementitious Mixtures at Ambient Temperature Curing." Construction and Building Materials, vol. 100: pp. 225-233. 77. Lie, T.T., Kodur, V.K.R. (1996). "Thermal and mechanical properties of steel-fibre-reinforced concrete at elevated temperatures." Canadian Journal of Civil Engineering, vol. 23(2): pp. 511517. 78. Lim, J., Moon, K., Falchetto, A.C., Jeong, J. (2016). "Testing and Modelling of HygroThermal Expansion Properties of Concrete." KSCE Journal of Civil Engineering, vol. 20(2): pp. 709-717. 79. Liu, C.T., Huang, J.S. (2009). "Fire performance of highly flowable reactive powder concrete." Construction and Building Materials, vol. 23.5: pp. 2072-2079. 80. Magureanu, C., Sosa, I., Negrutiu, C., Heghes, B. (2012). "Mechanical Properties and Durability of Ultra-High-Performance Concrete." ACI Materials Journal, vol. 109(2): pp. 177. 81. Mindeguia, J., Carré, H., Pimienta, P., La Borderie, C. (2015). "Experimental Discussion on the Mechanisms Behind the Fire Spalling of Concrete." Fire and Materials, vol. 39(7): pp. 619635. 82. Naser, M. Z., and Kodur, V.K.R. (2015). “A probabilistic assessment for classification of bridges against fire hazard.” Fire Safety Journal, vol. 76: pp. 65-73. 83. National Fire Data Center (U.S.) (2017). “Fire in the United States, 2005-2014.” Emmitsburg, MD: United States Fire Administration, National Fire Data Center. 84. Nazri, F.M., Jaya, R.P., Abu Bakar, B.H., Ahmadi, R. (2017). "Fire resistance of ultra-high performance fibre reinforced concrete due to heating and cooling." MATEC Web of Conferences. 87. EDP Sciences. 138 85. Nilson, A.H., Darwin, D., Dolan, C.W. (2010). “Design of Concrete Structures.” McGrawHill, New York, New York. 86. Peng, G.F., Yang, J., Long, Q.Q., Nin, X.J., Zeng, Q.P. (2016). “Comparison between UltraHigh-Performance Concretes with Recycled Steel Fiber and Normal Industrial Steel Fiber.” Fourth International Conference on Sustainable Construction Materials and Technologies, August 7-11, 2016. 87. Peng, G., Kang, Y., Huang, Y., Liu, X. & Chen, Q. (2012). "Experimental Research on Fire Resistance of Reactive Powder Concrete." Advances in Materials Science and Engineering, vol. 2012: pp. 1-6. 88. Phan, L.T. (1996). “Fire performance of high-strength concrete: A report of the state-of-the art.” US Department of Commerce, Technology Administration, National Institute of Standards and Technology, Office of Applied Economics, Building and Fire Research Laboratory, 1996. 89. Phan, L.T. (2008). "Pore Pressure and Explosive Spalling in Concrete." Materials and Structures, vol. 41(10): pp. 1623-1632. 90. Prem, P.R., Bharatkumar, B.H., Iyer, N.R. (2013). "Influence of Curing Regimes on Compressive Strength of Ultra High Performance Concrete." Sadhana, vol. 38(6): pp. 14211431. 91. Prem, P.R., Bharatkumar, B.H., Iyer, N.R. (2012). “Mechanical properties of Ultra High Performance Concrete.” International Journal of Civil, Environmental, Structural, Construction and Architectural Engineering, vol. 6(8): pp. 676-685. 92. Rahman, S., Molyneaux, T., Patnaikuni, I. (2005). "Ultra High Performance Concrete: Recent Applications and Research." Australian Journal of Civil Engineering, vol. 2(1): pp. 13. 93. Reda, M.M., Shrive, N.G., Gillott, J.E. (1999). "Microstructural investigation of innovative UHPC." Cement and Concrete Research, vol. 29(3): pp. 323-329. 94. Ren, W., Xu, J., Su, H. (2016). "Dynamic compressive behaviour of concrete after exposure to elevated temperatures." Materials and Structures, vol. 49(8): pp. 3321-3334. 95. Richard, P., Cheyrezy, M. (1995). "Composition of Reactive Powder Concretes." Cement and Concrete Research, vol. 25(7): pp. 1501-1511. 96. RILEM Technical Committee 200-HTC. (2007). “Recommendation of RILEM TC 200-HTC: mechanical concrete properties at high temperatures – modelling and applications: Part 1: Introduction-General presentation.” Mater. Struct., vol. 40: pp. 841-853. 139 97. RILEM Technical Committee 200-HTC. (2007). “Recommendation of RILEM TC 200-HTC: mechanical concrete properties at high temperatures—modelling and applications: Part 2: Stress–strain relation.” Mater. Struct., vol. 40: pp. 855–864. 98. Russell, H.G., Graybeal, B.A. (2013). “Ultra-High Performance Concrete: A State-Of-The-Art Report for the Bridge Community.” U.S. Department of Transportation, Federal Highway Administration, Research, Development, and Technology, Turner-Fairbank Highway Research Center, McLean, VA, 2013. 99. Sanchayan, S., Foster, S.J. (2016). "High Temperature Behaviour of Hybrid steel–PVA Fibre Reinforced Reactive Powder Concrete." Materials and Structures, vol. 49(3): pp. 769-782. 100. Sarhat, S.R., Sherwood, E.G. (2013). "Residual Mechanical Response of Recycled Aggregate Concrete after Exposure to Elevated Temperatures." Journal of Materials in Civil Engineering, vol. 25(11): pp. 1721-1730. 101. Schrefler, B.A., Majorana, C.E., Khoury, G.A., Gawin, D. (2002). "Thermo-hydromechanical modelling of high performance concrete at high temperatures." Engineering Computations, vol. 19.7: pp. 787-819. 102. So, H., Jang, H., Khulgadai, J., So, S. (2015). "Mechanical Properties and Microstructure of Reactive Powder Concrete using Ternary Pozzolanics Materials at Elevated Temperature." KSCE Journal of Civil Engineering, vol. 19(4): pp. 1050-1057. 103. So, H., Yi, J., Khulgadai, J., So, S. (2014). "Properties of Strength and Pore Structure of Reactive Powder Concrete Exposed to High Temperature." ACI Materials Journal, vol. 111(3): pp. 335. 104. Soliman, A.M., Nehdi, M.L. (2011). "Effect of Drying Conditions on Autogenous Shrinkage in Ultra-High Performance Concrete at Early-Age." Materials and Structures, vol. 44(5): pp. 879-899. 105. Sultan, M.A., Kodur, V.K.R. (2003). "Effect of Temperature on Thermal Properties of HighStrength Concrete." Journal of Materials in Civil Engineering, vol. 15(2): pp. 101-107. 106. Tai, Y.S., Pan, H.H., Kung, Y.N. (2011). "Mechanical Properties of Steel Fiber Reinforced Reactive Powder Concrete Following Exposure to High Temperature Reaching 800 °C." Nuclear Engineering and Design, vol. 241(7): pp. 2416-2424. 107. Ulm, F.J. (2008). “What's the matter with concrete?” Atti del XX Convegno Nazionale del Gruppo Italiano Frattura, vol. 3. 140 108. Voit, K., Kirnbauer, J. (2014). "Tensile Characteristics and Fracture Energy of Fiber Reinforced and Non-Reinforced Ultra High Performance Concrete (UHPC)." International Journal of Fracture, vol. 188(2): pp. 147-157. 109. Wang, D., Shi, C., Wu, Z., Xiao, J., Huang, Z., Fang, Z. (2015). "A review on ultra high performance concrete: Part II. Hydration, microstructure and properties." Construction and Building Materials, vol. 96: pp. 368-377. 110. Wang, J.J., Ren, F., DiPaolo, B.P. (2013). "Thermal Expansion Study and Microstructural Characterization of High-Performance Concretes." Journal of Materials in Civil Engineering, vol. 25.10: pp. 1574-8. 111. Wang, R., Gao, X. (2016). "Relationship between Flowability, Entrapped Air Content and Strength of UHPC Mixtures Containing Different Dosage of Steel Fiber." Applied Sciences, vol. 6(8): pp. 216. 112. Watanabe, K., Bangi, M.R., Horiguchi, T. (2013). "The effect of testing conditions (hot and residual) on fracture toughness of fiber reinforced high-strength concrete subjected to high temperatures." Cement and Concrete Research, vol. 51: pp. 6-13. 113. Way, R.T., Wille, K. (2015). "Effect of Heat-Induced Chemical Degradation on the Residual Mechanical Properties of Ultrahigh-Performance Fiber-Reinforced Concrete." Journal of Materials in Civil Engineering, vol. 28.4. 114. Wille, K., Naaman, A.E., Parra-Montesinos, G.J. (2011). "Ultra-High Performance Concrete with Compressive Strength Exceeding 150 MPa (22 ksi): A Simpler Way." ACI Materials Journal, vol. 108(1): pp. 46-54. 115. Xiao, R., Deng, Z., Shen, C. (2014). “Properties of Ultra High Performance Concrete Containing Superfine Cement and without Silica Fume." Journal of Advanced Concrete Technology, vol. 12(2): pp. 73-81. 116. Xiong, M.X., Liew, R.Y.J. (2015). “Spalling behavior and residual resistance of fibre reinforced Ultra-High performance concrete after exposure to high temperatures.” Mater. Construction, vol. 65: pp. e071. 117. Yang, S.L., Millard, S.G., Soutsos, M.N., Barnett, S.J., Le, T.T. (2009). "Influence of aggregate and curing regime on the mechanical properties of ultra-high performance fibre reinforced concrete (UHPFRC)." Construction and Building Materials, vol. 23(6): pp. 22912298. 141 118. Yazıcı, H., Yardımcı, M.Y., Yiğiter, H., Aydın, S., Türkel, S. (2010). "Mechanical Properties of Reactive Powder Concrete Containing High Volumes of Ground Granulated Blast Furnace Slag." Cement and Concrete Composites, vol. 32(8): pp. 639-648. 119. Yazıcı, H., Yardımcı, M.Y., Aydın, S., Karabulut, A.Ş. (2009). “Mechanical Properties of Reactive Powder Concrete Containing Mineral Admixtures Under Different Curing Regimes." Construction and Building Materials, vol. 23(3): pp. 1223-1231. 120. Ye, H., Feng, N., Ling-hu, Y., Ran, Z., Lin, L., Qi, S., Dong, Y. (2012). "Research on Fire Resistance of Ultra-High-Performance Concrete." Advances in Materials Science and Engineering, vol. 2012: pp. 1-7. 121. Youssef, M.A., Moftah, M. (2007). "General stress–strain relationship for concrete at elevated temperatures." Engineering Structures, vol. 29(10): pp. 2618-2634. 122. Yu, K., Yu, J., Lu, Z., Chen, Q. (2016) "Fracture properties of high-strength/highperformance concrete (HSC/HPC) exposed to high temperature." Materials and Structures, vol. 49(11): pp. 4517-4532. 123. Zdeb, T. (2013). “Ultra-high performance concrete – properties and technology.” Bull. Pol. Acad. Sci. Tech. Sci., vol. 61: pp. 183–193. 124. Zdeb, T. (2017). "An Analysis of the Steam Curing and Autoclaving Process Parameters for Reactive Powder Concretes." Construction and Building Materials, vol. 131: pp. 758-766. 125. Zheng, W., Luo, B., Lu, S. (2014a). "Rezistenta La Compresiune Si Încovoiere a Betoanelor Cu Continut De Pulberi Reactive Si Fibre Hibride La Temperaturi înalte/compressive and Tensile Strengths of Reactive Powder Concrete with Hybrid Fibres at Elevated Temperatures." Revista Romana de Materiale, vol. 44(1): pp. 36. 126. Zheng, W., Luo, B., Wang, Y. (2013). "Compressive and Tensile Properties of Reactive Powder Concrete with Steel Fibres at Elevated Temperatures." Construction and Building Materials, vol. 41: pp. 844-851. 127. Zheng, W., Luo, B., Wang, Y. (2014b). "Microstructure and Mechanical Properties of RPC Containing PP Fibres at Elevated Temperatures." Magazine of Concrete Research, vol. 66(8): pp. 397-408. 128. Zheng, W., Luo, B., Wang, Y. (2015). "Stress–strain Relationship of Steel-Fibre Reinforced Reactive Powder Concrete at Elevated Temperatures." Materials and Structures, vol. 48(7): pp. 2299-2314. 142 129. Zheng, W., Li, H., Wang, Y. (2012). "Compressive stress–strain Relationship of Steel FiberReinforced Reactive Powder Concrete After Exposure to Elevated Temperatures." Construction and Building Materials, vol. 35: pp. 931-940. 143